Page 16
nano purification solutions.
17-110-0140
• The dew-point is displayed on the control panel. When the dew-point displayed is better
than -54°F PDP the dryer will switch into economy mode and stop cycling. When the
dew-point degrades to -43°F the dryer will restart cycling ensuring the dew-point is
maintained at or better than -40°F.
• If the dryer fails to achieve dew-point (falls below -22°F) the alarm output will be
indicated on the front screen and the remote alarm output will activate.
• Close the inlet and outlet valves.
• When the dryer is fully depressurized, isolate from the power supply.
• Cycle the dryer at least twice to ensure the dryer exhausts and is completely
depressurized.
• When fully depressurized the ‘clicking’ of the exhaust valves will be heard but
no air exhausted.
12.3. Monitoring dryer performance (Energy saving option)
12.4. Shutdown Procedure
The dryer will still be pressurized! In order to depressurize the dryer;
ensure the dryer is isolated from the compressed air supply source:
SERVICE L.E.D
DISPLAY PANEL
OPERATION L.E.D
HOURS RUN / DEW-POINT
COLUMN A / B ONLINE
ILLUMINATED WHEN
SERVICE REQUIRED
ILLUMINATED WHEN
IN OPERATION
Beware this is only an example as the dew-point set-points and alarms are
adjustable through the display panel.