Wiring
FP0
7 - 3
Matsushita Automation Controls
7.1 Safety Instructions
7.1
Safety Instructions
In certain applications, malfunction may occur for the following reasons:
D
Power ON timing differences between the FP0 control unit and I/O or
motorized devices
D
An operation time lag when a momentary power drop occurs
D
Abnormality in the FP0 unit, power supply circuit, or other devices
In order to prevent a malfunction resulting in system shutdown choose the adequate
safety circuits or other safety measures listed in the following:
7.1.1
Interlock Circuit
When a motor clockwise/counter-clockwise operation is controlled, provide an interlock
circuit that prevents clockwise and counter-clockwise signals from inputting into the
motor at the same time.
7.1.2
Emergency Stop Circuit
Add an emergency stop circuit to controlled devices in order to prevent a system
shutdown or an irreparable accident when malfunction occurs.
7.1.3
Start Up Sequence
The FP0 should be operated after all of the outside devices are energized. To keep this
sequence, the following measures are recommended:
D
Set the mode switch from PROG. mode to RUN mode after power is
supplied to all of the outside devices
D
Program the FP0 so as to disregard the inputs and outputs until the
outside devices are energized
.
Note
When stopping the operation of FP0 also, have the I/O devices
turned OFF after the FP0 has stopped operating.
.
next page
Содержание FP0 Series
Страница 1: ...PROGRAMMABLE CONTROLLER FP0 Hardware is a global brand name of Matsushita Electric Works...
Страница 12: ...Overview FP0 1 2 Matsushita Automation Controls...
Страница 20: ...Overview FP0 1 10 Matsushita Automation Controls 1 4 Programming Tools...
Страница 76: ...Analog I O Unit FP0 4 2 Matsushita Automation Controls...
Страница 94: ...Analog I O Unit FP0 4 20 Matsushita Automation Controls 4 7 Averaging Function...
Страница 96: ...I O Allocation FP0 5 2 Matsushita Automation Controls...
Страница 102: ...Installation FP0 6 2 Matsushita Automation Controls...
Страница 112: ...Installation FP0 6 12 Matsushita Automation Controls 6 5 Installation Using FP0 Flat Type Mounting Plate...
Страница 114: ...Wiring FP0 7 2 Matsushita Automation Controls...
Страница 134: ...Wiring FP0 7 22 Matsushita Automation Controls 7 9 Wiring the RS232C Port...
Страница 136: ...Connecting the I O P Display Panel FP0 8 2 Matsushita Automation Controls...
Страница 141: ...Chapter 9 Trial Operation 9 1 Before Turning ON the Power 9 3 9 2 Turning the Power ON 9 4...
Страница 142: ...Trial Operation FP0 9 2 Matsushita Automation Controls...
Страница 146: ...Self Diagnostic and Troubleshooting FP0 10 2 Matsushita Automation Controls...
Страница 160: ...Self Diagnostic and Troubleshooting FP0 10 16 Matsushita Automation Controls 10 3 Error Codes...
Страница 162: ...Dimensions FP0 A 2 Matsushita Automation Controls...
Страница 172: ...Record of changes FP0 R 2 Matsushita Automation Controls...