FP0 A/D Converter Unit
4.1
I/O Number of A/D Converter Unit
4-3
Matsushita Electric Works (Europe) AG
Conversion data switch flags
The resolution of the A/D converter unit is 12 bits, but when data is transferred to the
control unit, it is converted to 16–bit data. Therefore, although the WX2 data requires no
processing, for the WX3 data, the top two bits are used as conversion data switching
flags. Accordingly, the top two bits are processed as follows.
When the A/D conversion data is negative “–”, the WX2 and WX3 data become two’s
complement.
In other words, bit C to bit F of WX2 and bit C to bit D of WX3 become “1”.
Also, because the top two bits of WX3 are used as conversion data switch flags, masking
is required so that the bits are “00” when the conversion data is positive “+”, and “11”
when the conversion data is negative “–”.
Ch3 data
WX3
→
Data after masking
1
0100000000000001
→
0000000000000001
–1
0111111111111111
→
1111111111111111
Conversion data switch flags
Mask applied to the above values
Содержание FP0-A80
Страница 4: ...Table of Contents FP0 A D Converter Unit ii Matsushita Electric Works Europe AG...
Страница 5: ...Chapter 1 Parts and Terminology...
Страница 9: ...Chapter 2 Wiring and Input Range Setting Switch...
Страница 12: ...FP0 A D Converter Unit Wiring and Input Range Setting Switch 2 4 Matsushita Electric Works Europe AG...
Страница 13: ...Chapter 3 A D Conversion Characteristics...
Страница 19: ...Chapter 4 I O Allocation and Program...
Страница 25: ...FP0 A D Converter Unit 4 2 Program of A D Converter Unit 4 7 Matsushita Electric Works Europe AG...
Страница 27: ...Chapter 5 Specifications and Dimensions...
Страница 32: ...FP0 A D Converter Unit Specifications and Dimensions 5 6 Matsushita Electric Works Europe AG...
Страница 34: ...Index FP0 A D Converter Unit Matsushita Electric Works Europe AG I 2...
Страница 35: ...Record of Changes Manual No Date Description of changes ARCT1F321END JUNE 2001 First European Edition...