FP0 A/D Converter Unit
I/O Allocation and Program
4-2
Matsushita Electric Works (Europe) AG
4.1
I/O Number of A/D Converter Unit
I/O number of A/D converter unit
FP0 Control unit
WX2
WX3
WY2
WY3
WX4
WX5
WY4
WY5
WX6
WX7
WY6
WY7
A combined maximum of three A/D converter
units and other expansion units can be con-
nected to one control unit. WX and WY are
allocated two words each (2 x 16 bits each).
First
expansion
Second
expansion
Third
expansion
With the setup illustrated in the diagram above, the data for each channel is allocated
as I/O data as indicated in the table below.
A/D converter unit input channel
First expansion
Second expansion
Third expansion
ch0, 2, 4, 6
(Each 16 points)
WX2
(X20 to X2F)
WX4
(X40 to X4F)
WX6
(X60 to X6F)
ch1, 3, 5, 7
(Each 16 points)
WX3
(X30 to X3F)
WX5
(X50 to X5F)
WX7
(X70 to X7F)
Example of I/O allocation
The diagram below shows you the allocation of each channel’s conversion data, WX2
and WX3 when this unit is connected to the first expansion.
X
3
F
X
3
E
X
3
D
X
3
C
X
3
B
X
3
A
X
3
9
X
3
8
X
3
7
X
3
6
X
3
5
X
3
4
X
3
3
X
3
2
X
3
1
X
3
0
X
2
F
X
2
E
X
2
D
X
2
C
X
2
B
X
2
A
X
2
9
X
2
8
X
2
7
X
2
6
X
2
5
X
2
4
X
2
3
X
2
2
X
2
1
X
2
0
Bit F
A
1
A
0
Conversion data of ch1, 3, 5, 7
(14 bit with sign)
Conversion data of ch0, 2, 4, 6
(16 bit with sign)
Conversion data switch flag
Bit 0
Bit F
Bit 0
A1
A0
WX3
WX2
0
0
ch1 data
ch0 data
0
1
ch3 data
ch2 data
1
0
ch5 data
ch4 data
1
1
ch7 data
ch6 data
Содержание FP0-A80
Страница 4: ...Table of Contents FP0 A D Converter Unit ii Matsushita Electric Works Europe AG...
Страница 5: ...Chapter 1 Parts and Terminology...
Страница 9: ...Chapter 2 Wiring and Input Range Setting Switch...
Страница 12: ...FP0 A D Converter Unit Wiring and Input Range Setting Switch 2 4 Matsushita Electric Works Europe AG...
Страница 13: ...Chapter 3 A D Conversion Characteristics...
Страница 19: ...Chapter 4 I O Allocation and Program...
Страница 25: ...FP0 A D Converter Unit 4 2 Program of A D Converter Unit 4 7 Matsushita Electric Works Europe AG...
Страница 27: ...Chapter 5 Specifications and Dimensions...
Страница 32: ...FP0 A D Converter Unit Specifications and Dimensions 5 6 Matsushita Electric Works Europe AG...
Страница 34: ...Index FP0 A D Converter Unit Matsushita Electric Works Europe AG I 2...
Страница 35: ...Record of Changes Manual No Date Description of changes ARCT1F321END JUNE 2001 First European Edition...