FP0 A/D Converter Unit
A/D Conversion Characteristics
3-4
Matsushita Electric Works (Europe) AG
Voltage range: –10 to +10V DC input
2000
1000
0
–1000
–2000
–10
–5
5
10 (V)
(K)
Analog input range
A/D conversion value
Corresponding table of A/D conversion values
Input voltage (V)
A/D conversion value
–10.0
–2000
–7.5
–1500
–5.0
–1000
–2.5
–500
0.0
0
+2.5
+500
+5.0
+1000
+7.5
+1500
+10.0
+2000
Processing if the range is exceeded
Input value
Converted value
–10V or less
–2000
+10V or more
+2000
Voltage range: –100 to +100mV DC input
2000
1000
0
–1000
–2000
–100
–50
50
100 (mV)
(K)
Analog input range
A/D conversion value
Содержание FP0-A80
Страница 4: ...Table of Contents FP0 A D Converter Unit ii Matsushita Electric Works Europe AG...
Страница 5: ...Chapter 1 Parts and Terminology...
Страница 9: ...Chapter 2 Wiring and Input Range Setting Switch...
Страница 12: ...FP0 A D Converter Unit Wiring and Input Range Setting Switch 2 4 Matsushita Electric Works Europe AG...
Страница 13: ...Chapter 3 A D Conversion Characteristics...
Страница 19: ...Chapter 4 I O Allocation and Program...
Страница 25: ...FP0 A D Converter Unit 4 2 Program of A D Converter Unit 4 7 Matsushita Electric Works Europe AG...
Страница 27: ...Chapter 5 Specifications and Dimensions...
Страница 32: ...FP0 A D Converter Unit Specifications and Dimensions 5 6 Matsushita Electric Works Europe AG...
Страница 34: ...Index FP0 A D Converter Unit Matsushita Electric Works Europe AG I 2...
Страница 35: ...Record of Changes Manual No Date Description of changes ARCT1F321END JUNE 2001 First European Edition...