Specifications
FP0 RTD Unit
Parameter Specification
Resolution 0.1
-200.0 to 500.0°C:
-328.0 to 800.0°F:
-2000 to 5000
-3280 to 8000
Pt100
Resolution 0.01
-80.00 to 80.00°C:
-80.00 to 80.00°F:
-8000 to 8000
-8000 to 8000
Resolution 0.1
-200.0 to 300.0°C:
-328.0 to 572.0°F:
-2000 to 3000
-3280 to 5720
Pt1000
Resolution 0.01
-80.00 to 80.00°C:
-80.00 to 80.00°F:
-8000 to 8000
-8000 to 8000
Resolution 0.1
-30.0 to 150.0°C:
-22.0 to 302.0°F:
-300 to 1500
-220 to 3020
Ni1000
Resolution 0.01
-30.00 to 80.00°C:
-22.00 to 80.00°F:
-3000 to 8000
-2200 to 8000
Resolution 1
20 to 2200
Ω
:
20 to 2200
Resistor
Resolution 0.1
20.0
Ω
to 1630.0
Ω
:
200 to 16300
Digital output
When out of range or RTD is broken: 8191 or 16383 (see note 2)
Until temperature can be measured at initial startup: see note 3
Resolution
0.1K/°F, 0.01K/°F
Sampling cycle
0.1 or 1s for all channels (see note 4)
Ambient temp.: 25°C
0.3K (-10°C to +30°C)
0.2%/1.4K (-200°C to +500°C)
Cycle 1s
Whole temp. range
0.35%/2.5K
Pt100
Cycle 0.1s
Whole temp. range
0.5%/3.5K
Ambient temp.: 25°C
0.3K (-10°C to +30°C)
0.2%/1.0K (-200°C to +300°C)
Cycle 1s
Whole temp. range
0.35%/1.7K
Pt1000
Cycle 0.1s
Whole temp. range
0.5%/2.5K
Cycle 1s
Whole temp. range
1K
Ni1000
Cycle 0.1s
Whole temp. range
2K
Cycle 1s
Whole temp. range
1
Ω
(20 to 2200
Ω
)
Accuracy
Resistor
Cycle 0.1s
Whole temp. range
2
Ω
(20 to 2200
Ω
)
Insulation
method
none
16 points for WX2, 4, 6
Analog input CH0, 2, 4 (WX2)
(see notes 5 and 6)
Input 32
points:
16 points for WX3, 5, 7
Analog input CH1, 3, 5 (WX3)
(see notes 5 and 6)
Input/output
points
Output
8 + 24 points (reserved)
NOTES
1. The measurement range available for degrees Celsius is larger than
for degrees Fahrenheit as the digital value (temperature value
displayed) for °F is higher than the one for °C.
2. When the RTD is broken, the digital value will change to 8191 or
16383. Use a program to avoid risks resulting from a broken RTD. A
broken RTD needs to be replaced.