FP0 RTD Unit
Unit Outline
1 Unit Outline
1.1 Functions
RTD input unit for the FP0/FP
Σ
control unit.
The temperature data obtained using the RTD (Resistance Temperature Detector) is
converted to the digital value to be read into the FP0/ FP
Σ
control unit.
Available RTD types
Pt100 (to IEC751), Pt1000 (to IEC751), Ni1000 (to DIN43760), and Resistor.
Temperature measurement ranges available
°C °F
RTD
Type
Resolution 0.1K
Resolution 0.01K
Resolution 0.1°F
Resolution 0.01°F
Pt100
-200.0 … +500.0
-80.00 … +80.00
-328.0 … +800.0
-80.00 … +80.00
Pt1000
-200.0 … +300.0
-80.00 … +80.00
-328.0 … +572.0
-80.00 … +80.00
Ni1000
-30.0 … +150.0
-30.00 … +80.00
-22.0 … +302.0
-22.00 … +80.00
Resistor measurement ranges available
Ω
RTD
Type
Resolution 1
Ω
Resolution
0.1
Ω
Resistor
20 … +2200
20.0 … 1630.0
Conversion to degrees Celsius or degrees Fahrenheit possible
The temperature data measured using the sensor is converted to degrees Celsius or degrees
Fahrenheit inside the FP0 RTD unit.
Broken-RTD detector attached
A broken RTD can be detected.
1.2 Product Number
Product name
RTD input points
Product number
Part number
FP0 RTD unit
6 points
FP0RTD6
AFP0430
1.3 Expansion Limit
Number
Up to 3 expansion units can be connected to the control unit.
Position
Always install the FP0 RTD unit the farthest to the right of the control unit.
1
Содержание FP Series
Страница 5: ......
Страница 9: ......
Страница 33: ...Dimensions FP0 RTD Unit 8 Dimensions 24...
Страница 36: ...Record of Changes Manual No Date Description of Changes ACGM0159V10END SEPT 2004 First Edition...