Conversion Characteristics
FP0 RTD Unit
4 Conversion Characteristics
NOTE
The measurement range available for degrees Celsius is larger than for degrees
Fahrenheit as the digital value (temperature value displayed) for °F is higher
than the one for °C.
4.1 Pt100
Input range:-200.0°C to 500.0°C/-328.0°F to 800.0°F, resolution: 0.1K/0.1°F
Conv
ert
ed
va
lu
e
Input value
Conv
ert
ed
va
lu
e
Input value
Correspondence table for A/D conversion values
Analog input
value (°C)
Digital output
value
Analog input
value (°F)
Digital output
value
-200.0 -2000
-328.0 -3280
+500.0 +5000
+800.0 +8000
Processing if the input value range is exceeded
Analog input
value (°C)
Digital output
value
Analog input
value (°F)
Digital output
value
-200.1 or less
-328.1 or less
+500.1 or more
+800.1 or more
RTD broken
8191
RTD
broken
8191
6