14 of 35
Opus Control Wiring and Programming Installation Manual
www.NabcoEntrances.com
P/N C-00139
Rev 3-9-18
SECTION 9.4: Output Settings
Output Setting
Parameter
Terminal
Default
Range
Description
Output 1
Terminal 7
Full Open
Fully Opened Position
Output doesn’t change state
Output 2
Terminal 13 Full Close
Fully Closed Position
Output changes when fully closed
Relay Output 3
Electric
Lock
Terminals
— —
Closing Status
Output changes when door is closing
Opening Status
Output changes when door is opening
Error State Output
Output changes when error detected
Recycle happened
Output changes when recycle occurs
Electric Strike Lock
Set for electric strike functionality
Electric Magnetic Lock
Set for Mag lock functionality
Air lock
Set for Air lock functionality
Breakout Pass through
Output changes when breakout occurs
Door Sequencing
Provision for door sequencing
Sensor Monitoring (N.O.) Normally open contacts for Monitoring
Sensor Monitoring (N.C.) Normally closed contacts for Monitoring
Trmn1 H PassThrough
Passes through a signal from Input H
Breakout PassThrough
Output changes status when breakout occurs
Bodyguard Output
Outputs data for bodyguard sensors and other
sensors that utilize same data
For Elite N Output
For Elite (N) sensor made by Optex. (Output 1 only)
Open Delay Timer N/A
0.4
0.1, 0.4, 1.5 sec
After Unlock Input
Delay time after activation to allow lock to unlock
before the door starts moving.
Only functional if Electric Lock is selected
Sequence
Delay Timer
N/A
0
0-10, 12, 15, 20, 25
Same as Open Timer
Amount of Hold Open time after deactivation in
seconds
Lock Condition
N/A
Every Fully
Closed
Every Fully Closed
One way/Night Only
Determines when the electric lock engages