background image

 

14 of 35

 

Opus Control Wiring and Programming Installation Manual 

www.NabcoEntrances.com

P/N C-00139 

Rev 3-9-18

SECTION 9.4: Output Settings

Output Setting

Parameter

Terminal

Default

Range

Description

Output 1 

Terminal 7

Full Open

Fully Opened Position

Output doesn’t change state

Output 2

Terminal 13 Full Close

Fully Closed Position

Output changes when fully closed

Relay Output 3

Electric

Lock

Terminals

— — 

Closing Status

Output changes when door is closing

Opening Status

Output changes when door is opening

Error State Output

Output changes when error detected

Recycle happened

Output changes when recycle occurs

Electric Strike Lock

Set for electric strike functionality

Electric Magnetic Lock

Set for Mag lock functionality

Air lock

Set for Air lock functionality

Breakout Pass through

Output changes when breakout occurs

Door Sequencing

Provision for door sequencing

Sensor Monitoring (N.O.) Normally open contacts for Monitoring
Sensor Monitoring (N.C.) Normally closed contacts for Monitoring
Trmn1 H PassThrough

Passes through a signal from Input H

Breakout PassThrough

Output changes status when breakout occurs

Bodyguard Output

Outputs data for bodyguard sensors and other 

sensors that utilize same data

For Elite N Output

For Elite (N) sensor made by Optex. (Output 1 only) 

Open Delay Timer N/A

0.4

0.1, 0.4, 1.5 sec

After Unlock Input

Delay time after activation to allow lock to unlock 

before the door starts moving.

Only functional if Electric Lock is selected

Sequence 

 

Delay Timer

N/A

0

0-10, 12, 15, 20, 25

Same as Open Timer

Amount of Hold Open time after deactivation in 

seconds

Lock Condition

N/A

Every Fully

Closed

Every Fully Closed

One way/Night Only

Determines when the electric lock engages

Содержание Opus Control

Страница 1: ...s operational WARNING Table of Contents CHAPTER 1 SAFETY 3 CHAPTER 2 SCOPE 4 SECTION 2 1 To the Installer 4 SECTION 2 2 Objective 4 CHAPTER 3 FEATURES 4 CHAPTER 4 SPECIFICATIONS 4 SECTION 4 1 General...

Страница 2: ...CTION 12 2 Activation using ON OFF Hold Open Switch 21 SECTION 12 3 Safety 22 SECTION 12 4 Safety with Monitoring 23 SECTION 12 5 Lock 24 SECTION 12 6 Standard Wiring for Single Full Automatic 25 SECT...

Страница 3: ...sult in seriouc personal or fatal injury When uncertain whether power supply is disconnected always verify using a voltmeter Do not place finger or uninsulated tools inside the electrical controller T...

Страница 4: ...ces at 1 877 622 2694 between 8 am 4 30 pm Central time for additional assistance SECTION 2 2 Objective The Opus Control is designed to be installed within the Header of X X New Swing and Folding Door...

Страница 5: ...mber Current Consumption Acuvision V 00202 80mA ea unit at 12VDC Optex Reaction V 00173 125mA Acusensor M A 01306 150mA Optex i one V 00055 130mA Radio Control Receiver 24 11467 50mA CX33 Logic Relay...

Страница 6: ...d is properly secured to the grounding screw or grounding wire whichever is provided Attention Insert all Incoming 120 VAC Power wires into the pre drilled Electric Service Access Hole located at the...

Страница 7: ...Communication 7 CN1 Power Connector 4 Rotary Dial 8 Fuse CHAPTER 7 THE ROTARY DIAL X X Push down on the Rotary Dial Long push 2 seconds to gain access to LCD Catagory Screens Short push under 2 second...

Страница 8: ...se Recycle Cnt Latest Recycle Posi on DN 1334 LEVEL 4 Push and Hold Rotary Dial 2 Sec Rotate Dial Rotate Dial Rotate Dial Short Push Figure 3 LCD Screen Transition SECTION 8 1 Level One Specification...

Страница 9: ...ke Learning Go to Se ng menu Reset to Default Set Yes No Passcode Stroke Learning Yes No Ac vate Passcode Rotate Dial Rotate Dial Rotate Dial Figure 6 Level Two Screen Attention To prevent tampering a...

Страница 10: ...Passcode 8 2 3 Stroke Learning Stroke Learning is used to measure from Fully Closed to Fully Open points in effort to determine where Check Points should happen Stroke Learning is also used to determ...

Страница 11: ...which Handing to enter Left or Right DN 0833 EXTERIOR BREAKOUT SIDE LEFT HAND RIGHT HAND Door Hand for Slide Doors Left Right Left From the Exterior Side of Building determine which Handing to enter L...

Страница 12: ...er Range Default Description Hold Close Force 0 3 0 0 OFF 3 Strongest Hold Close force Power Close Range No Power Close No Power Close Closing assisted by Motor to fight wind or stack pressure Whole C...

Страница 13: ...the door slams open No Sim Pair Setting Single Door Single Door Select type of Door Normal Sim Pair If selected before returning to last screen option to copy settings to other Control is given Double...

Страница 14: ...lock functionality Breakout Pass through Output changes when breakout occurs Door Sequencing Provision for door sequencing Sensor Monitoring N O Normally open contacts for Monitoring Sensor Monitoring...

Страница 15: ...side of Door If activated Opus will ignore the Activation Sensor while Door is moving This input is for the ASIAN market ONLY AsiaSpec_ExtActSwgSd Input 62 Open Timer N A Same as Open timer Same as Op...

Страница 16: ...ing N A Not Active Active Not Active Sensor monitoring function SWL Monitoring N A Not Active Active Not Active Sensor monitoring function If Monitoring is enabled for any input then the sensor MUST b...

Страница 17: ...Push Rotary Dial LEVEL 4 1 Rotate Dial to select Movement Se ng 2 Push Rotary Dial Back Check Speed 0 1 2 3 4 5 6 7 0 1 Slow 7 Fast Speed Ajustment 11 20 10 12 Push and Hold Rotary Dial 2 Sec SECTION...

Страница 18: ...en al Ac va on signals to open or signals to close 10 H Input H Programmable input 11 M0 Mode 0 When grounded puts door into One Way Mode Hold Open when grounded with M1 12 M1 Mode 1 When grounded put...

Страница 19: ...uen al Sequen al Ac va on signals to open or signals to close 10 H Input H Programmable input 11 M0 Mode 0 When grounded puts door into One Way Mode Hold Open when grounded with M1 12 M1 Mode 1 When g...

Страница 20: ...kout overhead swing side safety sensor Slide Door Sidelite Sensor 7 Out1 Programmable Output 5 6 7 2 8 12 14 11 13 9 10 1 2 3 4 5 6 7 3 4 1 2 3 4 5 6 7 1 2 3 4 2 3 4 1 N O COM N O COM Exterior Push Pl...

Страница 21: ...utput 5 2 8 12 14 11 13 9 10 1 2 3 4 5 6 7 3 4 1 5 6 7 1 2 3 4 2 3 4 1 N O COM N O COM Exterior Push Plate Interior Push Plate ALL DEVICES MUST BE N O DRY CONTACT 8 12 14 11 13 9 10 1 2 3 4 5 6 7 N O...

Страница 22: ...ty with Lockout overhead swing side safety sensor Slide Door Sidelite Sensor 7 Out1 Programmable Output NOTE For Safety Sensors equipped with a monitoring func on TERMINAL 7 should be connected to MON...

Страница 23: ...o BODYGUARD OUTPUT Please see programming instruc ons for details PWR PWR TEST TEST Door Mounted Approach Side Sensor N O COM PWR PWR TEST TEST N O COM PWR PWR TEST TEST 5 2 4 5 1 2 3 4 6 7 1 6 7 8 12...

Страница 24: ...13 12 11 10 9 8 7 6 5 4 3 2 1 Fail Secure Electric Strike Fail Secure Lock Shown Fail Safe and Mag Locks will use N C instead of N O Power Supply For Electric Strike N O COM N C Varistor MOV TVS DO N...

Страница 25: ...13 14 8 WHITE Rocker Switch P N A 00805 1 5 6 Door Mounted Approach Side Sensor Door Mounted Swing Side Sensor BLUE 8 12 14 11 13 9 10 1 5 7 2 3 4 6 Ac va on Sensor Overhead Swing Side Sensor if used...

Страница 26: ...ker Switch P N A 00805 1 5 6 Door Mounted Approach Side Sensor Door Mounted Swing Side Sensor BLUE 8 12 14 11 13 9 10 1 5 7 2 3 4 6 Ac va on Sensor Overhead Swing Side Sensor if used WARNING TOTAL POW...

Страница 27: ...0805 1 5 6 Door Mounted Approach Side Sensor Door Mounted Swing Side Sensor BLUE 8 12 14 11 13 9 10 1 5 7 2 3 4 6 Ac va on Sensor Overhead Swing Side Sensor if used WARNING TOTAL POWER CONSUMPTION OF...

Страница 28: ...OTAL POWER CONSUMPTION OF ALL SENSORS MUST NOT EXCEED 750 MA N O COM PWR PWR N O COM PWR PWR N O COM PWR PWR COM PWR PWR N O Door Mounted Approach Side Sensor Door Mounted Swing Side Sensor 5 2 4 1 2...

Страница 29: ...30 Clear A 70430 Dark Bronze RED BLACK 14 13 12 11 10 9 8 8 WHITE Off Hold Open On Off 14 13 12 11 10 9 8 8 14 BA break out input must be set to N C on the Opus Control is by default Panic Latch must...

Страница 30: ...LAY TIMER must be set to an appropriate me for the door to unlock before opening LOCK CONDITION must be set to ONE WAY NIGHT ONLY NOTE If the Rocker Switch is not being used Interior Ac va on connects...

Страница 31: ...mon for all above signals Example A Switch being used to turn ON OFF Power Close and Hold Close Programmable Terminal 10 Input H would be set to SPRING CLOSE ONLY 12 8 9 1011 1314 5 1 2 3 4 6 7 12 8 9...

Страница 32: ...t highlighted turn off power for at least 4 seconds then turn on again With the doorstill closed status should now show Fully Closed Must navigate back to the main screen as shown at right for an acti...

Страница 33: ...rive Circuit If the Drive Circuit detects an unusual state the Opus will stop door movement Possible causes are Abnormal voltage at Motor Circuit Abnormal current draw from motor Check all connections...

Страница 34: ...ROLLER OPUS W CHASSIS BRAKE 9 M 01072 HARNESS POWER MAGNUM BOARD 10 V 00713 Used on A 01249 FUSE 2 AMP 5X20MM 250V FAST ACTING 11 A 01249 Used on GT710 8710 only HARNESS MOTOR OPUS 710 12 A 01002 Retr...

Страница 35: ...10 7 M 01680 HARNESS OPUS CONTROL SIM PAIR 8 A 01098 CONTROLLER W BRAKE BOTTOM LOAD OPUS 9 M 01735 PLATE BOTTOM LOAD OPUS 10 A 01143 CONTROLLER W O BRAKE BOTTOM LOAD OPUS 11 A 01003 Not used on GT710...

Отзывы: