background image

Magnum IV Control Manual for Gyro Tech Swing Door Systems 

Page 7

 

www.NabcoEntrances.com

 

 

 

 

 

1/4/06 

CURRENT
LIMIT

MOTOR

J1

R28

MAGNUM IV

Fuse 2: 3A 120/240

DN0033

BLACK

RED

LED

TRANSFORMER

CAPACITOR

O

F

F

1

2

AUX

PWR

4

J2

3

J5

AC IN

F2

SW2

SW1

F1

RELAY

RELAY

J4

TDAS

SIGNAL
INPUT

TDPG

LCHK

CLOSE

Fuse 1: 0.5A 24 VAC

STOP

OPEN

BCHK

Wiring Connectors:

 

 

 

There are four connectors located on the control board labeled J2, J3, J4, and J5 (Figure 2).  There is a re-
settable fuse 1 (F1) and a replaceable fuse 2 (F2).   

 J1

 is the signal input.  It is a six-pin connector with a mating connector installed. 

1. 

Pin 1 - Safety with Lockout The wire to this pin is white. This is a lock out circuit so that 

 

 

the signal only works when the door is in the closed or fully open position.  The logic is 

 

 

turned off and on through back check and door closed switches. Completing the circuit 

 

 

from the common (pin 6) will prevent the door from opening or closing from a fully 

 

 

closed or fully open position. It is generally used for swing side presence detectors 

 

 

where the detector needs to be deactivated as the door sweeps across the detection zone.   

2. 

Pin 2 - Door Closed Switch The wire to this pin is orange. This circuit should be 
connected to the door closed switch to determine when the door is closed and out of the 
detection area of the presence sensor.   

3. 

Pin 3 - Back check Switch The wire to this pin is blue. This circuit should be connected 
to the back check switch to determine when the door is in back check .   

4. 

Pin 4 - Activation The wire to this pin is black. This circuit receives the activate signal 
from the actuating device when someone approaches.   

5. 

Pin 5 - Continuous Safety The wire to this pin is purple. This circuit is used with the 
ACUGARD 2 System, swing side floor mats, or other continuous safety systems.  
Completing the circuit from the common (pin 6) will stop the door during opening, 
prevent activation during closing, as well as prevent it from moving if it is fully open or 
closed.  This safety circuit is always active unlike the safety circuit described for pin 1.  

6. 

Pin 6 - Common The wire to this pin is red. This is the common, so connecting this red 
wire to any of the other five will cause that feature to be activated.  For example, 
connecting the red and blue will result in back check.  

 J2 

is the 24 VAC output to the actuating device.  It is a two-pin connector. 

1. 

This circuitry was designed to work with any sensor that operates on 24 VAC. Do not 

 

 

exceed 0.5 amp current draw. A greater that 0.5 amp current will cause the onboard 

 

 

re-settable fuse (F1) to trip until the situation is corrected. If a sensor requires a different 

 

 

operating voltage, a separate voltage module must be used to supply power to the 

 

 

sensor.   

Figure 2 – Magnum IV Control 

Adjustment potentiometers 

Current Limit Pot. 
Set this pot fully 
clockwise initially 

J1 

J5 

J2 

J4 

Diagnostic LED’s 

Dip Switches 

120 VAC fuse 

24 VAC 

re-settable fuse 

Slide switch UP for GT-500/710 
Slide switch DOWN for GT-300/400 

Braking module. 
Used to provide 
braking on closing 
cycle. Not used on 
GT-710.  

Содержание GYRO TECH Magnum IV Control

Страница 1: ...h Swing Door Operators Part Number 15 10682 1 4 06 Revision NABCO ENTRANCES Inc S82 W18717 Gemini Drive P O Box 906 Muskego WI 53150 Phone 877 622 2694 Fax 888 679 3319 Technical Assistance 866 622 83...

Страница 2: ...be performed by qualified electrical technicians and must comply with all applicable governing agency codes It is the responsibility of the installing door technician to install all warning and instru...

Страница 3: ...e 16 General Wiring Single Diagram Page 17 General Wiring Simultaneous Pair Page 18 Section B Retrofit Kit Manual Model 300 400 500 Swing Door System With Magnum IV Control Page 19 Tools required Page...

Страница 4: ...ts must be made by qualified NABCO trained technicians Overview Earlier versions of Gyro Tech GT300 GT400 GT500 and GT710 Swing Door Operators can be retrofitted with the newer Magnum IV Control Board...

Страница 5: ...rd can be ordered from Customer Service It is a valuable tool that provides a quick visual indication of signals being received by the control and is also compatible with earlier models of Magnum cont...

Страница 6: ...or mounted ACUGARD is not activated Fast Flashing Not applicable Slow Flashing The swing side door mounted ACUGARD is activated On Steady Close on Obstruction Current Limit activated LED on for 5 seco...

Страница 7: ...back check switch to determine when the door is in back check 4 Pin 4 Activation The wire to this pin is black This circuit receives the activate signal from the actuating device when someone approac...

Страница 8: ...250 volt fuse that protects the circuit board from voltage spikes and incorrect voltage being applied to the board Back Check This takes place from about the last 10 of sweep to the full open positio...

Страница 9: ...the controller will vary slightly as the voltage supplied to the unit varies due to fluctuations in building and electrical supply loads To allow for variations the manufacturer recommends adding 1 se...

Страница 10: ...k Clockwise rotation increases back check speed If back check is set too high the door will slam open The current limit will trip If back check is set too low the door will reach back check and stop G...

Страница 11: ...vation and cuts power to the motor if the motor current exceeds the setting It is used to set how much force the opening door will push on an encountered object before it recycles When the recycle is...

Страница 12: ...ered Check door activation device power consumption If power draw exceeds 0 5 amps at 24 VAC replace with lower draw sensor Motor spins when activated but door does not open 1 GT 500 Check polarity of...

Страница 13: ...or other accessories do not function while door is moving All units Connection of accessories was made to Safety w Lockout not Continuous Safety Rewire accessory to Continuous Safety connection Red 5...

Страница 14: ...T 300 GT 400 and GT 500 s provide the necessary latch check and back check limit switches the Magnum IV control requires for correct operation These switches are mounted on the top of the operator ass...

Страница 15: ...multaneous Pair door b Main Harness Assy Magnum Board Part 22 10065 for single door 22 10270 for Simultaneous Pair door c Magnum Board Harness for 300 400 500 Part 21 9934 FIGURE 7 WIRING HARNESSES FO...

Страница 16: ...ck between Terminal Block 3 violet and 5 red as shown in Figure 9 c Also cut the connectors off the Panic Latch harness and connect these wires to Continuous Safety input of Terminal Block Between Ter...

Страница 17: ...Brown Latch Check Limit Switch Part 22 10065 Harness Assy for Single Back Check Limit Switch Ter 5 Note Common connection 5 Red not shown for simplicity to Terminal 5 red to Terminal 5 red to Terminal...

Страница 18: ...ed Brown Black Black Black White Black Green Grounded Black White Neutral Black Hot Red Comm Blue N C Brown Part 21 9934 300 400 500 Harness for Magnum Board IF ROCKER SWITCH IS NOT REQUIRED CONNECT T...

Страница 19: ...0 seconds No adjustment Adjustable door action when detection continuous safety occurs allow door to stop creep open or creep closed No adjustment Automatic shut off of motor if door does not open wit...

Страница 20: ...22 10270 Main Harness Simultaneous Pair 1 With Terminal Block 4 21 9934 300 400 500 Harness Magnum Board 1 2 5 21 9933 Power Harness Single 1 6 14 5883 Power Harness Simultaneous Pair 1 7 14 3867 Mic...

Страница 21: ...ion of cams on right hand versus left hand operator FIGURE 14 BACK CHECK AND LATCH MICRO SWITCHES When the unit has a break out feature the panic breakout circuit must be connected to shut down the sy...

Страница 22: ...HARNESS Black Black Brown Brown DN0061 USE THESE CONNECTIONS ON INSWING DOORS WITH PANIC BREAKOUT DN0049 Panic Latch must be flipped Arrow marked EXT must point into the building Contacts must close w...

Страница 23: ...ug at the end of the main harness Figure 18 9 Connect the Rocker Switch to the terminal block of the main harness Figure 18 10 Connect the motor harness from J5 marked MOTOR on the Magnum IV board to...

Страница 24: ...115VAC 5A Part 21 9934 300 400 500 Harness for Magnum Board Red Comm Blue N C White Comm Green N C Black Brown Common N O Device Not Used Typical Mat or Wall Switch 24 VAC Input Typical Sensor Device...

Страница 25: ...9934 300 400 500 Harness for Magnum Board White Comm Green N C Latch Check Limit Switch Black Green When the unit has Panic Breakout feature Breakout Limit Switch Signals and Panic Latch Signals MUST...

Страница 26: ...perators This section details the installation and adjustments of the Magnum IV control in a GT 710 swing door unit Step 1 Install all components as per the applicable hardware installation manual Ste...

Страница 27: ...r Door Block Relay On Off WHITE Fuse 2 3A Relay 4 J5 J1 Selector Switches R13 R8 R21 Fuse 1 5A J4 J2 STOP OPEN BCHK R29 R40 R27 R24 LCHK R23 1 2 TDPG TDAS CLOSE CONNECT THE ACTIVATION SIGNALS TO RED O...

Страница 28: ...CK ACTIVATION 24VAC COMMON SAFETY WITH LOCKOUT CONTINUOUS SAFETY 24VAC HOT 24VAC NEUTRAL 6 BLACK 5 RED 4 WHITE 3 VIOLET 2 ORANGE 1 BROWN TERMINAL BLOCK 2 4 5 3 6 1 DN0053 J4 Transformer R23 1 6 3 5 4...

Страница 29: ...t Magnetic Reed Switch p n 103069 4 3 2 1 1 2 4 3 OPEN Transformer Fuse 1 5A Fuse 2 3A R13 R8 J4 J2 STOP 1 4 3 2 1 2 4 3 R40 R27 R21 R24 R29 TDPG 1 Relay On Off 3 4 2 Selector Switches BCHK TDAS Door...

Страница 30: ...Green Green Brown Tan Green Transformer J4 Motor Black J2 STOP R8 1 OFF Relay ON 2 4 3 BCHK R21 DN0055 Transformer Installation and Wiring for 240 Volts R13 Selector Switches OPEN Green wires are 24 v...

Страница 31: ...y with Lockout during door swing Continuous Safety 24 VAC AUX Output for sensors TERMINAL BLOCK 1 BROWN 2 ORANGE 3 VIOLET 4 WHITE 5 RED 6 BLACK 24VAC NEUTRAL 24VAC HOT CONTINUOUS SAFETY SAFETY WITH LO...

Страница 32: ...witch 2 OFF Switch 3 ON Switch 4 ON 5 Refer to GT 710 and Door Sequencer Installation Manuals for additional instructions 6 24 VAC shown to electric strike If strike is DC a rectifier must be installe...

Страница 33: ...LY MOM GND EXTD POWER SA 1 Door sequencer P N 1410062 Activation Device Connect To Terminal Block 5 Red 24 VAC Common Connect To Terminal Block 6 Black Activation Or Black Wire Of Rocker Switch Fire A...

Отзывы: