LO-LINE RC & LO-LINE RC Heater Cooler

1.0 General Information

2.0 Heating System Design

G

This MYSON LO-LINE fan convector is designed for wall
mounted installation with a minimum installation height of
150mm to the underside of the unit.

G

The LO-LINE should only be used on closed circulation, two
pipe, pump assisted central heating systems (LO-LINE) or
heating and cooling systems (LO-LINE Heater-Cooler).

G

The LO-LINE Heater and Heater-Cooler can be used on heat
pump systems.

G

Before proceeding with the installation, the heating system
design must be considered and the unit correctly sized to
meet the heat loss requirements of the room at normal fan
speed.

G

This unit is supplied with an infra red remote control system,
giving automatic temperature control. Alternatively, the unit
can be run in manual, which allows manual switching between
the 3 fan speeds available to circulate ambient air.

This fan convector must be fitted on a two pipe, pumped
circulation heating system.

For optimum fan convector heating performance the system
must be capable of providing sufficient hot water through the
heat exchanger. This means that:

1. The minimum pipe size from boiler to fan convector must be

at least 15mm.

2. This unit is not suitable for use on microbore pipe-work.

3. Where the unit is fitted on to a system with other emitters a

separate circuit for the fan convector should be considered
to provide adequate water flow.

4. The system water must be above 43°C for heating mode.

5. For heat pump applications - see Commissioning Procedure

6. This unit is NOT suitable for one-pipe systems.

7. Optimum performance will require effective balancing of

the whole system.

8. This unit must not be used to replace a radiator in an

existing system unless an adequate flow of water through
the unit can be guaranteed.

3.0 Unit Selection/Sizing

Heat output performance is given in the Technical Data section
of this manual. Outputs are shown for the three fan speeds,
however, it is important to size the unit to match the calculated
heat loss requirements of the room with the unit operating on

the low fan speed. The higher fan speeds are used in automatic
mode when the room temperature is significantly lower than the
preset temperature.

4.0 Location

G

This LO-LINE unit may be fitted to any convenient wall at a
height from floor level that suits the application, providing an
unimpeded flow of warm air into the area to be heated.

G

The minimum distance from the underside of the unit to floor
level is 150mm.

G

The unit should be mounted on a flat wall, and stud or
partition walls should be avoided to minimise the possibility
of noise transmission.

G

For cooling applications, the need for disposal of condensate
may influence the position of the unit.

1

.0

2

.0

3

.0

4

.0

This unit MUST NOT be installed in a bathroom or other similar high humidity area.

For latest prices and delivery to your door visit MyTub Ltd - www.mytub.co.uk - [email protected] 0844 556 1818   

Содержание LO-LINE RC 14-10

Страница 1: ...56 service convectors myson co uk Spare parts and technical help on all Convector products are available from Myson Service MYSON Eastern Avenue Team Valley Gateshead Tyne Wear NE11 0PG UK T 0845 402 3434 F 0191 491 7568 sales myson co uk www myson co uk For latest prices and delivery to your door visit MyTub Ltd www mytub co uk info mytub co uk 0844 556 1818 ...

Страница 2: ... Number Please leave this manual with the end user Part Number 1370057 Issue 1 heatingthroughinnovation LO LINE RC LO LINE RC Heater cooler Models 6 4 9 6 14 10 19 15 For latest prices and delivery to your door visit MyTub Ltd www mytub co uk info mytub co uk 0844 556 1818 ...

Страница 3: ... 04 6 0 Fixing 04 7 0 Water Connections 05 8 0 Electrical Connections 06 9 0 Commissioning Procedure 07 10 0 Technical Data 08 11 0 Operating Instructions 09 12 0 Troubleshooting 10 13 0 Maintenance 11 Contents For latest prices and delivery to your door visit MyTub Ltd www mytub co uk info mytub co uk 0844 556 1818 ...

Страница 4: ...should be considered to provide adequate water flow 4 The system water must be above 43 C for heating mode 5 For heat pump applications see Commissioning Procedure 6 This unit is NOT suitable for one pipe systems 7 Optimum performance will require effective balancing of the whole system 8 This unit must not be used to replace a radiator in an existing system unless an adequate flow of water throug...

Страница 5: ...e wall plugs are suitable for the wall type G Remove the backing from the self adhesive washers and place on screws with adhesive side towards the point G Tighten the screws into the wall leaving about 9mm projecting G Press adhesive washers to the wall Remove the outer casing as follows G Remove the 2 screws from the underside of the unit see fig 2 G Lift off the outer case G Fit chassis on to mo...

Страница 6: ...s added to the system as necessary G Open valves fully check pipe connections for leaks and vent the heat exchanger see Commissioning Procedure LO LINE Heater Cooler installations with chilled water will require provision for condensate disposal in accordance with any local regulations A drain tray is fitted for condensate collection within the unit This should be connected to a 15mm drain pipe No...

Страница 7: ...he cable gland provided or through the hole provided at the upper right hand corner of the chassis G Connect live and neutral wires to the power board terminal connections and the earth wire to the chassis earth terminal 8 0 Electrical Connection WARNING This appliance must be earthed The electrical installation must comply with local or national wiring regulations O O L N Motor Power Board Contro...

Страница 8: ... but for systems such as those with heat pumps a lower water set point may be required The set point can be adjusted using the set point switch located on the control board G Isolate electrical supply G Remove outer cover G Change switch position see fig 4 G Refit cover G Switch on electrical supply Displayed Temperature Calibration This function enables calibration of the displayed temperature to...

Страница 9: ...1533 1305 2291 1656 3128 1725 1464 1203 2187 1511 2987 1632 1340 1104 2002 1345 2734 1452 1228 1052 1835 1347 2505 1427 1032 878 1542 1113 2106 1159 877 754 1310 969 1788 1034 710 581 1061 770 1448 957 600 507 896 639 1223 655 499 423 745 535 1018 553 496 397 741 526 1012 654 391 335 585 429 798 454 321 277 480 357 655 383 Boost Medium Low Boost Medium Low Boost Medium Low Boost Medium Low 19 15 1...

Страница 10: ... summer for example or that heating performance can be controlled manually The unit can be controlled using the infra red remote control handset supplied with the unit see fig 5 and also using the control panel on the unit see fig 6 If necessary however the control panel can be locked electronically to prevent tampering once the controls have been set see below The remote control hand set takes 2 ...

Страница 11: ...tton for about 6 seconds until the horizontal bars disappear 10 LO LINE RC LO LINE RC Heater Cooler 12 0 Troubleshooting Once installed this fan convector becomes part of a complete heating system that will generally include a boiler pump other emitters such as radiators and fan convectors and a number of heating controls dependent on system complexity An apparent problem with this unit may be the...

Страница 12: ... spur Replace fuse Open valves Check boiler Programmer ON Boiler ON and set to high with central heating pump running Note Operation of fan convector can be checked by switching to manual fan setting Heating Mode Heater Model only poor heating performance and or unit cycles on water sensor Possible Causes Boiler thermostat set too low Lack of flow to fan convector Pump set on low setting Isolating...

Отзывы: