113903G -System Installation Manual
14
AC INPUT AND OUTPUT CONNECTION
Series C-M Inverter Module
Connect the AC Input and Output to the AC Terminal Blocks Labeled AC Input and
AC Output. Ensure that the systems ac voltage matches the utility input.
For the AC input, use a minimum 10 AWG wire for Line, Neutral and Ground.
For the AC output, use a minimum 12 AWG wire for Line, Neutral and Ground.
Earth Grounding of the system is achieved through the Ground terminal block. There
is a ground terminal block provided for the input and output connections. The
terminal block connects to the din rail through a clamping system and the din rail
connects to the Chassis through the din rail hardware. No additional Ground lugs are
required.
AC LINE INPUT (Black)
AC NEUTRAL INPUT (White)
EARTH GROUND (Green/Yellow)
AC LINE OUTPUT (Black)
AC NEUTRAL OUTPUT (White)
EARTH GROUND (Green/Yellow)