9.2
Testing
Before leaving site, it is wise to perform a few checks to ensure that the sensors and heaters have been
correctly installed and are functional.
Step 1:
Test the heaters by trying a manual boost, and check the power reading on the screen for the heater
corresponds to the heater rating.
Step 2:
Cancel the boost by pressing the button twice during the boost
NOTE
By default, the
eddi
is set to operate as in
Application Examples 1: Single Element Water Heater.
If
the application differs, refer to the specific application example for details of settings that may
need to be changed.
If
eddi
has been installed alongside other
eddi
units or another
myenergi
device, refer to
Linking
Devices
for guidance on pairing devices. Also refer to the instruction documentation for the other
devices
NOTE
When
eddi
is diverting surplus power to the heater, the grid power figure (above the pylon symbol)
should be 0.0kW).
Note; however, if the surplus power exceeds the rating of the heater then this
cannot be achieved and some export power will be observed.
If power is being imported from the grid when the
eddi
is in Heating mode, it is likely that the Grid
CT is incorrectly installed.
If a Generation CT has been installed, the generated power will show at the top left of the main
screen.
If the generation reading is missing, the most likely cause is the Generation CT has not been
configured – see CT Config on page 21. Or, if the Grid CT is instead wired to a
harvi
ensure the
device settings are correct.
NOTE – vHub & WiFi
For instruction on vHub & WiFi Set-up please see separate vHub & WiFi Module Instructions.