06: reserved
Interface
Setting
reserved
07: reserved
Interface
Setting
reserved
08: Bypass mode setting
Interface
Setting
Parameter 2:
OPN: Bypass allowed. When selected, UPS will run at Bypass
mode depending on bypass enabled/disabled setting.
FBD: Bypass not allowed. When selected, it’s not allowed for
running in Bypass mode under any situations.
Parameter 3:
ENA: Bypass enabled. When selected, Bypass mode is activated.
DIS: Bypass disabled. When selected, automatic bypass is
acceptable, but manual bypass is not allowed. Manual bypass
means users manually operate UPS for Bypass mode. For
example, pressing OFF button in AC mode to turn into Bypass
mode.
09: Battery maximum discharge time setting
Interface
Setting
Parameter 3:
000~999: Set the maximum discharge time from 0min to
999min. UPS will shut down to protect battery after discharge time
arrives. The default value is 990min.
DIS: Disable battery discharge protection and backup time will
depend on battery capacity.
10: reserved
Interface
Setting
reserved