13

some non-critical loads to disable the shutdown alarm and prolong the backup time. If there is no 
more load to be switched off at that time, you have to shut down all loads as soon as possible to 
protect the devices or save data. Otherwise, there is a risk of data loss or load failure.   

2)    In Battery mode, if buzzer sound annoys, users can press the Mute button to disable the buzzer. 

3)    The backup time of the long-run model depends on the external battery capacity. 

4)    The backup time may vary from different environment temperature and load type. 

5)    When setting backup time for 16.5 hours (default value from LCD panel), after discharging 16.5 

hours, UPS will shut down automatically to protect the battery. This battery discharge protection 
can be enabled or disabled through LCD panel control. (Refer to 3-7 LCD setting section) 

6. Test the batteries 

1)    If you need to check the battery status when the UPS is running in AC mode/CVCF mode, you could 

press the “Test” button to let the UPS do battery self-test. 

2)    Users also can set battery self-test through monitoring software. 

7. Turn off the UPS with utility power supply in AC mode 

1)    Turn off the inverter of the UPS by pressing “OFF” button for at least 0.5s, and then the buzzer will 

beep once. The UPS will turn into Bypass mode.   

NOTE 1: If the UPS has been set to enable the bypass output, it will bypass voltage from utility 
power to output sockets and terminal even though you have turned off the UPS (inverter). 

NOTE 2: After turning off the UPS, please be aware that the UPS is working at Bypass mode and 
there is risk of power loss for connected devices.   

2)    In Bypass mode, output voltage of the UPS is still present. In order to cut off the output, switch off 

the input breaker. A few seconds later, there is no display shown on the display panel and UPS is 
complete off. 

8. Turn off the UPS without utility power supply in Battery mode 

1)    Turn off the UPS by pressing “OFF” button for at least 0.5s, and then the buzzer will beep once. 

2)    Then UPS will cut off power to output and there is no display shown on the display panel. 

9. Mute the buzzer 

1)    To mute the buzzer, please press the “Mute” button for at least 0.5s. If you press it again after the 

buzzer is muted, the buzzer will beep again. 

2)    Some warning alarms can’t be muted unless the error is fixed. Please refer to section 3-3 for the 

details.   

10. Operation in warning status 

1)    When Fault LED flashes and the buzzer beeps once every second, it means that there are some 

problems for UPS operation. Users can get the fault code from LCD panel. Please check the trouble 
shooting table in chapter 4 for details.   

2)    Some warning alarms can’t be muted unless the error is fixed. Please refer to section 3-3 for the 

details. 

11. Operation in Fault mode 

1)    When Fault LED illuminates and the buzzer beeps continuously, it means that there is a fatal error in 

the UPS.    Users can get the fault code from display panel. Please check the trouble shooting table 
in chapter 4 for details. 

Содержание POWERMUST 10800 ONLINE LCD

Страница 1: ...PowerMust 6048 Online LCD X PowerMust 10800 Online LCD X Uninterruptible Power Supply System User Manual EN...

Страница 2: ...g instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all safety inf...

Страница 3: ...W 5 2 3 SINGLE UPS INSTALLATION 6 2 4 SOFTWARE INSTALLATION 8 3 OPERATIONS 9 3 1 BUTTON OPERATION 9 3 2 LED INDICATORS AND LCD PANEL 9 3 3 AUDIBLE ALARM 11 3 4 SINGLE UPS OPERATION 11 3 5 ABBREVIATION...

Страница 4: ...nect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over them Do not b...

Страница 5: ...mains Ensure that no liquid or other foreign objects can enter into the UPS system The UPS can be operated by any individuals with no previous experience 1 5 Standards Safety IEC EN 62040 1 EMI Condu...

Страница 6: ...npack the package and check the package contents The shipping package contains One UPS One user manual One monitoring software CD One RS 232 cable option One USB cable One battery cable option NOTE Be...

Страница 7: ...g must be performed in accordance with the local electric laws regulations and execute the following instructions by professional personnel 1 Make sure the mains wire and breakers in the building are...

Страница 8: ...making wire connection Disconnect the earth wire last when making wire disconnection Terminal Block wiring diagram for 6K L 10K L NOTE 1 Make sure that the wires are connected tightly with the termin...

Страница 9: ...battery pack please make sure you modify the setting simultaneously The connection with wrong battery voltage may cause permanent damage of the UPS Make sure the voltage of the battery pack is correc...

Страница 10: ...this button to display next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details Down key Pr...

Страница 11: ...s disabled Output Battery voltage information Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level by...

Страница 12: ...an failure Over temperature Charger failure IP fuse broken Overload 3 times in 30min EPO status Cover of maintain switch is open Fault Bus start failure Beeping continuously Yes Bus over Bus under Bus...

Страница 13: ...please remove some loads immediately It is recommended to have the total loads connected to the UPS less than 80 of its nominal power capacity to prevent overload for system safety 5 If the overload...

Страница 14: ...output sockets and terminal even though you have turned off the UPS inverter NOTE 2 After turning off the UPS please be aware that the UPS is working at Bypass mode and there is risk of power loss for...

Страница 15: ...e for long run model or disconnect battery wire for standard model 4 Remove the cabinet cover and then modify the jumpers JP1 JS3 on the control board to set the battery numbers as following table Bat...

Страница 16: ...Reserved 08 Bypass mode setting Y Y 09 Battery maximum discharge time setting Y Y Y Y Y 10 Reserved 11 Reserved 12 Reserved 13 Battery voltage Calibration Y Y Y Y Y 14 Charger voltage adjustment Y Y Y...

Страница 17: ...he input frequency within 46 54 Hz at 50Hz or within 56 64 Hz at 60Hz according to setting in parameter 2 If 50 Hz selected in parameter 2 UPS will transfer to battery mode when input frequency is not...

Страница 18: ...e is activated DIS Bypass disabled When selected automatic bypass is acceptable but manual bypass is not allowed Manual bypass means users manually operate UPS for Bypass mode For example pressing OFF...

Страница 19: ...ltage range is from 0V to 5 7V the default value is 0V 14 Charger voltage adjustment Interface Setting Parameter 2 you may choose Add or Sub to adjust charger voltage Parameter 3 the voltage range is...

Страница 20: ...4A automatically even though the setting is 6A 19 Battery capacity and groups setting Interface Setting Parameter 2 Set the battery capacity such as 7AH 9AH 10AH 12AH 17AH 26AH 40AH 65AH 100AH and so...

Страница 21: ...splay Battery mode Description When the input voltage is beyond the acceptable range or power failure UPS will backup power from battery and alarm will beep every 4 seconds LCD display Bypass mode Des...

Страница 22: ...lay short circuited 24 None Inverter soft start failure 11 None Over temperature 41 None High Inverter voltage 12 None CPU communication failure 42 None Low Inverter voltage 13 None Overload 43 3 9 Wa...

Страница 23: ...is locked in the Bypass mode Connected devices are fed directly by the mains Remove excess loads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon lights...

Страница 24: ...required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery terminals and...

Страница 25: ...2A 10 Charging Voltage 218 4 VDC 1 273 VDC 1 Long run Model Type Depending on applications Numbers 16 20 adjustable Note When using internal batteries from 16 to 19 the unit will de rate according to...

Отзывы: