background image

 

 

3. Operations 

3-1. Button Operation 

Button 

Function   

ON/Enter Button   

 

Turn on the UPS: Press and hold the button more than 0.5s to turn on the UPS. 

 

Enter Key: Press this button to confirm the selection in setting menu. 

OFF/ESC Button   

 

Turn off the UPS: Press and hold the button more than 0.5s to turn off the UPS. 

 

Esc key: Press this button to return to last menu in setting menu.   

Test/Up Button 

 

Battery test: Press and hold the button more than 0.5s to test the battery while 
in AC mode, or CVCF mode. 

 

UP key: Press this button to display next selection in setting menu. 

Mute/Down Button   

 

Mute the alarm: Press and hold the button more than 0.5s to mute the buzzer. 
Please refer to section 3-4-9 for details.   

 

Down key: Press this button to display previous selection in setting menu. 

Test/Up + 

Mute/Down Button 

 

Press and hold the two buttons simultaneous more than 1s to enter/escape the 
setting menu.   

* CVCF mode means converter mode.   

3-2. LED Indicators and LCD Panel   

 

 

LED Indicators: 

There are 4 LEDs on front panel to show the UPS working status: 

Mode                    LED 

Bypass 

Line 

Battery 

Fault 

UPS Startup 

● 

● 

● 

● 

Bypass mode 

● 

 

 

 

AC mode 

 

● 

 

 

Battery mode 

 

 

● 

 

CVCF mode 

 

● 

 

 

Battery Test 

● 

● 

● 

 

Fault 

 

 

 

● 

Note: 

 means LED is lighting, and 

 means LED is faded.   

LCD panel 

LED indicators 

Содержание POWERMUST 10800 ONLINE LCD

Страница 1: ...PowerMust 6048 Online LCD X PowerMust 10800 Online LCD X Uninterruptible Power Supply System User Manual EN...

Страница 2: ...g instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all safety inf...

Страница 3: ...W 5 2 3 SINGLE UPS INSTALLATION 6 2 4 SOFTWARE INSTALLATION 8 3 OPERATIONS 9 3 1 BUTTON OPERATION 9 3 2 LED INDICATORS AND LCD PANEL 9 3 3 AUDIBLE ALARM 11 3 4 SINGLE UPS OPERATION 11 3 5 ABBREVIATION...

Страница 4: ...nect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over them Do not b...

Страница 5: ...mains Ensure that no liquid or other foreign objects can enter into the UPS system The UPS can be operated by any individuals with no previous experience 1 5 Standards Safety IEC EN 62040 1 EMI Condu...

Страница 6: ...npack the package and check the package contents The shipping package contains One UPS One user manual One monitoring software CD One RS 232 cable option One USB cable One battery cable option NOTE Be...

Страница 7: ...g must be performed in accordance with the local electric laws regulations and execute the following instructions by professional personnel 1 Make sure the mains wire and breakers in the building are...

Страница 8: ...making wire connection Disconnect the earth wire last when making wire disconnection Terminal Block wiring diagram for 6K L 10K L NOTE 1 Make sure that the wires are connected tightly with the termin...

Страница 9: ...battery pack please make sure you modify the setting simultaneously The connection with wrong battery voltage may cause permanent damage of the UPS Make sure the voltage of the battery pack is correc...

Страница 10: ...this button to display next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details Down key Pr...

Страница 11: ...s disabled Output Battery voltage information Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level by...

Страница 12: ...an failure Over temperature Charger failure IP fuse broken Overload 3 times in 30min EPO status Cover of maintain switch is open Fault Bus start failure Beeping continuously Yes Bus over Bus under Bus...

Страница 13: ...please remove some loads immediately It is recommended to have the total loads connected to the UPS less than 80 of its nominal power capacity to prevent overload for system safety 5 If the overload...

Страница 14: ...output sockets and terminal even though you have turned off the UPS inverter NOTE 2 After turning off the UPS please be aware that the UPS is working at Bypass mode and there is risk of power loss for...

Страница 15: ...e for long run model or disconnect battery wire for standard model 4 Remove the cabinet cover and then modify the jumpers JP1 JS3 on the control board to set the battery numbers as following table Bat...

Страница 16: ...Reserved 08 Bypass mode setting Y Y 09 Battery maximum discharge time setting Y Y Y Y Y 10 Reserved 11 Reserved 12 Reserved 13 Battery voltage Calibration Y Y Y Y Y 14 Charger voltage adjustment Y Y Y...

Страница 17: ...he input frequency within 46 54 Hz at 50Hz or within 56 64 Hz at 60Hz according to setting in parameter 2 If 50 Hz selected in parameter 2 UPS will transfer to battery mode when input frequency is not...

Страница 18: ...e is activated DIS Bypass disabled When selected automatic bypass is acceptable but manual bypass is not allowed Manual bypass means users manually operate UPS for Bypass mode For example pressing OFF...

Страница 19: ...ltage range is from 0V to 5 7V the default value is 0V 14 Charger voltage adjustment Interface Setting Parameter 2 you may choose Add or Sub to adjust charger voltage Parameter 3 the voltage range is...

Страница 20: ...4A automatically even though the setting is 6A 19 Battery capacity and groups setting Interface Setting Parameter 2 Set the battery capacity such as 7AH 9AH 10AH 12AH 17AH 26AH 40AH 65AH 100AH and so...

Страница 21: ...splay Battery mode Description When the input voltage is beyond the acceptable range or power failure UPS will backup power from battery and alarm will beep every 4 seconds LCD display Bypass mode Des...

Страница 22: ...lay short circuited 24 None Inverter soft start failure 11 None Over temperature 41 None High Inverter voltage 12 None CPU communication failure 42 None Low Inverter voltage 13 None Overload 43 3 9 Wa...

Страница 23: ...is locked in the Bypass mode Connected devices are fed directly by the mains Remove excess loads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon lights...

Страница 24: ...required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery terminals and...

Страница 25: ...2A 10 Charging Voltage 218 4 VDC 1 273 VDC 1 Long run Model Type Depending on applications Numbers 16 20 adjustable Note When using internal batteries from 16 to 19 the unit will de rate according to...

Отзывы: