background image

 

1. Important Safety Warning 

Please  comply  with  all  warnings  and  operating  instructions  in  this  manual  strictly.  Save  this 
manual properly and read carefully the following instructions before installing the unit. Do not 
operate this unit before reading through all safety information and operating instructions carefully 
 

1-1. Transportation 

 

Please transport the UPS system only in the original package to protect against shock 
and impact. 

 

1-2. Preparation 

 

Condensation may occur if the UPS system is moved directly from cold to warm 
environment. The UPS system must be absolutely dry before being installed. Please 
allow at least two hours for the UPS system to acclimate the environment.   

 

Do not install the UPS system near water or in moist environments. 

 

Do not install the UPS system where it would be exposed to direct sunlight or near 
heater. 

 

Do not block ventilation holes in the UPS housing. 

 

1-3. Installation 

 

Do not connect appliances or devices which would overload the UPS system (e.g. laser 
printers) to the UPS output sockets.   

 

Place cables in such a way that no one can step on or trip over them.   

 

Do not connect domestic appliances such as hair dryers to UPS output sockets.   

 

The UPS can be operated by any individuals with no previous experience. 

 

 

Connect the UPS system only to an earthed shockproof outlet which must be easily 
accessible and close to the UPS system.   

 

Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your 
computer) to connect the UPS system to the building wiring outlet (shockproof outlet).   

 

Please use only VDE-tested, CE-marked power cables to connect the loads to the UPS 
system.   

 

When installing the equipment, it should ensure that the sum of the leakage current of 
the UPS and the connected devices does not exceed 3.5mA. 

 

1-4. Operation 

 

Do not disconnect the mains cable on the UPS system or the building wiring outlet 
(shockproof socket outlet) during operations since this would cancel the protective 
earthing of the UPS system and of all connected loads.   

 

The UPS system features its own, internal current source (batteries). The UPS output 
sockets or output terminals block may be electrically live even if the UPS system is not 
connected to the building wiring outlet.   

 

In order to fully disconnect the UPS system, first press the OFF/Enter button to 
disconnect the mains.   

 

Prevent no fluids or other foreign objects from inside of the UPS system.   

 

Содержание POWERMUST 1008 ONLINE LCD

Страница 1: ...PowerMust 1008 Online LCD RM PowerMust 2016 Online LCD RM PowerMust 3024 Online LCD RM Online UPS User Manual EN...

Страница 2: ...s 3 2 Installation and setup 4 2 1 Rear panel view 4 2 2 Setup the UPS 5 3 Operations 7 3 1 Button operation 7 3 2 LCD Panel 7 3 3 Audible Alarm 9 3 4 LCD display wordings index 9 3 5 UPS Setting 9 3...

Страница 3: ...er them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed sh...

Страница 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Страница 5: ...rMust 3024 Online LCD Standard PowerMust 3024L Online LCD Long run 2 1 Rear panel view PowerMust 1008 L Online LCD PowerMust 2016 L Online LCD PowerMust 3024 L Online LCD PowerMust 1008 L Online LCD R...

Страница 6: ...5 12 Output circuit breaker...

Страница 7: ...or the wiring configuration a Remove the small cover of the terminal block b Suggest using AWG14 or 2 1mm2 power cords Suggest using WG12 10 or 3 3mm2 5 3mm2 power cords for NEMA type c Upon completio...

Страница 8: ...tware to fully configure UPS shutdown You may insert provided CD into CD ROM to install the monitoring software If not please follow steps below to download and install monitoring software from the in...

Страница 9: ...e UPS will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS set...

Страница 10: ...6 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuit Programmable outlets information Indicates that programmable management outlets are working Mode operatio...

Страница 11: ...reviation Display content Meaning ENA Enable DIS Disable ESC Escape HLS High loss LLS Low loss BAT Battery CF Converter EP EPO FA Fan TP Temperature CH Charger 3 5 UPS Setting There are three paramete...

Страница 12: ...ency setting Interface Setting Parameter 2 3 Output frequency setting You may set the initial frequency on battery mode BAT 50 presents output frequency is 50Hz BAT 60 presents output frequency is 60H...

Страница 13: ...240 VAC models 230 264 setting the high voltage point in parameter 3 from 230Vac to 264Vac For 110 115 120 127 VAC models 120 132 setting the high voltage point in parameter 3 from 120Vac to 132Vac L...

Страница 14: ...ry mode When the input voltage is beyond the acceptable range or power failure and alarm is sounding every 4 second UPS will backup power from battery Bypass mode When input voltage is within acceptab...

Страница 15: ...cond Battery is not connected Sounding every second Over Charge Sounding every second Site wiring fault Sounding every second EPO enable Sounding every second Fan Failure Sounding every second Over te...

Страница 16: ...cted Check if all batteries are connected well Fault code is shown as 27 and the icon is lighting on LCD display and alarm is continuously sounding Battery voltage is too high or the charger is fault...

Страница 17: ...p time is shorter than nominal value Batteries defect Contact your dealer to replace the battery The icon and the warning code flashing on LCD display and alarm is sounding every second Fan is locked...

Страница 18: ...Harmonic Distortion 3 THD Linear Load 6 THD Non linear Load 4 THD Linear Load 7 THD Non linear Load AC Mode to Batt Mode Zero Transfer Time Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure Sin...

Отзывы: