User’s
Manual

Yokogawa Electric Corporation

IM 01C25R51-01E

FSA120 (EJXMVTool

TM

)

EJX-MV Configuration DTM

IM 01C25R51-01E

4th Edition

Summary of Contents for vigilantplant EJXMVTool FSA120

Page 1: ...User s Manual Y okogawa Electric Corporation IM 01C25R51 01E FSA120 EJXMVToolTM EJX MV Configuration DTM IM 01C25R51 01E 4th Edition...

Page 2: ...ns 1 5 1 2 7 DIPPR 1 5 2 General 2 1 3 Functional Specification 3 1 3 1 PC 3 1 3 1 1 Hardware Operating Environment 3 1 3 1 2 Software Operating Environment 3 1 3 2 Field Communication 3 2 3 3 Model t...

Page 3: ...nications Manager 4 16 4 5 5 Connect the EJX910A to the power supply 4 16 4 5 6 Connect the NI FBUS card to the EJX910A 4 16 4 6 Start FDT frame application 4 17 4 6 1 Update DTM Browser 4 17 4 6 2 St...

Page 4: ...Fluid Operating Range Setup 6 28 6 3 6 Fluid Physical Property Setup 6 31 6 3 7 Apply Flow Configuration 6 33 6 4 Flow ConfigurationWizard Basic Mode 6 33 6 4 1 Flow Configuration Mode 6 33 6 4 2 Basi...

Page 5: ...Blank Page...

Page 6: ...nd user The information contained in this manual is subject to change without prior notice The information contained in this manual in whole or part shall not be transcribed or copied withoutYOKOGAWA...

Page 7: ...trademark of Intel Corporation IBM PC AT is a registered trademark of International Business Machines Corp HART is a registered trademark of HART Communication Foundation MACTek is a registered tradem...

Page 8: ...essing operations Use of the Licensed Software for any purpose other than those as ex pressly specified in the documentation provided by Licensor shall be prohibited Any result or damage arising out o...

Page 9: ...RE LICENSOR AND SUPPLIERS DISCLAIM ANY AND ALL LIABILITY AND WILL HAVE NO LIABILITY FOR VIOLA TION MISAPPROPRIATION OR INFRINGEMENT OF INTELLECTUAL PROPERTY RIGHTS OF ANY THIRD PARTY 2 IN NO EVENT SHA...

Page 10: ...ems it is not reasonable to license without such void or unen forceable part Licensor is entitled to modify the terms of this Agreement or terminate this Agreement at its option without owing any liab...

Page 11: ...Blank Page...

Page 12: ...lculation of flow parameters for EJX910 Database EJX MV Configuration DTM Dialog editor Fluid information Notebook PC FF H1 HART Communications Frame Application Comm DTM Flow Parameter Management Sen...

Page 13: ...Blank Page...

Page 14: ...er with an administrative authority Microsoft Windows XP Professional SP2 English Following software is necessary to be installed in your computer Common Adobe Reader FDT Frame application conforming...

Page 15: ...Files FJX910 HART DTM included inYokogawa DTM Library HART FJX910 FF DTM included inYokogawa DTM Library FF IMPORTANT If you already have FSA210 Mass Flow Configuration Software installed in your comp...

Page 16: ...am and HART DTMs of other YOKOGAWA products Yokogawa DTM Library FF Includes EJX910 FF DTM EJXMVTool source program and FF DTMs of other YOKOGAWA products Yokogawa MVTool additional resource disk Prog...

Page 17: ...VTool Flow Configuration Wizard Obtain Flow Coefficient Database Table 3 2 Function of EJXMVTool for FF communication T0301 2E EPS Program Function Startup method Entry of License Contens Install loca...

Page 18: ...ess value monitoring Tag Range Unit Damping Lowcut Indicator display Maintenance Adjustment Status information display 2 Offline Parameter The Transmitter General parameters of the device can be edite...

Page 19: ...low operation and density compensation are performed conventionally with the flow factors being input manually Refer to section 6 4 3 File management xmv file Import export User Flow parameters Import...

Page 20: ...67 1 1991 Orifice Corner Taps ISO5167 2 2003 Orifice Flange Taps ISO5167 1 1991 Orifice Corner Taps ISO5167 1 1991 Orifice Corner Taps ASME MFC 3M 1989 ASME FLOW NOZZLES ASME MFC 3M 1989 Classical Ven...

Page 21: ...e 1 Decene Carbon Monoxide Methyl Vinyl ether 1 Decanal Carbon Tetrachloride Monochlorobenzene 1 Decanol Chlorine n Butane 1 Dodecene Chlorodifluoromethane n Butanol 1 Dodecanol Chloroprene n Butyrald...

Page 22: ...Association for the Properties of Water and Steam 3 Density compensation using standard Natural gas AGA8 Compressibility Factors of Natural Gas and Other Related Hydrocarbon Gases American Gas Associa...

Page 23: ...Blank Page...

Page 24: ...choose Start Control Panel PowerOptions to open Power Options Properties dialog box Confirm the settings on this dialog box are the same as follows Power Schemes Tab System standby and System hibernat...

Page 25: ...ab Hibernate Tab Do not check the option Enable hibernation Apply F0403E EPS Hibernate Advanced Power Schemes Power Options Properties Cancel OK UPS Disk space for hibernation Hibernate When you compu...

Page 26: ...lick the filename in Windows Explorer FieldInstDrive is the drive on which field communication server is installed FieldInstDrive is the drive where the PRM directory is located The default drive is t...

Page 27: ...ing the previous version of FieldMate Advance If the version is equivalent or higher install Additional Resource Disk alone if you have purchased FSA120 with FieldMate Advance check the version of Fie...

Page 28: ...l resource installation Execute CDROM Resource setup exe Double click the file name in Windows Explorer and the EJXMVTool installation program will be started CDROM is the CD ROM drive of your compute...

Page 29: ...ight 2006 Yokogawa Electric Corporation IM 01C25R51 01E 3 Input User Name Organization and Click Next F0407E EPS Figure 4 6c Customer Information Screen 4 Select Complete or Custom Complete setup is r...

Page 30: ...Preparation All Rights Reserved Copyright 2006 Yokogawa Electric Corporation IM 01C25R51 01E 5 Click Install F0409E EPS Figure 4 6e Ready to install screen 6 Click Finish F0410E EPS Figure 4 6f Finish...

Page 31: ...F0411E EPS Version number Figure 4 7 Version Number of DTM Library 2 EJXMVTool DTM The version number is displayed on the HELP screen of Flow Configuration Wizard or Obtain Flow Coefficient Refer to 6...

Page 32: ...01E 4 3 Uninstallation 1 FieldMate Refer to User s manual IM01R01A01 00E 2 MVTool Additional Resouce Use the Add or Remove Programs function of the Windows Control Panel Select Yokogawa MVTool additi...

Page 33: ...RT Communication Modem Connect the HART communication modem to the PC s COM port NOTE Either a serial RS232C or USB port may be used 4 4 2 COM port Find out which COM port the modem will be connected...

Page 34: ...ration All Rights Reserved Copyright 2006 Yokogawa Electric Corporation IM 01C25R51 01E F0415E EPS Figure 4 10b Hardware propoerties Click Ports COM LPT to find out the port number F0416E EPS Figure 4...

Page 35: ...4 4 Communication setting HART communication This subsection describes the procedures to change the communication related setting of FieldMate Please try these procedures after you start FieldMate an...

Page 36: ...lue 1 Click the Tool HART Modem Configuration at FieldMate window 2 Select address number 3 Click the OK button F0435E EPS Maximum value of communication Addressfor scaning Figure 4 14 Address Setting...

Page 37: ...tivate the program as an Administrator or user with an Administrative authority 1 Activate the program On PC click the following order and activate the program Click Start All Programs National Instru...

Page 38: ...4 15c NI FBUS H1 Port Properties 1 Device Address Select Visitor Device Type Select Basic Device Usage Select NI FBUS CAUTION Do not set the NI FBUS card to Link Master Device in the Fieldbus segment...

Page 39: ...15e Starting NI FBUS IMPORTANT When running the program log in the Windows as an Administrator or an user with an administrative authority 4 5 5 Connect the EJX910A to the power supply Please refer to...

Page 40: ...plication This section describes the operation of DTM with using FieldMate For the detailed operation of FieldMate refer to User s manual of FieldMate IMPORTANT When running the program log in the Win...

Page 41: ...eldMate Starting FieldMate by following operation 1 Click Start All Programs YOKOGAWA FieldMate FieldMate F0424E EPS Figure 4 17a Start FieldMate 2 Default Scan Segment is to select the communication...

Page 42: ...nect to FieldMate If not No device found message is shown on the window If a connected device icon does not appear check that initial setting for communication is correctly done Refer to section 4 4 f...

Page 43: ...Electric Corporation IM 01C25R51 01E F0428 03E EPS Figure 4 17e Version Number of EJX910 DTM 4 6 3 Start EJX910 DTM 1 Start DTM Works Select the icon of the target device for configuration in the win...

Page 44: ...ter snapshot is saved to an external file dfs file which includes the following parameters User Flow parameters Transmitter Flow parameters Transmitter General parameters For a file format of dfs refe...

Page 45: ...by closing each window 1 Click the File Exit at DTM Works window 2 Click the File Exit at FieldMate window 4 7 EJXMVTool Activation 4 7 1 How to Activate Start EJX910DTM see 4 6 3 Start DTM Works Sel...

Page 46: ...ight 2006 Yokogawa Electric Corporation IM 01C25R51 01E F0431E EPS Figure 4 22 Software License Form Once the license number is confirmed Flow Configuration Wizard screen below appears F0432E EPS Figu...

Page 47: ...Blank Page...

Page 48: ...e Setup Fluid Physical Property Setup Export XMV menu Fluid type Setup Initialize menu Offline Parameter Flow Configuration Wizard Parameter Device Upload Transmitter Flow parameters and Transmitter G...

Page 49: ...nline Parameter screen is opened Offline Parameter Disconnect Device Goes online Connect Device Open Offline Parameter window Parameter Device Load the XXXXXX dfs User Flow parameters Transmitter Flow...

Page 50: ...Additional functions Device You can check th flow coefficient The value is saved in a log file FlowCoeffLog Download to device 2 Device Obtain Flow Coefficient Additional functions Disconnect Device D...

Page 51: ...h flow coefficient The value is saved in a log file FlowCoeffLog Download to device 2 Device Obtain Flow Coefficient Additional functions Device FieldMate Menu DTM Works Menu Sub Menu Sub Menu Procedu...

Page 52: ...r Online Parameter Obtain Flow Coefficient Export Report Initia lize Import Help Import PRM Export XMV Report Initialize Import XMV EJXMVTool Help EJXMVTool About Refer to section 6 1 Flow configurati...

Page 53: ...rt File CSV initialize Xmv file Transmitter General Parameters dfs file Compatible between different frame applications Compatible between HART and FFDTMs Not compatible between different frame applic...

Page 54: ...ion of EJX910 DTM Please refer to EJX910DTM HELP for detail Please also refer to FieldMate User s Manual for operation F0603E EPS Click here to refer EJX910DTM HELP for detail HART Click here to refer...

Page 55: ...nd address are not shown on the online parameter screen Use Segment Viewer to confirm the PD Tag and address of the device NOTE Connect menu is active only while the transmitter is disconnected 2 How...

Page 56: ...and stored in offline database Parameters saved in offline database can be downloaded to the device by using Download to Device function Parameters in the device can be uploaded to the offline databa...

Page 57: ...All Rights Reserved Copyright 2006 Yokogawa Electric Corporation IM 01C25R51 01E 2 Offline Parameter Click the Device Parameter Offline Parameter F0606E EPS Figure 6 6a Go to Offline Parameter F0606 0...

Page 58: ...EPS Figure 6 7 Upload from Device Offline Parameters Transmitter Flow Parameters Transmitter General Parameters are uploaded from the transmitter to offline database They can be edited using offline p...

Page 59: ...2 Click the Device Download to Device FF DTM 1 Click the Device Parameter Offline Parameter 2 Check the checkbox of the function blocks downloading to a device F0608aE EPS Figure 6 8a Checkbox of Blo...

Page 60: ...okogawa Electric Corporation IM 01C25R51 01E Downloading icon on the tool bar can also be used to execute download F0608bE EPS Figure 6 8b Download to Device NOTE Download to Device menu is active onl...

Page 61: ...rameters can be printed out by using print function Click the Device Print Select Online Parameter Offline Parameter Diag Service Observe F0609E EPS Figure 6 9 Print 6 1 5 Properties The EJX910 DTM ve...

Page 62: ...6 Additional functions 1 Diag Service for HART Diagnostics related parameters are shown Click the Device Additional Functions Diag Service F0611E EPS Figure 6 11a Diag Service 2 Observe for HART Proc...

Page 63: ...Management can be done from the Flow Configuration Wizard by the following procedures Click the Device Additional Functions Flow Configuration Wizard F0613E EPS Figure 6 12Top Menu Screen of Flow Con...

Page 64: ...PS Figure 6 13b Initializing Message 6 2 2 Import 1 Import Flow Configuration XMV file User Flow parameters and Transmitter Flow parameters can be imported NOTE Refer to 7 File Format for information...

Page 65: ...ng R1 02 00 or earlier the following message is displayed F0615 02E EPS Figure 6 14b Information Message for Reference Pressure Reenter the absolute pressure equivalent to the displayed gauge pressure...

Page 66: ...E EPS Figure 6 15 Exporting a File 6 2 4 Report Export user flow parameters in CSV File format NOTE Report can be used only in the Apply Flow Configuration screen F0617E EPS Figre 6 16 Report NOTE Use...

Page 67: ...opyright 2006 Yokogawa Electric Corporation IM 01C25R51 01E 6 2 5 Help 1 EJXMVTool Help The EJXMVTool manual map opens when this menu is clicked F0618E EPS Figure 6 17 Help NOTE EJXMVTool Online Help...

Page 68: ...in Flow Cefficient version number is shown when this menu is clicked F0619E EPS Figure 6 18 About The EJXMVTool DTM version number is also shown by Add or Remove Program of Windows Control Panel Refer...

Page 69: ...uid physical properties and primary element for the EJX910 can be performed using a dialog window Basic Mode Flow operation and density compensation are performed conventionally with the flow factors...

Page 70: ...d sheet iron convergent section ISO5167 1 1991 ISO5167 4 2003 ASME Venturi Tubes With a rough Cast or Fabricated Convergent ASME MFC 3M 1989 Long radius nozzle ISO5167 1 1991 ISO5167 3 2003 Classical...

Page 71: ...ally calculated according to the material Table 6 3 Pipe material T0605E EPS Pipe Material Remarks 304 Stainless Steel Default 316 Stainless Steel Carbon Steel Hastelloy C Monel 6 3 3 Fluid Setup Auto...

Page 72: ...m Gas DIPPR Gas Custom Data Table When Natural Gas Default is selected for Category select the Fluid name Method from the followings AGA8 Detail Characterization Method Default AGA8 Gross Characteriza...

Page 73: ...achloride Monochlorobenzene 1 Decanol Chlorine n Butane 1 Dodecene Chlorodifluoromethane n Butanol 1 Dodecanol Chloroprene n Butyraldehyde 1 Heptanol Chlorotrifluoroethylene n Butyronitrile 1 Heptene...

Page 74: ...ry Liquid Custom set the Fluid name Method in the blank box 6 3 4 Natural Gas Setup 1 AGA8 Detail Characterization F0623E EPS Figure 6 22 Natural Gas Setup Screen 1 Input the value as mole percent for...

Page 75: ...tane mole percent 0 6 1 13 C5H12 i Pentane mole percent 0 4 2 14 C5H12 n Pentane mole percent 0 4 2 15 C6H14 n Hexane mole percent 0 Dew Point 3 16 C7H16 n Heptane mole percent 0 Dew Point 3 17 C8H18...

Page 76: ...10 0 3 17 76 42 87 MJ m3 477 1150 BTU ft3 at 14 73 psi abs 60 F at 101 56 kPa abs and 15 56 F at 14 73 psi abs 60 F at 101 56 kPa abs and 15 56 F Expanded Range Remarks 3 AGA8 Gross Characterization...

Page 77: ...as Setup Screen 4 Input the value as mole percent for each component shown in Table 6 9 The each value must be specified within the range shown in Table 6 9 Total mole percent must become 100 Standard...

Page 78: ...C4H10 i Butane mole percent 0 1 5 1 12 C4H10 n Butane mole percent 0 1 5 1 13 C5H12 i Pentane mole percent 0 0 5 2 14 C5H12 n Pentane mole percent 0 0 5 2 15 C6H14 n Hexane mole percent 0 0 1 16 C7H16...

Page 79: ...emarks 6 3 5 Fluid Operating Range Setup 1 Gas or Steam excluding Category Saturated steam F0628E EPS Figure 6 27 Fluid Operating Range Setup Screen 1 Input operating ranges and select units Pressure...

Page 80: ...e configuration If the temperature and pressure range input on the Fluid Operating Range Setup is too wide there is a probability of the calculation error of density is big These ranges are used only...

Page 81: ...value on the following page fluid physical property setup page and continue configuration If the pressure range input on the Fluid Operating Range Setup is too wide there is a probability of the calcu...

Page 82: ...used only for the density and viscosity calculation Range of Transmitter are not changed 6 3 6 Fluid Physical Property Setup 1 Gas or Steam Natural gas ISO physical properties setup F0633E EPS Figure...

Page 83: ...Operating Range Setup is narrow Please specify another value wider range and try again F0634E EPS Figure 6 33 Information message for setting range 2 Liquid F0635E EPS Figure 6 34 Fluid Physical Prope...

Page 84: ...S Figure 6 35 Apply Flow Configuration In order to download the configuration to the transmitter please select Apply Then perform download store to device from your frame application Please refer to C...

Page 85: ...flow factors being input manually NOTE 1 The flow unit is not automatically converted in basic mode 2 The flow range is set to LRV 0 and URV 100 when the Flow Configuration Mode is changed to Basic Mo...

Page 86: ...calculated according to the Flow unit category 3 Reter to table 6 5 6 6 6 7 Qm or Qv_norm 1 Kfactor Flow unit Category 3 P T Tb SPb SP P 1 Temp K1 T Tb P Tb T SP SPb 2 b 2 b norm 2 b 2 b 1 K 2 b 1 K...

Page 87: ...Electric Corporation IM 01C25R51 01E 2 Liquid F0639E EPS Figure 6 38 Basic Mode Setup for Liquid Input Reference Temperature Tb Kfactor Temp K1 Input Reference static pressure to 0 This factor is use...

Page 88: ...tter please select Apply Then perform download store to device from your frame application Please also refer to Chapter 5 and Figure 6 2 6 5 Obtain Flow Coefficient Click the Device Additional Functio...

Page 89: ...Blank Page...

Page 90: ...rent frame application can access the file Compatible between both protocol DTM HART and FF WinInstDrive Desk Top My Documents Default HART General parameters file XXXXXX prm HART Transmitter General...

Page 91: ...awa DTMs EJXMVTool Report File XXXXXX csv User flow parameters in CSV file format WinInstDrive Desk Top My Documents Default Physical property Error Log File 1 FF EJXMVToolFF log EJXMVToolFF1 log Back...

Page 92: ...and sub code is shown in error log file EJXMVTool log 8 1 Error Message Table 8 1 Error message T0801E EPS Code Sub code Explanation Recovery Information Message 600 8 Rank deficient The temperature...

Page 93: ...Blank Page...

Page 94: ...ed to take the following three steps 1 Uninstall field communication server Execute FieldInstDrive PRM Program PRMUninstall exe Double click the filename in Windows Explorer FieldInstDrive is the driv...

Page 95: ...FSA210 Uninstallation All Rights Reserved Copyright 2006 Yokogawa Electric Corporation IM 01C25R51 01E NOTE It takes a few seconds for the EXA Bossed service to stop FA0103E EPS Figure A1 3 Click OK F...

Page 96: ...stall the EJXMVTool program with the Add or Remove Programs function of the Windows Control Panel Select EJXMVTool and click Change Remove FA0105E EPS Figure A1 5 3 Uninstall Exaopc Use the Add or Rem...

Page 97: ...wa Electric Corporation IM 01C25R51 01E Click OK FA0107E EPS Figure A1 7 Click Yes FA0108E EPS Figure A1 8 Select Yes and click Finish This will reboot the computer FA0109E EPS Figure A1 9 NOTE After...

Page 98: ...updating on Offline parameters screen in EJX910 FF DTM 6 13 6 2 2 Add Note for xmv file made in FSA120 R 102 00 or before 6 19 6 3 3 Correct the method name for steam 6 23 6 3 4 Correct the mole vali...