4. Troubleshooting 

If the UPS system does not operate correctly, please solve the problem by using the table below.   

Symptom 

Possible cause 

Remedy 

The  AC  input  power  is  not 
connected well. 

Check  if  input  power  cord 
firmly  connected  to  the 
mains.   

No indication and alarm even 
though the mains is normal.   

The  AC  input  is  connected 
to the UPS output. 

Plug AC input power cord to 
AC input correctly.   

The icon 

and the warning code 

  flashing on LCD display and 

alarm is sounding every second. 

EPO function is activated. 

Set  the  circuit  in  closed 
position  to  disable  EPO 
function. 

The icon 

and 

  flashing on 

LCD display and alarm is sounding 
every second. 

Line and neutral conductors 
of UPS input are reversed. 

Rotate  mains  power  socket 
by 180° and then connect to 
UPS system. 

The icon 

and 

  flashing on 

LCD display and alarm is sounding 
every second. 

The external or internal 
battery is incorrectly 
connected. 

Check  if  all  batteries  are 
connected well. 

Fault code is shown as 27 and the 

icon 

 

is lighting on LCD 

display and alarm is continuously 
sounding. 

Battery  voltage  is  too  high 
or the charger is fault. 

Contact your dealer. 

Fault code is shown as 28 and the 

icon 

 

is lighting on LCD 

display and alarm is continuously 
sounding. 

Battery voltage is too low or 
the charger is fault. 

Contact your dealer. 

UPS is overload   

Remove  excess  loads  from 
UPS output. 

UPS is overloaded. Devices 
connected to the UPS are 
fed directly by the electrical 
network via the Bypass. 

Remove  excess  loads  from 
UPS output. 

The icon 

  and

is 

flashing on LCD display and alarm 
is sounding twice every second. 

After repetitive overloads, 
the UPS is locked in the 
Bypass mode. Connected 
devices are fed directly by 
the mains. 

Remove  excess  loads  from 
UPS output first. Then shut 
down the UPS and restart it. 

Fault code is shown as 43 and The 

icon 

 

is lighting on LCD 

display and alarm is continuously 
sounding. 

The UPS shut down 
automatically because of 
overload at the UPS output. 

Remove  excess  loads  from 
UPS output and restart it. 

Содержание POWERMUST 1008 ONLINE LCD

Страница 1: ...PowerMust 1008 Online LCD RM PowerMust 2016 Online LCD RM PowerMust 3024 Online LCD RM Online UPS User Manual EN...

Страница 2: ...s 3 2 Installation and setup 4 2 1 Rear panel view 4 2 2 Setup the UPS 5 3 Operations 7 3 1 Button operation 7 3 2 LCD Panel 7 3 3 Audible Alarm 9 3 4 LCD display wordings index 9 3 5 UPS Setting 9 3...

Страница 3: ...er them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed sh...

Страница 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Страница 5: ...rMust 3024 Online LCD Standard PowerMust 3024L Online LCD Long run 2 1 Rear panel view PowerMust 1008 L Online LCD PowerMust 2016 L Online LCD PowerMust 3024 L Online LCD PowerMust 1008 L Online LCD R...

Страница 6: ...5 12 Output circuit breaker...

Страница 7: ...or the wiring configuration a Remove the small cover of the terminal block b Suggest using AWG14 or 2 1mm2 power cords Suggest using WG12 10 or 3 3mm2 5 3mm2 power cords for NEMA type c Upon completio...

Страница 8: ...tware to fully configure UPS shutdown You may insert provided CD into CD ROM to install the monitoring software If not please follow steps below to download and install monitoring software from the in...

Страница 9: ...e UPS will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS set...

Страница 10: ...6 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuit Programmable outlets information Indicates that programmable management outlets are working Mode operatio...

Страница 11: ...reviation Display content Meaning ENA Enable DIS Disable ESC Escape HLS High loss LLS Low loss BAT Battery CF Converter EP EPO FA Fan TP Temperature CH Charger 3 5 UPS Setting There are three paramete...

Страница 12: ...ency setting Interface Setting Parameter 2 3 Output frequency setting You may set the initial frequency on battery mode BAT 50 presents output frequency is 50Hz BAT 60 presents output frequency is 60H...

Страница 13: ...240 VAC models 230 264 setting the high voltage point in parameter 3 from 230Vac to 264Vac For 110 115 120 127 VAC models 120 132 setting the high voltage point in parameter 3 from 120Vac to 132Vac L...

Страница 14: ...ry mode When the input voltage is beyond the acceptable range or power failure and alarm is sounding every 4 second UPS will backup power from battery Bypass mode When input voltage is within acceptab...

Страница 15: ...cond Battery is not connected Sounding every second Over Charge Sounding every second Site wiring fault Sounding every second EPO enable Sounding every second Fan Failure Sounding every second Over te...

Страница 16: ...cted Check if all batteries are connected well Fault code is shown as 27 and the icon is lighting on LCD display and alarm is continuously sounding Battery voltage is too high or the charger is fault...

Страница 17: ...p time is shorter than nominal value Batteries defect Contact your dealer to replace the battery The icon and the warning code flashing on LCD display and alarm is sounding every second Fan is locked...

Страница 18: ...Harmonic Distortion 3 THD Linear Load 6 THD Non linear Load 4 THD Linear Load 7 THD Non linear Load AC Mode to Batt Mode Zero Transfer Time Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure Sin...

Отзывы: