Command Value
83 (0x53)
Name
Data Type
Byte
Bits
Description
Command
Byte
1
Command for index pointer (which message your sending)
INMODE1A
4 bit
2
1,2,3,4
Mode 0x0=disabled, 0x1=Digital Positive, 0x2=Digital Ground
INMODE1B
5,6,7,8
Mode 0x0=disabled, 0x1=Digital Positive, 0x2=Digital Ground, 0x3= 4-20mA (4000-20000),
0x4= 0-5V DC (0-5000, 0x5= 0-10V DC (0-10000), 0x6= 0-32V DC(0-32000),
0x9= Ratiometric (0-100.0% of source V DC)
INMODE2A
3
1,2,3,4
Mode 0x0=disabled, 0x1=Digital Positive, 0x2=Digital Ground
INMODE2B
5,6,7,8
Mode 0x0=disabled, 0x1=Digital Positive, 0x2=Digital Ground, 0x3= 4-20mA (4000-20000),
0x4= 0-5V DC (0-5000, 0x5= 0-10V DC (0-10000), 0x6= 0-32V DC(0-32000),
0x9= Ratiometric (0-100.0% of source V DC)
INMODE3A
4
1,2,3,4
Mode 0x0=disabled, 0x1=Digital Positive, 0x2=Digital Ground
INMODE3B
5,6,7,8
Mode 0x0=disabled, 0x1=Digital Positive, 0x2=Digital Ground, 0x3= 4-20mA (4000-20000),
0x4= 0-5V DC (0-5000, 0x5= 0-10V DC (0-10000), 0x6= 0-32V DC(0-32000),
0x9= Ratiometric (0-100.0% of source V DC)
INMODE4A
5
1,2,3,4
Mode 0x0=disabled, 0x1=Digital Positive, 0x2=Digital Ground
INMODE4B
5,6,7,8
Mode 0x0=disabled, 0x1=Digital Positive, 0x2=Digital Ground, 0x3= 4-20mA (4000-20000),
0x4= 0-5V DC (0-5000, 0x5= 0-10V DC (0-10000), 0x6= 0-32V DC(0-32000),
0x9= Ratiometric (0-100.0% of source V DC)
INMODE5A
6
1,2,3,4
Mode 0x0=disabled, 0x1=Digital Positive, 0x2=Digital Ground
INMODE5B
5,6,7,8
Mode 0x0=disabled, 0x1=Digital Positive, 0x2=Digital Ground, 0x3= 4-20mA (4000-20000),
0x4= 0-5V DC (0-5000, 0x5= 0-10V DC (0-10000), 0x6= 0-32V DC(0-32000),
0x9= Ratiometric (0-100.0% of source V DC)
INMODE6A
7
1,2,3,4
Mode 0x0=disabled, 0x1=Digital Positive, 0x2=Digital Ground
INMODE6B
5,6,7,8
Mode 0x0=disabled, 0x1=Digital Positive, 0x2=Digital Ground, 0x3= 4-20mA (4000-20000),
0x4= 0-5V DC (0-5000, 0x5= 0-10V DC (0-10000), 0x6= 0-32V DC(0-32000),
0x9= Ratiometric (0-100.0% of source V DC)
INMODE7A
4 bit
8
1,2,3,4
Mode 0x0=disabled, 0x1=Digital Positive, 0x2=Digital Ground,
0x7=Digital Positive Frequency
,
0x8= Counter, 0xA=Encoder
INMODE7B
4 bit
8
5,6,7,8
Mode 0x0=disabled, 0x1=Digital Positive, 0x2=Digital Ground, 0x3= 4-20mA (4000-20000),
0x4= 0-5V DC (0-5000, 0x5= 0-10V DC (0-10000), 0x6= 0-32V DC(0-32000),
0x9= Ratiometric (0-100.0% of source V DC)
5.3.4 FRE./COUNTER/ENCODER OPERATION
5.3.4.1 FREUENCY
1. The input must be put into Frequency MODE = 7 (Only valid on input 7A & 8A)
This puts the Input into frequency operation mode. When a positive signal is present on the input pin, the frequency will be shown.