Instruction manual for devices of the MASI20 series
18
V 1.0
3.4.3 Wiring system
3.4.3.1 Stripping connectors
To connect a terminal for module MASI20 it is initially necessary to lead the wire in the terminal then to fix
the cap of the terminal by strongly supporting until locking of the cap (pins on the side) so that the claws
make a good contact with the heart of the wire. This terminal makes it possible to ensure the continuity of
the bus even if module MASI20 is disconnected.
The connection of the cables is identical for both connection.
The acceptable section of wire goes from 0,5 to 0,75mm².
1
-
+
2
-
+
Fig 3-4 :
wiring stripping connectors
3.4.3.2 Screw connectors
AS accessory
6
we provide screw connectors. Those one accept a bigger wire section but don’t ensure the
continuity of the bus even if module MASI20 is disconnected.
The connection of the cables is identical for both connection.
The acceptable section of wire goes from 0,5 to 1,5mm².
1
2
0,22Nm
Fig 3-5 :
wiring screw connectors
6
AS-i (yellow) Ref. 55 211
Power (black) Ref. 55 212