6.3 Outputs
A short-circuit or an overload on the outputs corresponds to a peripheral error (FID) of the slave ; error
indicated by the master if it is in conformity with the specification AS-i 2.1.
§
The slave indicates such errors by flashing display of the red LED „F
AULT
“. The slave still works
normally.
§
The short-cut output is disconnected by the output driver.
§
The master indicates the peripheral error by flashing display of the „
CONFIG ERR
“ LED.
When the cause of the error has been corrected.
§
The slave is reset (the red LED „F
AULT
“ is off ).
§
The output is reset (initial status on the AS-i bus).
§
The error is no more indicated by the master.
By commuting big capacitive load it is possible that the module indicate a periphery