Software Release: [TBD]
Section 40
27
00-02-1167
2018-09-18
Prestart Delay
(Low Security)
: Factory set to 00.00.00
Prestart Delay 2
(Low Security)
:
after a start condition has been accepted by the controller, this
delay begins timing, and the prestart #2 output turns on.
Auto Only
(Medium Security)
: Factory set to Disabled.
Prestart Delay
(Low Security)
: Factory set to 00.00.00
Prestart Delay 2 Mode
(High Security)
:
this setting determines if the prestart #2 output is active
through the crank state or only through the prestart #2 state.
Factory set to PreCrank
Spindown Timer
(Medium Security)
:
this delay begins timing when there is no call to run and the
engine speed is zero. No auto start functions will occur until this delay expires.
Factory set to 30
seconds
(Unable to set below 5 seconds)
Post Crank Lockout Setup
(Medium Security)
:
this is a setup for a delay that begins timing after
crank disconnect at startup. During this delay, the selected functions are ignored. When this delay
expires, the selected functions are armed. During the duration of this delay, the selected functions
can cycle from active to not active and not reset the delay.
Post Crank Lockout Time
(Medium Security)
: Factory set to 30 seconds
Post Crank Lockout 1
(Medium Security)
: Factory set to Low Oil Pressure
Post Crank Lockout 2
(Medium Security)
: Factory set to High Engine Temperature
Post Crank Lockout 3
(Medium Security)
: Factory set to Disabled
Post Crank Lockout 4
(High Security)
: Factory set to Disabled
Post Crank Lockout 5
(High Security)
: Factory set to Disabled
Post Warm-up Lockout Setup
(Medium Security)
:
this is a setup for a delay that begins timing
when the warm-up delay expires. During this delay, the selected functions are ignored. When this
delay expires, the selected functions are armed. During the duration of this delay, the selected
functions can cycle from active to not active and not reset the delay.
Post Warm-up Lockout Time
(Medium Security)
: Factory set to 00.00.00
Post Warm-up Lockout 1
(Medium Security)
: Factory set to Disabled
Post Warm-up Lockout 2
(Medium Security)
: Factory set to Disabled
Post Warm-up Lockout 3
(Medium Security)
: Factory set to Disabled
Post Warm-up Lockout 4
(High Security)
: Factory set to Disabled
Post Warm-up Lockout 5
(High Security)
: Factory set to Disabled
Bubble Lockout Setup
(Medium Security)
:
this is a setup for a delay that begins timing when the
selected functions are active. If the selected functions are removed during this delay, the delay
resets to zero. If the selected functions remain active throughout this delay, the selected action for
the parameter will occur.
Bubble Lockout Time
(Medium Security)
: Factory set to 00.00.00
Bubble Lockout 1
(Medium Security)
: Factory set to Disabled
Bubble Lockout 2
(Medium Security)
: Factory set to Disabled
Bubble Lockout 3
(Medium Security)
: Factory set to Disabled
Bubble Lockout 4
(Medium Security)
: Factory set to Disabled
Bubble Lockout 5
(Medium Security)
: Factory set to Disabled