Software Release: [TBD]
Section 40
13
00-02-1167
2018-09-18
Communication
The Communications menu allows the operator to choose the type of RS485 communications such as PVA
Gauge, Modbus or Local Display. The menu also allows for the operator to choose CAN termination and
enabling of the CAN Parameter Map. Review Communication under the Menu Glossary section of this
manual for a full list and definition of each setting.
Passcodes
The Passcodes menu is only available in the high security menu and allows the operator to see the three
level of passcodes set in the controller. The passcodes are read only in this view. Passcodes are able to
be changed from default passcode setting via PowerVision for Controllers configuration tool.
Load Configuration
The Load Configuration menu is only available in the high security menu. This menu item allows the
operator to choose a file to load onto the controller when a USB drive is attached to the programming
harness of the controller. Review Load Configuration under the Menu Glossary section of this manual for
a full list and definition of this item.
Auto Start/Stop Functions Defined
There are two automatic start/stop types in the MGC1000. Each is detailed below:
Single Contact Start/Stop (commonly known as a contact from a transfer switch)
The Single Contact Start/Stop occurs when a remote contact is active for auto start and inactive for an auto
stop as a digital input.
Local Start Key Start/Stop
The Local Start Key function uses the green and red buttons on the front interface for auto start and stop
sequencing. The passcode of 1212 must be entered for the first key start after power up.
Quick-Start Setup
The following sections provide a walk-through of the steps necessary for some of the various configurations
and settings available on the MGC1000 Controller.
Cycling power to the controller is recommended
after making changes to set points.
Stepping through the Menu will be depicted as follows:
Menu/System/Brightness directs the operator to go into the Menu first, then look for a parameter titled
System and press
[Enter]
to go into the System menu. Then look for a parameter titled Brightness and
press
[Enter]
to go into the Brightness menu, etc.
Mechanical Engine Setup
1. Access
Menu/Engine Settings/Engine Type,
and select Mechanical then press
[Enter]
.
2. Press down arrow to
Engine Manufacturer
, select which engine manufacturer the controller is/will be
used then press
[Enter]
.