background image

(c)  “Water Temperature” light will come on and engine will

stop.

(d)  Turn Mode Selector switch OFF.

4-4.9 Low Water Temperature; to test the low water temperature
alarm circuit:

(a)  Engine does not have to be running.
(b)  Use a jumper wire and short from terminal 31 to 4.
(c) “Low Water Temperature” alarm light will come on as long

as the jumper maintains the circuit.

4-4.10 Other Alarm and/or Shutdowns;  all other alarms and
shutdowns would be tested in the same manner.

(a)  For shutdown circuits, the engine must be running for test.
(b)  Most alarm only circuits can be tested without starting the

engine.  Low Oil Pressure Pre-alarm and High Water
Temperature Pre-alarm are exceptions.

(c)  To test other shutdowns or alarms, a jumper wire can be

used to short out the switch contacts at the switch or if this
is not possible, the test can be run by shorting the input
terminal for that circuit, to ground, terminal 4.

(d)  To test Low Oil Pressure Pre-alarm;

1. Turn Mode Selector switch to TEST.  When engine

starts, wait 30 seconds then,

2.  Use a jumper wire and short from terminal 50 to 4;

“Low Oil Pressure Pre-alarm” light will come on as
long as the jumper maintains the circuit.

(e)  To test High Water Temperature Pre-alarm;

1. Turn Mode Selector switch to TEST.  When engine

starts, wait 30 seconds then,

2.  Use a jumper wire and short from terminal 51 to 4;

“High Water Temperature Pre-alarm” light will come
on as long as the jumper maintains the circuit.

Section 5: Operation

5-1  Operator Controls.
5-1.1  
Mode Selector Switch;  allows the operator to select either
manual (TEST), automatic operation (AUTO), or no operation
(OFF).
5-1.2 The OFF position on the mode selector also provides a
reset function for the shutdown circuits.  If the engine is shut
down by the automatic control, the operator must turn selector
off and back on to reactivate the system.
5-1.3 Push to Test Lamps;  this pushbutton tests the alarm and
shutdown indicator lights.
5-1.4  Alarm Silence Pushbutton;  if so equipped, silences the
local and remote audible alarm.  Visual indicator remains on
until reset or sensor switch contacts clear.

5-2  Operating Modes.
5-2.1  
The A900 Generator Engine Control has two operating
modes: manual and automatic.
5-2.2  Manual Operation is provided for testing of the generator
set.
5-2.2.1  To initiate Manual Control, place the Mode Selector
switch in the TEST position.  This provides the automatic
control a start signal.
5-2.2.2  To stop, turn selector switch to OFF.  This removes start
signal and the engine will stop.
5-2.3 Automatic operation is the normal mode.
5-2.3.1 To initiate Automatic Control, place the Mode Selector
switch in the AUTOMATIC position.  When a start signal is

received, the engine will start.
5-2.3.2 When the start signal is removed, the engine will stop.
It is now ready to restart.
5-2.4  OFF or Not Operating; to prevent operation of the engine,
turn selector switch OFF.

Section 6: Routine Maintenance 

and Operational Tests

6-1 Routine Maintenance.
6-1.1 
Due to the design and types of components used, very
little maintenance is required to the A900 Control.
6-1.2  Visual inspection of the internal wiring of the control
panel, along with checking wire connections for tightness,
should be done on a semiannual schedule for stand-by systems
or quarterly for prime power.  Check wire bundles for chafing
and wear to the insulation of the wires where they contact the
panel or engine.
6-1.4  Shutdown and Alarm Circuits should be tested on a
monthly basis for prime power and quarterly for stand-by sets.
The same tests run during pre-operation check out, Section 4-4,
should be included.

6-2  Operational Tests.
6-2.1 
No special operational tests are required.  The routine
operational tests for the generator set will exercise the control.

Section 7: Troubleshooting and Repair

7-1  Tools Required.
7-1.1  
Some of the tools necessary for troubleshooting are built
into the A900 Series controls.
7-1.1.1 By observing the lights on the front and rear of the control
panel, clues to a problem and the possible source can be seen.
7-1.1.2 Operational problems with the automatic engine control
will show up by looking at the input and output lights on the rear
of the A900 SELECTRONIC

®

Control / Display Module.

7-1.2  Other tools which may be required are:
7-1.2.l  AC/DC Voltmeter for taking voltage readings and an
Ohmmeter for testing resistance of wires and connections.
7-1.2.2 Jumper wires with alligator clips to bypass or simulate
circuit closures.
DO NOT USE THESE JUMPER WIRES TO CHECK IF
VOLTAGE IS PRESENT AT A TERMINAL BY DRAWING
AN ARC TO GROUND.  THIS WILL DAMAGE OR
DESTROY EQUIPMENT IN THE A900 CONTROL PANEL.

7-2  A900 SELECTRONIC Control Operation And

Shutdown.

7-2.1 The first step in troubleshooting any equipment is to
understand its normal operation.  Table 7-2.1 contains normal
voltage readings taken at the terminals of the A901 with all
equipment shown on the standard drawing, connected.

(a)  All voltage readings are DC, except at terminal 29, and

were taken with the negative lead of the meter connected
to ground at terminal 4.  Voltage reading at terminal 29
was taken with negative lead grounded and the meter on
AC scale.

(b)  The battery voltage, at the time readings were recorded,

was 13.8 V and 27.6 V.  All readings will vary depending
on battery voltage, equipment supplied in the panel and
external devices connected to the A900 control.  See notes

21

Содержание MURPHYMATIC A900 Series

Страница 1: ...SERIES A900 MURPHYMATIC GENERATOR ENGINE CONTROL SYSTEM DESIGN INSTALLATION AND OPERATING MANUAL A900 9025N Revised 10 99 Section 40 00 02 0197...

Страница 2: ...ot operate during installation Follow all safety warnings of the machine manufacturer Read and follow all installation instructions Certain danger to human safety and to equipment may occur if some eq...

Страница 3: ...4 Installation 14 4 1 Location 14 4 2 Wiring 14 4 3 Crank Disconnect 19 4 4 Pre Operational Check Out 19 Section 5 Operation 21 5 1 Operator Controls 21 5 2 Operating Modes 21 Section 6 Routine Maint...

Страница 4: ...phy c SWICHGAGE A combination indicating gauge and switch d TATTLETALE A term that refers to a shutdown indicating device or circuit in the control panel 1 5 How to use this manual 1 5 1 Section 1 2 4...

Страница 5: ...of a two cycle engine 3 1 7 Table 3 1 7 illustrates the alarm and shutdown require ments of NFPA 110 NFPA99 and CAN CSA C282 M89 and compares the features of the A900 series controls to those require...

Страница 6: ...X X X O O i Control Switch not set in Auto X X X X O O O X X X X X X X X O O j High Battery Voltage X X X O O O X X X O O k Low VoltageBattery X X X O O O X X X X X X X O O l Lamp Test X X X X X X X...

Страница 7: ...preset speed c Oil Pressure tripped by the oil pressure SWICHGAGE if pressure drops below preset point while the engine is running d Water Temperature tripped by the water temperature SWICHGAGE if en...

Страница 8: ...automatic control and the engine start sequence begins 3 3 1 2 Lamp Test Pushbutton Tests the lights on the A 901 2 module 3 3 1 3 Alarm Silence Pushbutton Turns off any audible alarm that is connecte...

Страница 9: ...ill running Since the Overspeed shutdown circuit is activated by the frequency input it prevents the engine from running without overspeed protection g Remote Shutdown this circuit is provided to shut...

Страница 10: ...ntrol Module includes the following engine control features a Cycle crank circuit will crank the engine for 15 seconds then rest for 15 seconds until the engine starts The crank rest time is selectabl...

Страница 11: ...s circuit is provided for an additional alarm that may be required by the user 3 4 2 Relay Module The Relay Module figure 3 4 2 includes all of the control alarm and shutdown relays that are required...

Страница 12: ...is depressed the set point of the speed switch is lowered approximately 10 3 The push to test switch can also be used to set the overspeed switch at approximately 110 of running speed Hold the switch...

Страница 13: ...he Mode Selector Switch is in either Auto or Test When the Mode Selector is turned Off the Control On signal is open This can be used to signal switch position or to reset an external circuit when the...

Страница 14: ...ing With engine speed at 1800 RPM or 3540 Hz g Cooldown circuit this circuit keeps the engine running for five minutes after the transfer switch has removed the load from the generator and signaled th...

Страница 15: ...Test and no shutdown TATTLETALE circuit is latched on This can be used to signal that the generator engine is ready to automatically start or is running in Test 3 6 3 3 The Control On function at term...

Страница 16: ...tdown Circuits provide first out indication of cause of shutdown These circuits deactivate the fuel relay and lockout the A903 until reset Shutdown circuits are activated by the crank disconnect circu...

Страница 17: ...ces recommended for installation 4 1 3 Wiring Terminals Terminal blocks are provided on both sides of the Control Display enclosure and the Relay Module Torque all terminal screws to 12 inch pound max...

Страница 18: ...3 4 in 171 mm 9 3 8 in 238 mm 6 in 152 mm 4 15 32 in 114 mm Mounting Holes 1 8 in 3 mm diameter 1 1 2 in 38 mm clearance 5 in 127 mm maximum between A 900 Series module relay module when mounting 1 7...

Страница 19: ...REMOTE AUDIBLE LOCAL AUDIBLE N C N C OVERSPEED RELAY SHUTDOWN RELAY FUEL RELAY CRANK RELAY AUX CRANK DISCONNECT N C CONTROL ON SYSTEM READY FUSED B B Energize to Stop solenoid Energize to Run solenoid...

Страница 20: ...Alarm I Fuel Relay J1 J2 Q2 Q1 J1G Red Blk LOW WATER LEVEL REMOTE VISUAL REMOTE AUDIBLE LOCAL AUDIBLE N C N C OVERSPEED RELAY SHUTDOWN RELAY FUEL RELAY CRANK RELAY AUX CRANK DISCONNECT N C CONTROL ON...

Страница 21: ...dible Alarm H Shut Down Relay D Local Audible Alarm I Fuel Relay J1 J2 Q2 Q1 J1G Red Blk LOW WATER LEVEL REMOTE VISUAL REMOTE AUDIBLE LOCAL AUDIBLE N C N C OVERSPEED RELAY SHUTDOWN RELAY FUEL RELAY CR...

Страница 22: ...e to increase setting The adjustments are 20 turn controls without stops at either end 4 4 1 1 Be sure to have a fully charged battery to do these tests Low battery voltage can cause improper results...

Страница 23: ...on and the engine shuts down f Release pushbutton check Overspeed light on front panel to be sure it is on g Turn Mode Selector switch OFF to reset shutdown circuits then back to TEST h When engine s...

Страница 24: ...the Mode Selector switch in the AUTOMATIC position When a start signal is received the engine will start 5 2 3 2 When the start signal is removed the engine will stop It is now ready to restart 5 2 4...

Страница 25: ...put Voltage Input Voltage Input Voltage Input Voltage Input Voltage 13 8 27 6 13 8 27 6 13 8 27 6 13 8 27 6 13 8 27 6 31 6 6 6 6 6 6 6 6 6 6 32 6 6 6 6 6 6 6 6 6 6 33 6 6 6 6 6 6 6 6 6 6 34 6 6 6 6 6...

Страница 26: ...o shutdown the engine and generator a The TATTLETALE light for that function turns on b Shutdown relay K 2 is energized closing its contacts at terminal 9 These contacts can be wired to a shunt trip s...

Страница 27: ...e OEM parts and are available only to Detroit Diesel and their distributors 8 2 1 The A900 DDC parts are the same as the Murphy A900 series that has been covered throughout the A900 manual except the...

Страница 28: ...1722 410697 fax 44 1722 410088 e mail france fwmurphy co uk www fwmurphy co uk francais htm In order to consistently bring you the highest quality full featured products we reserve the right to chang...

Отзывы: