a. Cartridge – The water flow can be adjusted using a slotted narrow blade screwdriver and turning
clockwise to increase flow and counterclockwise to decrease flow.
TROUBLE SHOOTING:
c. Transformer polarity crossed. Replace transformer, sensor may be damaged and also need replacement.
e. Sensor is picking up a highly reflective surface. Eliminate cause of reflection and wait 30 seconds before
checking.
b. There is debris or scale in the solenoid assembly. Remove solenoid, pull out plunger and spring. Clean
with scale remover solution.
e. The cartridge valve located in the water control assembly or bubbler can also become clogged with
foreign material. The cartridge valve can only be replaced and not repaired.
a. Repair bad connection from sensor to solenoid.
b. Replace valve cartridge.
c. Bubbler Stream - Bubbler can be rotated slightly to direct the stream backwards or forwards. Adjust the
stream to minimize splashing. Splashing may occur from bubbler stream if the unit is not level. Shim lower
mounting point, if necessary, to level chiller.
a. Ensure water supply service stop valve is fully open.
d. Check the water inlet “Y” strainer. Sediment from the main supply can get trapped in the screen along
with installation materials such as pipe dope and flux. The screen should be cleaned and checked on a
regular basis and replace if needed.
1. ADJUSTMENTS:
b. Cold Water Thermostat – The water temperature can be adjusted using a slotted screwdriver and turning
clockwise to make colder and counterclockwise to make warmer.
c. Check for twists or kinks in outlet tubing.
4. IF LIGHT WITHIN SENSOR DOES NOT FLASH ONCE WHEN USER IS WITHIN RANGE:
3. WATER DRIPS OR WILL NOT SHUT OFF:
f. Check flow adjustment. See start up note #3.
h. No power to transformer connections, loose or wires cut.
a. Open fixture. Loosen nuts holding valve bracket assembly to bottom of fixture but do not remove. Move
complete valve bracket assembly further back from the front push pad and tighten to lock in place.
2. RESTRICTED OR NO WATER FLOW:
SENSOR TROUBLE SHOOTING:
a. Verify 120VAC input & 9VDC output transformer output 9VDC.
b. Replace defective transformer.
b. Verify minimum 20 psig supply line flow pressure.
g. Flow control in solenoid valve outlet elbow clogged remove & clean.
d. Sensor in “Security Mode” after 30 seconds of consistent detection. Remove source of detection and wait
30 seconds before checking.
5. IF LIGHT WITHIN SENSOR LENS FLASHES ONCE WHEN THE USER IS WITHIN RANGE:
c. There is debris or scale in the center or two holes in convolution of the water diaphragm. Remove and
clean
A151-VR-BF4
Page 15 of 19
New:
10/28/2020
7021-021-001
MURDOCK MFG. •
15125 Proctor Avenue • City of Industry, CA 91746 USA
Phone 800-453-7465 or 626-333-2543 • Fax 626-855-4860 • www.murdockmfg.com
Member of
CONTEMPORARY WATER COOLERS
I N S TA L L AT I O N / M A I N T E N A N C E I N S T R U C T I O N S
DRINKING FOUNTAINS