5.3. Shut down. 
 

 

Set switch to “OFF” to shut the flame off. The fan will go on rotating for 1 min 45 sec to cool the heater 

down.  The  fan  motor  will  automatically  stop  at  the  end  of  the  aftercooling  time,  then  the  unit  can  be 
disconnected from mains. 

 

Never disconnect the supply plug to stop the heater while in operation 

The big amount of heat produced could damage the components: allow cooling sequence to take place  

 
6. MAINTENANCE

 

 

 

Before carrying out any maintenance operation, disconnect the power plug. 

 

Maintenance must be carried out by qualified personnel (see also par. 7) 

 

The appliance must be thoroughly cleaned once a year to ensure good combustion and long life. 

 

Clean periodically 

 

the oil spraying nozzle and its filter; 

 

the oil pump filter 

 

the main fuel filter cartridge 

 

the ignition electrodes 

 

the fan blades 

 

the inside of the appliance, using compressed air 

 

the flame sensor with a mild detergent  

 

Periodically check cables and electrical connections.  

 

Check the oil filter and replace if necessary. 

  

7. TROUBLESHOOTING 
 

TROUBLE 

CAUSE 

SOLUTION 

Heater does not start 

No power 
 

Check  main  distribution  board  and 
power supply line  

 

Faulty cable/connections 

Check/have  cable  replaced  by  a 
qualified electrician 

 
 

Burnt fuse 
Room thermostat set too low  

Check and replace if required 
 
Set  room  thermostat  on  a  higher 
temperature 

 

Room  thermostat  socket  cap  not 

inserted 

Insert cap into the thermostat socket 

 

Heater in lock-out mode 

Reset  

Dirty or faulty flame sensor  

Clean or replace 

Heater  starts,  flame  ignites  but  then 
heater locks out 

 
Faulty burner control unit  

 
Contact service personnel 

Clogged nozzle 

Clean or replace 

Flame  sensor  receives  an  external  light 
signal during ignition sequence 

Check  for  external  lights  (sun,  lamps, 
etc.)   

Heater starts, flame  does  not  ignite and 
then heater locks out 

Faulty burner control unit 

Contact service personnel 

 

No fuel 

Fill tank 

 

Ignition fault, dirty or incorrectly spaced 
electrodes  

Clean 

electrodes, 

contact 

service 

personnel if required 

Dirty or blocked nozzle 

Clean or replace 

Clogged filters 

Clean or replace 

Heater  starts,  but  combustion  is  not 
good  

Leakes in fuel circuit 

Check and eventually replace 

 

Oil pump provides low pressure 

Contact service personnel 

 

Insufficient combustion air 

Wrong air lock setting  

 

Insufficient ventilation air 

Contact service personnel 

Heater  stops  as  the  air  pressure  switch 
functions  

The appliance has overheated 
Faulty pressure switch 

See par. 5.2. 
Contact service personnel 

Содержание MIR 37 WU

Страница 1: ...Operating Installation and Service Instructions Direct and Indirect fired Diesel Kerosene Heaters TOR 67 WU TOR 115 WU TOR 175 WU MIR 37 WU MIR 55 WU MIR 85 WU TOR MIR ...

Страница 2: ...________________________________________________________________________________________________ 2 ...

Страница 3: ...ERIALS PAPER OR CARDBOARD A SAFE DISTANCE AWAY FROM THE HEATER AS RECOMMENDED BY THE INSTRUCTIONS NEVER USE THE HEATER IN SPACES WHICH DO OR MAY CONTAIN VOLATILE OR AIRBORNE COMBUSTIBLES OR PRODUCTS SUCH AS GASOLINE SOLVENTS PAINT THINNER DUST PARTICLES OR UNKNOWN CHEMICALS WARNING COMBUSTION BY PRODUCTS PRODUCED WHEN USING THIS PRODUCT CONTAIN CARBON MONOXIDE A CHEMICAL KNOWN TO THE STATE OF CALI...

Страница 4: ...0 180 900 288 700 Air Flow Rate ft min 1180 1470 2650 Fuel Types Diesel Kerosene 1 2 Fuel Oil Fuel Consumption gal hr 0 88 1 28 2 04 Fuel Nozzle 0 65 60 H 1 00 60 H 1 50 80 W Efficiency 87 1 87 1 88 5 Noise Level at 2m dB A 75 73 73 Voltage V 115V 60Hz 1ph Electrical Power W 460 460 800 Current Rating A 7 0 7 0 12 5 Weight lb 154 178 282 Lenght in 47 54 8 68 0 Width in 24 27 6 29 5 Height in 31 32...

Страница 5: ...e unit level When a direct fired heater or an indirect fired heater not connected to a flue pipe is used in a closed room provide a minimum opening area of 3 ft2 per US gallon capacity at the unit level and a continuous natural air circulation through windows and doors For the use of the heater the general and special fire safety regulations in force in all fields of applications must be followed ...

Страница 6: ...himney or to a exhaust duct To get a proper draught at least 0 1 mbar in the chimney the exhaust gas path must rise Avoid any elbows and bends in the first part of the exhaust ducts for at least 3 m For operation of heater in closed rooms without flue refer to the instructions for installation par 4 If a room remote thermostat is used set maximum temperature on it Turn switch to position ON Set th...

Страница 7: ...wer Check main distribution board and power supply line Faulty cable connections Check have cable replaced by a qualified electrician Burnt fuse Room thermostat set too low Check and replace if required Set room thermostat on a higher temperature Room thermostat socket cap not inserted Insert cap into the thermostat socket Heater in lock out mode Reset Dirty or faulty flame sensor Clean or replace...

Страница 8: ... Solenoid Valve TR Ignition Transformer M Motor SL Warning Lamp PA Air Pressure Switch FS Fuse FC Flame Sensor PL Reset Button IN Switch TH Remote Thermostat FR Heated Filter TOR 175 WU TH IN FC EV M black green green black white PL TR white EV TR M L N FR TRcont FC PL TH IN PL black black black white white L N FR SL green white red black white white white black M13 M17 M15 M9 M7 M11 M18 M16 M14 M...

Страница 9: ...________________________________________________________________________________________________ 9 ...

Страница 10: ...________________________________________________________________________________________________ 10 ...

Отзывы: