THE  ELECTRICAL  SYSTEM  TO  WHICH  THE  APPLIANCE  IS  CONNECTED  MUST  COMPLY 

WITH ALL SAFETY REGULATIONS IN FORCE. A RESIDUAL CURRENT CIRCUIT BREAKER MUST 
BE PROVIDED ON THE MAIN DISTRIBUTION BOARD. 

 

 

UNPLUG THE HEATER BEFORE ATTEMPTING ANY SERVICE OR MAINTENANCE. 

 

ALWAYS  CHECK  THE  POWER  SUPPLY  CABLE  BEFORE  USE.  IT  MUST  NOT  BE  BENT, 

CRUSHED, OR ANYWAY DAMAGED. 

 

THE POWER SUPPLY CABLE MUST BE REPLACED ONLY BY QUALIFIED PERSONNEL. 

 

ONLY USE AN ORIGINAL POWER CABLE WITH A 3-PIN GROUNDED PLUG. 

 

DO NOT TOUCH THE EXHAUST GAS OUTLET. DANGER OF BURNS! 

 

2. PRODUCT DESCRIPTION

 

 

 

Mobile space heater with: 

 

closed combustion chamber and gas exhaust duct  (indirect-fired models) 

 

open combustion chamber (direct-fired models) 

 

3. TECHNICAL SPECIFICATIONS

 

 
3.1 Indirect-fired heaters 
 

Model # 

MIR 37 WU 

MIR 55 WU 

MIR 85 WU 

Firing rate (BTU/hr) 

125,200 

180,900  

288,700  

Air Flow Rate (ft³/min) 

1180 

1470 

2650 

Fuel Types 

Diesel / Kerosene / #1-2 Fuel Oil 

Fuel Consumption (gal/hr) 

0.88 

1.28 

2.04 

Fuel Nozzle 

0.65 60°H 

1.00 60° H 

1.50 80° W 

Efficiency (%) 

87.1 

87.1 

88.5 

Noise Level at 2m (dB(A)) 

75 

73 

73 

Voltage (V) 

115V 60Hz 1ph 

Electrical Power (W) 

460 

460 

800 

Current Rating (A) 

7.0 

7.0 

12.5 

Weight (lb) 

154 

178 

282 

Lenght  (in) 

47 

54.8 

68.0 

Width (in) 

24 

27.6 

29.5 

Height (in) 

31 

32.7 

40.4 

Flue Diameter (in) 

Tank Capacity (gal) 

14 

26.5 

36.0 

Fuel Pressure (psi) 

175 

175 

175 

Air Lock Setting  

3.5 

 
3.2 Direct-fired heaters 
 

Model # 

TOR 67 WU 

TOR 115 WU 

TOR 175 WU 

Firing rate (BTU/hr) 

227,000 

396,500 

607,000 

Air Flow Rate (ft³/min) 

1650 

2825 

3240 

Fuel Types 

Diesel/Kerosene/ #1-2 Fuel Oil 

Fuel Consumption (gal/hr) 

1.60 

2.80 

4.28 

Fuel Nozzle 

1.25 60°S 

2.25 80°W 

3.50 80°S 

Efficiency (%) 

100 

100 

100 

Noise Level at 2m (dB(A)) 

73 

73 

76 

Voltage (V) 

115V 60Hz 1ph 

Electrical Power (W) 

460 

800 

1100 

Current Rating (A) 

12.5 

17.5 

Weight (lb) 

142 

223 

264 

Lenght (in) 

55.3 

66.1 

76.3 

Width (in) 

24.4 

27.2 

29.6 

Height (in) 

29.5 

35.4 

40.8 

Tank Capacity (gal) 

14 

26 

36 

Fuel Pressure (psi) 

175 

175 

175 

Air Lock Setting 

1.5  

3.5 

9.0 

 

Содержание MIR 37 WU

Страница 1: ...Operating Installation and Service Instructions Direct and Indirect fired Diesel Kerosene Heaters TOR 67 WU TOR 115 WU TOR 175 WU MIR 37 WU MIR 55 WU MIR 85 WU TOR MIR ...

Страница 2: ...________________________________________________________________________________________________ 2 ...

Страница 3: ...ERIALS PAPER OR CARDBOARD A SAFE DISTANCE AWAY FROM THE HEATER AS RECOMMENDED BY THE INSTRUCTIONS NEVER USE THE HEATER IN SPACES WHICH DO OR MAY CONTAIN VOLATILE OR AIRBORNE COMBUSTIBLES OR PRODUCTS SUCH AS GASOLINE SOLVENTS PAINT THINNER DUST PARTICLES OR UNKNOWN CHEMICALS WARNING COMBUSTION BY PRODUCTS PRODUCED WHEN USING THIS PRODUCT CONTAIN CARBON MONOXIDE A CHEMICAL KNOWN TO THE STATE OF CALI...

Страница 4: ...0 180 900 288 700 Air Flow Rate ft min 1180 1470 2650 Fuel Types Diesel Kerosene 1 2 Fuel Oil Fuel Consumption gal hr 0 88 1 28 2 04 Fuel Nozzle 0 65 60 H 1 00 60 H 1 50 80 W Efficiency 87 1 87 1 88 5 Noise Level at 2m dB A 75 73 73 Voltage V 115V 60Hz 1ph Electrical Power W 460 460 800 Current Rating A 7 0 7 0 12 5 Weight lb 154 178 282 Lenght in 47 54 8 68 0 Width in 24 27 6 29 5 Height in 31 32...

Страница 5: ...e unit level When a direct fired heater or an indirect fired heater not connected to a flue pipe is used in a closed room provide a minimum opening area of 3 ft2 per US gallon capacity at the unit level and a continuous natural air circulation through windows and doors For the use of the heater the general and special fire safety regulations in force in all fields of applications must be followed ...

Страница 6: ...himney or to a exhaust duct To get a proper draught at least 0 1 mbar in the chimney the exhaust gas path must rise Avoid any elbows and bends in the first part of the exhaust ducts for at least 3 m For operation of heater in closed rooms without flue refer to the instructions for installation par 4 If a room remote thermostat is used set maximum temperature on it Turn switch to position ON Set th...

Страница 7: ...wer Check main distribution board and power supply line Faulty cable connections Check have cable replaced by a qualified electrician Burnt fuse Room thermostat set too low Check and replace if required Set room thermostat on a higher temperature Room thermostat socket cap not inserted Insert cap into the thermostat socket Heater in lock out mode Reset Dirty or faulty flame sensor Clean or replace...

Страница 8: ... Solenoid Valve TR Ignition Transformer M Motor SL Warning Lamp PA Air Pressure Switch FS Fuse FC Flame Sensor PL Reset Button IN Switch TH Remote Thermostat FR Heated Filter TOR 175 WU TH IN FC EV M black green green black white PL TR white EV TR M L N FR TRcont FC PL TH IN PL black black black white white L N FR SL green white red black white white white black M13 M17 M15 M9 M7 M11 M18 M16 M14 M...