4. INSTALLATION INSTRUCTIONS

 

 

4.1. General instructions 

 

 

THE  INSTALLATION  OF  THE  EQUIPMENT  SHALL  BE  IN  ACCORDANCE  WITH  THE 

REGULATION OF AUTHORITIES HAVING JURISDICTION AND CSA B139.  

 

The heater must be operated  only  by  properly trained personnel. The manufacturer’s instructions must be 

followed. 

 

The heater must be installed and operated so that people are not exposed to dangers deriving from exhaust 

gases, from the hot air flow and in such a way that no fire risks exist. 

 

It is forbidden to install the heater in the surroundings of flammable materials, combustible products, or in 

explosive atmospheres.  

 

When  an 

indirect-fired

  heater  connected  to  a  flue  pipe  is  used  in  a  closed  room,  provide  a  minimum 

opening area of 1 ft³ per US gallon capacity at the unit level. 

 

When a 

direct-fired

 heater - or an 

indirect-fired

 heater 

not 

connected to a flue pipe -  is used in a closed 

room, provide a minimum opening area of  3 ft

2

 per US gallon capacity at the unit level and a continuous, natural 

air circulation through windows and doors.  

 

For the use of the heater the general and special fire safety regulations in force in all fields of applications 

must be followed. In any case the following minimum safety clearances from flammable materials or objects in 
the surroundings of the heater must be ensured:   
 

Sides:        

2 ft   (610 mm) 

Air inlet :    

2 ft  (610 mm) 

Top: 

     

5 ft   (1520 mm)  

Air outlet:    

10 ft (3050 mm) 

Flue pipe:   

3 ft   (915 mm) 

 

 

 

Floors and ceilings must be made of fireproof materials in the place where the heater is operated. 

 

The air inlet and outlet must never be blocked for any reason. 

 

Install the heater on a flat, level floor in a steady position. 

 

It is forbidden to connect direct-fired heaters to air ducts. 

 

4.2 Assembling the heater 
 

 

Before operating the heater, assemble axle, wheels and lower support following the diagram below: 

 
  
 

 

 
 
 

Содержание MIR 37 WU

Страница 1: ...Operating Installation and Service Instructions Direct and Indirect fired Diesel Kerosene Heaters TOR 67 WU TOR 115 WU TOR 175 WU MIR 37 WU MIR 55 WU MIR 85 WU TOR MIR ...

Страница 2: ...________________________________________________________________________________________________ 2 ...

Страница 3: ...ERIALS PAPER OR CARDBOARD A SAFE DISTANCE AWAY FROM THE HEATER AS RECOMMENDED BY THE INSTRUCTIONS NEVER USE THE HEATER IN SPACES WHICH DO OR MAY CONTAIN VOLATILE OR AIRBORNE COMBUSTIBLES OR PRODUCTS SUCH AS GASOLINE SOLVENTS PAINT THINNER DUST PARTICLES OR UNKNOWN CHEMICALS WARNING COMBUSTION BY PRODUCTS PRODUCED WHEN USING THIS PRODUCT CONTAIN CARBON MONOXIDE A CHEMICAL KNOWN TO THE STATE OF CALI...

Страница 4: ...0 180 900 288 700 Air Flow Rate ft min 1180 1470 2650 Fuel Types Diesel Kerosene 1 2 Fuel Oil Fuel Consumption gal hr 0 88 1 28 2 04 Fuel Nozzle 0 65 60 H 1 00 60 H 1 50 80 W Efficiency 87 1 87 1 88 5 Noise Level at 2m dB A 75 73 73 Voltage V 115V 60Hz 1ph Electrical Power W 460 460 800 Current Rating A 7 0 7 0 12 5 Weight lb 154 178 282 Lenght in 47 54 8 68 0 Width in 24 27 6 29 5 Height in 31 32...

Страница 5: ...e unit level When a direct fired heater or an indirect fired heater not connected to a flue pipe is used in a closed room provide a minimum opening area of 3 ft2 per US gallon capacity at the unit level and a continuous natural air circulation through windows and doors For the use of the heater the general and special fire safety regulations in force in all fields of applications must be followed ...

Страница 6: ...himney or to a exhaust duct To get a proper draught at least 0 1 mbar in the chimney the exhaust gas path must rise Avoid any elbows and bends in the first part of the exhaust ducts for at least 3 m For operation of heater in closed rooms without flue refer to the instructions for installation par 4 If a room remote thermostat is used set maximum temperature on it Turn switch to position ON Set th...

Страница 7: ...wer Check main distribution board and power supply line Faulty cable connections Check have cable replaced by a qualified electrician Burnt fuse Room thermostat set too low Check and replace if required Set room thermostat on a higher temperature Room thermostat socket cap not inserted Insert cap into the thermostat socket Heater in lock out mode Reset Dirty or faulty flame sensor Clean or replace...

Страница 8: ... Solenoid Valve TR Ignition Transformer M Motor SL Warning Lamp PA Air Pressure Switch FS Fuse FC Flame Sensor PL Reset Button IN Switch TH Remote Thermostat FR Heated Filter TOR 175 WU TH IN FC EV M black green green black white PL TR white EV TR M L N FR TRcont FC PL TH IN PL black black black white white L N FR SL green white red black white white white black M13 M17 M15 M9 M7 M11 M18 M16 M14 M...

Страница 9: ...________________________________________________________________________________________________ 9 ...

Страница 10: ...________________________________________________________________________________________________ 10 ...

Отзывы: