CN83: COMP-STATE, connect with an ac light to indicate the state of the compressor
Attention: the control port value of the unit actually detected is ON/OFF but not 220-230V control power supply, so
ˈ
special attention should be paid when installing the light.
CN85
:
The alarm signal output of the unit (ON/OFF signal)
Attention: the control port value of the unit actually detected is ON/OFF but not 220-230V control power supply, so
special attention should be paid when installing the alarm signal output.
CN52: Fan realy driver port (only for model 60)
NO.
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
Detail information
CN2: HEAT1. Pipeline Auxiliary Heater
Attention: the control port value of the unit actually detected is ON/OFF but not 220-230V control power supply, so
special attention should be paid when installing the pipeline auxiliary heater.
CN20: TP-PRO, Discharge temperature switch protection (protection code P0, prevent the compressor from
over temperature 115
℃
)
CN70: EXVA, System electronic expansion valve 1.
CN61: Control panel (HMI) conmunication port
CN60: Outdoor units communication port (parallel system)
CN64: Fan inverter module communication ports
CN65: Compressor inverter module communication ports
CN300: Program burn in port (WizPro200RS programming device).
IC10: EEPROM chip
CN1:temperature sensors input port.
T4: outdoor ambient temperature sensor
T3A/T3B: pipe temperature sensor of the condenser
T5: water tank temperature sensor
T6A: Refrigerant inlet temperature of EVI plate heat exchanger
T6B: Refrigerant inlet temperature of EVI plate heat exchanger
CN16: System pressure sensor
CN31 :Temperature sensors input port
Th: System suction temperature sensor
Taf2: Water side antifreeze temperature sensor
Two: Unit water outlet temperature sensor
Twi: Unit water inlet temperature sensor
Tw: Total water outlet temperature sensor when several units are connected in parallel
CN3: IPM module 1 temperature sensor
CN10: IPM module 2 temperature sensor
CN15: Detection of current of the compressor system input port
INV1
:
Detection of current of the compressor A
INV2
:
Detection of current of the compressor B
CN69: Temperature sensors input port
Tp1
:
DC inverter compressor 1 discharge temperature sensor
Tp2: DC inverter compressor 2 discharge temperature sensor
Tz/7: coil final outlet temperature sensor
Taf1: Water side antifreeze temperature
CN19: Low voltage protection switch (Protection code P1)
CN91: Three-phase protector output switch (Protection code E8)
CN58: Fan realy driver port.
SW3: Up button
a) Select different menus when enter menu selection.
b) For sopt inspection in conditions.
SW4: Down button
a) Select different menus when enter menu selection.
b) For sopt inspection in conditions.
SW5: Menu button
Press to enter menu selection, short press to return to the previous menu.
SW6: OK button
Enter the submenu or confirm the function selected by short pressing.
CN8: Remote function of COOL/HEAT signal (terminal block XT2: 14-24, open is COOL and close is HEAT)
CN8: Remote function of ON/OFF signal (terminal block XT2: 15-25, open is OFF and close is ON)
Note: To be effective the DIP switch S5-3 must be ON.