Electrical Control Function
Electrical Control System
113
29
T2B of 1# indoor unit
If the temp. is lower than -9 degree, the digital display tube will
show “9”.If the temp. is higher than 70 degree, the digital
display tube will show “70”. If the capacity demand is 0, , the
digital displ
ay tube will show “0.
If the indoor unit is not
connected, the digital display tube will show: “――”
30
T2B of 2# indoor unit
If the temp. is lower than 0 degree, the digital display tube will
show “0”.If the temp. is higher than 70 degree, the digital
display tube will show “70”. If the capacity demand is 0, , the
digital display tube will show “0. If the indoor unit is not
connected, the digital display tube will show: “――”
Appendix
Shutdown Reason
Code
Frequency limit caused by current
1
Frequency limit caused by T2.in cooling
2
Frequency limit caused by T2.in heating
3
Reach to the setting temperature
4
Frequency limit caused by T4.
5
Defrosting
6
Mode switching
7
High discharge temperature protection
9
High evaporator coil temp.T2 protection
10
Evaporator low temperature T2 protection
11
Condenser high temperature T3 protection
12
Low indoor room temperature protection in drying mode
13
Too low
ambient
temperature protection
14
Refrigerant leakage detection
15
Communication malfunction between indoor and outdoor units
16
Communication error between outdoor main chip and compressor driven chip IR341
17
AC power input voltage protection
18
Top temperature protection of compressor
19
Outdoor EE Malfunction
20
Fan speed has been out of control
21
Open or short circuit of temperature sensor
22
Overcurrent protection
23
IMP overcurrent protection
24
Compressor lack of phase
25
Compressor has been out of control
26
Low pressure protection of 311
27
Fan current protection
28
Fan lack of phase
29
Fan zero speed protection
30
PFC module protection
31
High pressure protection of 311
32
Zero speed malfunction
33
PWM malfunction
34
MCE malfunction
35
Compressor overcurrent protection
36
Compressor EE malfunction
37
Compressor start-up malfunction
38
311 fan speed has been out of control
39
Low pressure protection
40
High pressure protection
41
PFC module malfunction
42
Shutdown stop
49
Electrical disconnect
50
DR stop
51
Содержание MUCR-H6 Series
Страница 15: ...Air Velocity Distributions Reference Data Indoor Units 13 30 42K Cooling Heating ...
Страница 16: ...Air Velocity Distributions Reference Data 14 Indoor Units 48 60K Cooling Heating ...
Страница 21: ...Field Wiring Indoor Units 19 10 Field Wiring ...
Страница 30: ...Static Pressure 28 Indoor Units 5 Static Pressure MUCR 12 H6 MUCR 18 H6 ...
Страница 31: ...Static Pressure Indoor Units 29 MUCR 24 H6 MUCR 30 H6 ...
Страница 32: ...Static Pressure 30 Indoor Units MUCR 36 H6 MUCR 42 H6 MUCR 48 H6 MUCR 48 H6T MUCR 60 H6T ...
Страница 41: ...Service Space Indoor Units 39 3 Service Space ...
Страница 52: ...50 Indoor Units 10 Field Wiring ...
Страница 61: ...Field Wiring Indoor Units 59 10 Field Wiring MUCSR 12 H6 MUCSR 18 H6 ...
Страница 64: ...Dimensions 62 Outdoor Units Model Unit mm W D H W1 A B 48 60 952 415 1333 1045 634 404 ...
Страница 95: ...Refrigerant pipe installation Installation 93 ...