Troubleshooting
132
Electrical Control System
2.4.4.11. J6 malfunction
P2 display
P2 display
Low pressure protection
Low pressure protection
Whether the wiring
between the low pressure
protector and main control
board is connected well or
correctly
Whether the wiring
between the low pressure
protector and main control
board is connected well or
correctly
Method: Disconnect the plug.
Measure the resistance of the
low pressure protector. If the
protector is normal the value is
o
Method: Disconnect the plug.
Measure the resistance of the
low pressure protector. If the
protector is normal the value is
o
Yes
Yes
Connect it well
Connect it well
Replace outdoor main board
Replace outdoor main board
No
Replace low pressure protector
Replace low pressure protector
No
Whether the low
pressure protector
is broken
Whether the low
pressure protector
is broken
Check whether the outdoor
ambient temperature is too
low
Check whether the outdoor
ambient temperature is too
low
No
Stop the unit
Stop the unit
Yes
Open fully valve core of
high pressure valve
Open fully valve core of
high pressure valve
No
Check whether valve core
of high p
ressure
valve is
opened
Check whether valve core
of high p
ressure
valve is
opened
Check if the indoor fan runs
properly in cooling mode
Check if the indoor fan runs
properly in cooling mode
please refer to the solution of fan
speed has been out of control
malfunction. Find out the cause and
have it solved.
please refer to the solution of fan
speed has been out of control
malfunction. Find out the cause and
have it solved.
No
Yes
Yes
No
Check whether the refrigerant
system is ok
Check whether the refrigerant
system is ok
Refrigerant is not enough add the
refrigerant
Refrigerant is not enough add the
refrigerant
No
J6
Содержание MUCR-H6 Series
Страница 15: ...Air Velocity Distributions Reference Data Indoor Units 13 30 42K Cooling Heating ...
Страница 16: ...Air Velocity Distributions Reference Data 14 Indoor Units 48 60K Cooling Heating ...
Страница 21: ...Field Wiring Indoor Units 19 10 Field Wiring ...
Страница 30: ...Static Pressure 28 Indoor Units 5 Static Pressure MUCR 12 H6 MUCR 18 H6 ...
Страница 31: ...Static Pressure Indoor Units 29 MUCR 24 H6 MUCR 30 H6 ...
Страница 32: ...Static Pressure 30 Indoor Units MUCR 36 H6 MUCR 42 H6 MUCR 48 H6 MUCR 48 H6T MUCR 60 H6T ...
Страница 41: ...Service Space Indoor Units 39 3 Service Space ...
Страница 52: ...50 Indoor Units 10 Field Wiring ...
Страница 61: ...Field Wiring Indoor Units 59 10 Field Wiring MUCSR 12 H6 MUCSR 18 H6 ...
Страница 64: ...Dimensions 62 Outdoor Units Model Unit mm W D H W1 A B 48 60 952 415 1333 1045 634 404 ...
Страница 95: ...Refrigerant pipe installation Installation 93 ...