REFRIGERANT PIPE CONNECTION

8

4. Refrigerant pipe connection

Oblique

90

Roughness

Burr

Main cause for refrigerant leakage
is due to defect in the flaring work. 
Carry out correct flaring work
using the following procedure:

A: Cut the pipes and the cable.

1. Use the piping kit accessory or pipes 
    purchased locally.
2. Measure the distance between the indoor 
    and the outdoor unit.
3. Cut the pipes a little longer than the 
    measured distance.
4. Cut the cable 1.5m longer than the pipe  
    length.

1. Flaring work

Pipe

Reamer

Point down

Fig.54

Fig.55

B: Burr removal

1. Completely remove all burrs from the cut 
     cross section of pipe/tube.
2. Put the end of the copper tube/pipe in a 
    downward direction as you remove burrs in 
    order to avoid dropping burrs into the tubing.

Flare nut

Copper tube

Fig.56

C: Putting nut on

     Remove flare nuts attached to indoor and 
     outdoor unit, then put them on pipe/tube 
      having completed burr removal.(not possible
      to put them on after flaring work) 

Additional charge (R410A)

Max. Length for all rooms (m)

OU higher than IU

OU lower than IU

10 

10 

10 

10 

15 

15 

15 

15 

UNIT

Max. Leng th for one indoor unit (m)

Max. height different between
indoor and outdoor unit (m)

Max. height different between indoor units (m)

Before installing, make sure that the height difference, the length of refrigerant pipe and number of bends
between indoor and outdoor units, meet the following specifications.

2 x 1 (H6.2)

3 x 1 (H6.3)

4 x 1 (H6.4)

5 x 1 (H6.5)

30 

45 

60 

75 

25 

30 

35 

35 

15 

15 

15 

15 

10m

15m

15m

Outdoor unit

Indoor unit

Max. height difference

Indoor unit

Indoor unit

 

 

 

 

2 x 1 (H6.2)

3 x 1 (H6.3)

4 x 1 (H6.4)

5 x 1 (H6.5)

 

Charged until

(g) 

UNIT

Total Liquid Length 1/4":

15 x (Total length - 15)

30 x (total length - 7,5)

15m

30m (Total Liquid Length 1/4")

(Total Liquid Length 1/4")

22,5m

7,5m (Total Liquid Length 3/8")

37,5m (Total  Liquid Length 1/4")

Additional

charge

(Total Liquid Length 1/4")

Total Liquid Length 1/4":

Total Liquid Length 1/4":

Total Liquid Length 1/4":

15 x (Total length - 22,5)

15 x (Total length - 30)

15 x (Total length - 37,5)

Total Liquid Length 3/8":

7,5m (Total Liquid Length 3/8")

Содержание H6M Series

Страница 1: ...CL20457 MULTI INVERTER SERIE H6M www mundoclima com English Thank you very muchfor purchasing our products Please read this manual carefully before installing and using the unit manual Installation a...

Страница 2: ...for questions on use or in the event that any irregularities occur This Air Conditioner should be used for hosehold use This unit must be installed by a professional according RD 795 2010 RD 1027 200...

Страница 3: ...gency or manufacturer for details Read This Manual Inside you will find many helpful hints on how to use and maintain your air conditioner properly Just a little preventative care on your part can sav...

Страница 4: ...ational wiring standard regulation and this installation instructions An independent circuit and single outlet must be used If electrical circuit capacity is not enough or defect found in electrical w...

Страница 5: ...o protect the pipe when drilling metal grid metal plate or the like Wall Indoor Outdoor 5 7mm Fit the installation plate Drill a hole in the w all Agujero lado izquierdo 65 mm Agujero lado derecho 65...

Страница 6: ...ful not to let the drain hose slack Heat insulated both of the auxiliary piping Be sure that the drain hose is located at the lowest side of the bundle Locating at the upper side can cause drain pan t...

Страница 7: ...LATION Model Unit mm W D H W1 A B MUEX 14 H6 2 800 333 554 860 514 340 MUEX 18 H6 2 800 333 554 860 514 340 MUEX 21 H6 3 845 363 702 923 540 350 MUEX 27 H6 3 845 363 702 923 540 350 MUEX 28 H6 4 946 4...

Страница 8: ...sible to put them on after flaring work Additional charge R410A Max Length for all rooms m OU higher than IU OU lower than IU 10 10 10 10 15 15 15 15 UNIT Max Length for one indoor unit m Max height d...

Страница 9: ...nit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove any noncondensables and moisture from the system Preparation Check that each tube both liquid and gas sid...

Страница 10: ...supply voltage must be within a range of 90 to 110 of nominal value The thermal circuit breaker and breaker should be 1 5 times the nominal consumption All installation and wiring must comply with loc...

Страница 11: ...L B N B S B L C N C S C L D N D S D L E N E S E TO B TO C TO A TO D TO E MUEX 14 H6 2 MUEX 18 H6 2 W 1 L 2 N S W 1 L 2 N S W 1 L 2 N S W 1 L 2 N S W 1 L 2 N S W 1 L 2 N S W 1 L 2 N S W 1 L 2 N S W 1...

Страница 12: ...e 7 Start up and performance testing Prior check s Measure the voltage supply and make sure it is within the specified range Testing must be performed in all modes of operation To operate in cool mode...

Страница 13: ...To Activate This Function 1 Check that outside temperature is above 5 This function does not work when outside temperature is not above 5 2 Check that the stop valves of the liquid pipe and gas pipe a...

Страница 14: ...t with the sales agency or manufacturer for details Read This Manual Inside you will find many helpful hints on how to use and maintain your air conditioner properly Just a little preventative care on...

Страница 15: ...ndard regulation and this installation instructions An independent circuit and single outlet must be used If electrical circuit capacity is not enough or defect found in electrical work it will cause...

Страница 16: ...nual control button Behind the front panel 11 Refrigerant connecting pipe drain hose and electric wiring 12 Stop valve 13 Air outlet Parts Indoor unit Outdoor unit Display for 3 seconds when TIMER ON...

Страница 17: ...Stop valve 9 Fan hood b Duct MUCR H6M 1 Drain pump drain water from indoor unit 2 Drain hose 3 Air outlet 4 Air inlet 5 Air in grill 6 Display panel 7 Remote controller 8 Refrigerant connecting pipe...

Страница 18: ...rotection features might come into operation and cause the unit to function abnormally 2 If the air conditioner operates in a room whose relative humidity is less than 80 the surface of the air condit...

Страница 19: ...The high speed fan inside may cause danger AUTO operation When you set the air conditioner in AUTO mode it will automatically select cooling heating cooling heating models only or fan only operation d...

Страница 20: ...the handle of the air filter and lift it up slightly to take it out from the filter holder then pull it downwards 3 Remove the Active Carbon Dust Filter from the indoor unit Clean the it once two wee...

Страница 21: ...high resulting in lower heating efficiency of the air conditioner During this condition air conditioner will stop heating operation and start defrosting automatically The time to defrost may vary from...

Страница 22: ...stored Check that plug is securely in wall receptacle Replace the fuse Replace the battery Wait or cancel timer setting Set temperature correctly For method please refer to Remote controller instructi...

Страница 23: ...ort circuit of T5 temperature sensor F3 O 4 Outdoor EEPROM malfunction For some units F4 O 5 Outdoor fan speed is out of control F5 O 6 Open or short circuit of T2B temperature sensor For multi system...

Страница 24: ...ee of charge to the user B When buying a new product the retailer will take back the old product at least free of charge C The manufacture will take back the old appliance for disposal at least free o...

Страница 25: ...25 REMOTE CONTROLLER Please read this Owner s Manual carefully before operation Save this manual in a safe place for future reference...

Страница 26: ...ll prevail All the functions described are accomplished by the unit If the unit has no this feature there is no corresponding operation happened when press the relative button on the remote controller...

Страница 27: ...BO Button Active Disable Turbo function Turbo function enables the unit to reach the preset temper ature at cooling or heating operation in the shortest time if the indoor unit does not support this f...

Страница 28: ...en the setting time displays 10 0 each press will increase the auto timed setting 60 minutes increments To cancel the auto timed program simply adjust the auto on time to 0 0 12 SILENCE FP Button Acti...

Страница 29: ...d Medium speed High speed Auto fan speed Note of clear presentation But during the actual operation only the relative functional signs are shown on the display window All indicators shown in the figur...

Страница 30: ...wer is available The OPERATION indicator on the display panel of the indoor unit starts flashing 1 Press the MODE button to select Auto 2 Press the UP DOWN button to set the desired temperature The te...

Страница 31: ...uto on time of the unit Press the TIMER OFF button can set the auto off time of the unit 1 Press the TIMER ON button The remote controller shows TIMER ON the last Auto on setting time and the signal H...

Страница 32: ...will show on the display area 2 Press the TIMER ON button to display 6 0H on the TIMER ON display of the remote controller 3 Wait for 3 seconds and the digital display area will show the temperature a...

Страница 33: ...MER ON display 5 Wait for 3 seconds and the digital display area will show the temperature again The TIMER ON OFF indicator remains on and this function is activated TIMER OFF TIMER ON On Stop Start o...

Страница 34: ...all programming After inserting new batteries the remote controller must be reprogrammed Replacing batteries Use the remote controller within a distance of 8 meters from the appliance pointing it tow...

Страница 35: ...ry subject matter is indicated in the icon or by images or characters aside Warning Warning arning Please entrust the distributor or professionals to install the unit The installers must have the rele...

Страница 36: ...For Mounting on the Wall Plastic screw bars Screws Wall plugs For fixing on switch box Optional Screws 1 1 Battery The connective wires group 1 1 Precaution of install the wire controller 1 This manua...

Страница 37: ...plate For flush mounting fasten the back plate on the switch box with 2 screws M4 25 and fasten it on the wall with 1 screw M4 20 Fig 3 4 Screw M4 20 Screws M4 25 NOTICE Put on a flat surface Be caref...

Страница 38: ...d the terminals of the indoor unit HA HB HA and HB do not have polarity Fig 3 6 Putty Putty Putty Trap Trap Trap Fig 3 7 All the pictures in this manual are for explanation purpose only Your wire cont...

Страница 39: ...Dry Heat Fan Fan speed Auto Low Med High speed Swing on some models Timer ON OFF Temp setting Weekly timer Follow me Child Lock LCD display Clock Faceplate function on some models Feature LCD display...

Страница 40: ...n 9 C F indication 10 Temperature display 11 Lock indication 12 Room temperature indication 13 Clock display 14 On Off timer 15 Timer display 1 2 3 4 5 7 9 10 11 12 13 15 14 6 8 7 Name of the button o...

Страница 41: ...nished and the time setting is prepared after pressing TIMER button or there is no pressing button in 10 seconds The setting is done after pressing TIMER button or there is no pressing button in 10 se...

Страница 42: ...scale selection on some models Fan speed Lock Press the Lock botton for 3 seconds to activate the child lock function and lock all buttons on the wire controller Press the button again for 3 seconds t...

Страница 43: ...els Not applicable to all the models Press the Swing button to start up down swing function Press it again to stop When the Up Down swing function is activated the mark appears Swing Up Down airflow d...

Страница 44: ...stops after the time has passed On and Off timer Use this timer function to start and stop air conditioner operation The timer operates and air conditioner operation starts and stops after the time h...

Страница 45: ...ess the button or to set the time of Off timer 5 Timer Confirm Confirm Confirm 10 2 Weekly timer Weekly timer setting 1 2 Day of the week setting 3 Timer Confirm Press the button or to select the day...

Страница 46: ...er setting 1 Press the button or to set the time of Off timer and then press the Confirm button to confirm the setting 5 6 ex Tuesday time scale 1 Confirm To activate WEEKLY TIMER operation WEEKLY tim...

Страница 47: ...function During the weekly timer pressing the Del button once display Press this button twice display and wait 3 seconds to confirm It means the unit will override 1 hours Press this button three tim...

Страница 48: ...the button or to select the day to copy to Press the Confirm button to confirm the settings Press the Back button to back to the weekly timer 5 Press the Copy button to confirm Other days can be copi...

Страница 49: ...MC and EMI comply with the CE certification requirements MALFUNCTION PROTECTION DEFINE DISPLAY F0 F1 DIGITAL TUBE NO 1 2 The faceplate is abnormal Error of communication between wire controler and ind...

Страница 50: ...ASK FOR MORE INFORMATION Phone 34 93 446 27 81 eMail info mundoclima com TECHNICAL ASSISTANCE Phone 34 93 652 53 57 www mundoclima com...

Отзывы: