maintenance of motor
˖
Table.15-1
ENC1
POWER_S
0
0 1 2
F
3
E
4
D
5
C
6
B
7
A
89
Mainboard codes indication label
Fig.15-1
Horsepower code
ENC1(system A)
Toggle switch
Code
7
Capacity(Horsepower)
11200W(4.0HP)
12500W(5.0HP)
14000W(5.0HP)
For set horsepower
Note: The horsepower
has been set before
leaving the factory,
anyone can’t
modify it except the
maintenance person.
A
6
5
4
3
2
1
0
8
9
2200W(0.8HP)
2800W(1.0HP)
3600W(1.2HP)
4500W(1.5HP)
5600W(2.0HP)
7100W(2.5HP)
8000W(3.0HP)
9000W(3.2HP)
10000W(4.0HP)
16000W(6.0HP)
Base on different purposes to set the switch codes on the main
boards of indoor unit, Once finish the setting, please cut off the
main power, and then switch on the power again. Otherwise,
setting functions could not work.
NOTE
200T1(8.0HP): Please dial switch ENC1 to B for system A
and 8 for system B.
250T1(9.0HP): Please dial switch ENC1 to C for system A
and 9 for system B.
280T1(10.0HP): Please dial switch ENC1 to D for system A
and 9 for system B.
Indoor unit address set
ENC1 is used for setting the refrigeration capacity(refer to
Table.15-1 for different indoor unit) of the indoor unit.
Capacity set
For 125/140 models
SW 2 Difinition
00 means shutting down the
unit to"stop cold air" at 15
ć
01 means shutting down the
unit to"stop cold air" at 20
ć
10 means shutting down the
unit to"stop cold air" at 24
ć
11 means shutting down the
unit to"stop cold air" at 26
ć
SW2
ON
1 2
SW2
ON
1 2
SW2
ON
1 2
SW2
ON
1 2
Static Pressure set
ENC2
6WDWLFB3UHVVXUH
0 1 2
F
3
E
4
D
5
C
6
B
7
A
89
Fig.15-2
ENC2 is used for setting the Static Pressure(refer to
Table.15-2 for different indoor unit) of the indoor unit.
The static pressure in below table is the optimal static pressure
range which means the airflow, noise, and dehumidification are
all in the best state.
0
1
12.5kW 14kW 20kW 25kW 28kW
0
̚
20Pa
21
̚
80Pa
0
̚
20Pa
21
̚
60Pa
ENC2
2
3
4
81
̚
120Pa
121
̚
170Pa
171
̚
200Pa
61
̚
120Pa
121
̚
170Pa
171
̚
200Pa
Table.15-2
Installation manual
17
Duct 100% fresh air
Note: To make the addressing you can contact with
Mundoclima after sales service.
If the outdoor unit has Auto-address function is not necessary to
set manually the indoor unit address.
If the outdoor unit does not have the Auto-address function or if
you want to set the address manually, it should be done by
remote control (wireless or wired). In models 200, 250 and 280
must be set two addresses, one on each control board. To do this,
first connect the infrared receiver to one PCB, assign the first
address and then connect to the other to do the same.
When connecting a centralized control, if all indoor units are
MVD D4+ or MVD DC series, the central control can be
connected directly to terminals XYE of the outdoor unit, you
must activate the Auto-address dip-switch (except 3 pipes system).
The system together have 64units (0-63), everyone has only
system addresscode,If two addresses are the same in one
system, the abnormal operation will occur.
Please switch off the power before setting,otherwise the
unexpected error will occur.
CAUTION