2

Bend the tubing in proper way. Do not harm to them. 

(Refer to Fig.7-5)

Connect the indoor unit at first, then the outdoor 
unit.

Too large torque will harm the bellmouthing and too small 
will cause leakage. Please determine the torque 
according to Table 7-2.

After the connecting work is finished, be sure to check 
that there is no gas leak.

The bending angle should not exceed 90.

Bending position is preferably in the middle of the 
bendable pipe. The larger the bending radius the better it 
is.

Do not bend the pipe more than three times.

When connecting the flare nut, coat the flare both inside 
and outside with either oil or ester oil and initially tighten 
by hand 3 or 4 turns before tighting firmly. 

(Refer to 

Fig.7-6)

Bend the pipe with thumb

min-radius 100mm

How to expel the air with a vacuum pump

Stop valve operation introduction

1          Opening stop valve

1.

2.

3.

Remove the cap and turn the valve 
counterclock-wise with the hexagon wrench.

Turn it until the shaft stops.Do not apply excessive force 
to the stop valve. Doing so may breakthe valve body, as 
the valve is not a backseat type. Always use the special 
tool.

Make sure to tighten the cap securely.

Fig.7-5

 Fig.7-6

Fig.7-7

Be sure to use both a spanner and torque wrench 
together when connecting or disconnecting pipes to /from 
the unit. 

(Refer to Fig.7-7)

Make sure to tighten the cap securely.
For the tightening torque,refer to the table below.

2         Closing stop valve

1.

2.

Remove the cap and turn the valve clockwise with the 
hexagon wrench.

Securely tighten the valve until the shaft contacts the 
main bodyseal.

CAUTION

CAUTION

Always use a charge hose for service port connection.

After tightening the cap, check that no refrigerant leaks are 
present.

Table 7-2

Tightening torque N  M (Turn clockwise to close)

Stop 

Valve size

Shaft (valve body)

Cap 

(Valve lid)

Φ6.4

Hexagonal 

wrench 4 mm

Φ12.7

Mainte-
nance nut

18

̚

22

13.5

̚

16.5

5.4

̚

6.6

8.1

̚

9.9

11.5

̚

13.9

1

2

4

3

5

7

6

Using the vacuum pump

Loosen and remove the maintenance nuts of stop valves A 
and B, and connect the charge hose of the manifold valve to 
the service port of stop valve A. (Be sure that stop valves A 
and B are both closed)

Connect the joint of the charge hose with the vacuum pump.

Open the Lo-lever of the manifold value completely.

Turn on the vacuum pump. At the beginning of pumping, 
loosen the maintenance nut of stop valve B a little to check 
whether the air comes in (the sound of the pump changes, 
and the indicator of compound meter turns below zero). Then 
fasten the maintenace nut.

When the pumping has finished, close the Lo-lever of the 
manifold valve completely and turn off the vacuum 
pump.Make pumping for 15 minutes or more and check that 
the compound meter indicates -76cmHg(-1X10 Pa)

Loosen and remove the cap of stop valves A and B to open 
stop valve A and B completely, then fasten the cap.

Disassemble the charge hose from the service port of stop 
valve A, and fasten the nut.

5

Fig.7-9

Fig.7-8

service port

cap

maintenance nut

Stop valve

Gas side

Liquid side

hexagon hole

shaft

seal

Outdoor

unit

Indoor

unit

A

C

D

B

9.1 Main board Code designation

Installation manual

Cassette 4 way compact

8

Содержание CL23220

Страница 1: ...MVD Installation manual English CL23220 to CL23223 Console www mundoclima com...

Страница 2: ...The appliance shall not be installed in the laundry Before obtaining access to terminals all supply circuits must be disconnected The appliance must be positioned so that the plug is accessible The en...

Страница 3: ...t 1 meter away from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient enough to eliminate the noise The app...

Страница 4: ...improvement without further notices Cautions on remote controller installation Remote controller holder Mounting screw B ST2 9x10 C H QUANTITY SHAPE NAME 1 Hook 8 Installation manual 3 Remote control...

Страница 5: ...under which the electric wave is generated even if 1 meter is kept When run some of the units among the indoor units in heating mode voice of refrigeration flowing comes from some other non operating...

Страница 6: ...oor unit Refer to Fig 5 5 Fig 5 6 Fig 5 8 Fig 5 4 195mm Hook Tapping screw Washer mm Removing front grille 1 Open the front panel 2 Remove the 4 screws and remove the front grille while pulling it for...

Страница 7: ...ation purpose only They may be slightly different from the air conditioner you purchased depend on model The actual shape shall prevail The outlet has PTI screw bread Please use sealing materials and...

Страница 8: ...o Fig 7 3 Fig 7 3 Remove the front panel 2 Remove the string Refer to Fig 7 2 Allowing the front panel to fall forward will enable you to remove it Fig 7 2 Cover the joints of the connecting pipe with...

Страница 9: ...turn the valve clockwise with the hexagon wrench Securely tighten the valve until the shaft contacts the main bodyseal CAUTION CAUTION Always use a charge hose for service port connection After tighte...

Страница 10: ...o apply for products like washing machines air conditioners or electrical ovens The temperature of refrigerant circuit will be high please keep the interconnection cable away from the copper tube 1 2...

Страница 11: ...erminal block of indoor and outdoor units Re install the Indoor unit and outdoor unit The Specification of Power 8 3 8 4 Wiring of Indoor Unit Power Supply and Signal Wire The indoor unit should use d...

Страница 12: ...0 C For the third code ON super high fan speed OFF extreme super high fan speed 1 2 3 Temperature corrected code 0 means in the heating T1 TS 0 C the units capacity should be 0 Temperature corrected...

Страница 13: ...r fan is 4 minutes 01 means the time of stopping indoor fan is 8 minutes 10 means the time of stopping indoor fan is 12 minutes 11 means the time of stopping indoor fan is 16 minutes 6 21 6 21 6 21 6...

Страница 14: ...and then switch on it If you don t switch on the power the capacity you set can not implement Installation manual Cassette 4 way compact 13 Table 10 1 NO Type Contents LED Lamp flash Remarks The evapo...

Страница 15: ...conditioner is pre heated by turning on the power Set the air conditioner under the mode of COOLING with the remote controller and check the following points If there is any malfunction please resolv...

Страница 16: ...ASK FOR MORE INFORMATION Phone 34 93 446 27 80 eMail info mundoclima com TECHNICAL ASSISTANCE Phone 34 93 652 53 57 MVD www mundoclima com...

Отзывы: