7.    INSTALL THE CONNECTING PIPE

CAUTION

All field piping must be provided by a licensed 
refrigeration technician and must comply with the 
relevant local and national codes.
Do not let air, dust, or other impurities fall in the pipe 
system during the time of installation.
The connecting pipe should not be installed until the 
indoor and outdoor units have been fixed already.
Keep the connecting pipe dry, and do not let moisture in 
during installation.
Execute heat insulation work completely on both sides 
of the gas piping and the liquid piping. Otherwise, this 
can sometimes result in water leakage.

   The Procedure of Connecting Pipes

7.1

Drill a hole in the wall (suitable just for the size of the wall 
conduit), then set on the fittings such as the wall conduit and 
its cover.

Bind the connecting pipe and the cables together tightly with 
binding tapes.
Pass the bound connecting pipe through the wall conduct 
from outside. Be careful of the pipe allocation to do on 
damage to the tubing.
 
Connect the pipes. Refer to "How to Connect the pipes" for 
details.

Expel the air with a vacuum pump. Refer to "How to expel the 
air with a vacuum pump" for details.

Open the stop values of the outdoor unit to make the 
refrigerant pipe connecting the indoor unit with the outdoor 
unit in fluent flow.

Check the leakage. Check all the joints with the leak detector 
or soap water.

6.    CONNECT THE DRAIN PIPE

1.5m~2m

Insulating

material

Downward declivity

lower than 1/100 

Bend

S shape 

VP30

Downward declivity 

lower than 1/100

Put as deep as possible

(about 10cm)

Fig. 6-1

NOTE

All the pictures in this manual are for explanation purpose only. 
They may be slightly different from the air conditioner you 
purchased(depend on model).The actual shape shall prevail.

The outlet has PTI screw bread, Please use sealing 
materials and pipe sheath(fitting) when connecting PVC

 

The drain pipe of indoor unit must be heat insulated, or it 
will condense dew, as well as the connections of the 
indoor unit.

Hard PVC binder must be used for pipe connection, and 
make sure there is no leakage.

With the connection part to the indoor unit, please be 
noted not to impose pressure on the side of indoor unit 
pipes.

When the declivity of the drain pipe downwards is over 
1/100, there should not be any winding.

The total length of  the drain pipe when pulled out 
traversely shall not exceed 20m, when the pipe is over 
long, a prop stand must be installed to prevent winding. 

Refer to the figures on the right for the installation of the 
pipes.

The distance between  the end of the drain pipe and the 
floor or the bottom of the waterspout must be more than 
50mm

ˈ

and do not put it in the water. when the  condense 

dew directly discharge to the slot

ˈ

 the drain pipe must be 

bend to make a U-shanped block to interdict the stench. 

6.1   Install indoor unit drain pipe

Make sure all the connecting point of the drainage system 
is sealed to prevent leakage.

CAUTION

6.2   Drainage test

Check whether the drainpipe is unhindered

New built house should have drain test done before 
paving the ceiling.

Stow water of about 500ml to the water receiver 
through the stow tube.

Turn on the power, set the air conditioner under 
the mode of “COOLING”. Check whether the 
drainpipe is unhindered(According to the length of 
the drainpipe,  it drained after one minute.), and 
whether there’s a leakage exisit in all the connect-
ing point

9.1 Main board Code designation

Installation manual

Cassette 4 way compact

6

Содержание CL23220

Страница 1: ...MVD Installation manual English CL23220 to CL23223 Console www mundoclima com...

Страница 2: ...The appliance shall not be installed in the laundry Before obtaining access to terminals all supply circuits must be disconnected The appliance must be positioned so that the plug is accessible The en...

Страница 3: ...t 1 meter away from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient enough to eliminate the noise The app...

Страница 4: ...improvement without further notices Cautions on remote controller installation Remote controller holder Mounting screw B ST2 9x10 C H QUANTITY SHAPE NAME 1 Hook 8 Installation manual 3 Remote control...

Страница 5: ...under which the electric wave is generated even if 1 meter is kept When run some of the units among the indoor units in heating mode voice of refrigeration flowing comes from some other non operating...

Страница 6: ...oor unit Refer to Fig 5 5 Fig 5 6 Fig 5 8 Fig 5 4 195mm Hook Tapping screw Washer mm Removing front grille 1 Open the front panel 2 Remove the 4 screws and remove the front grille while pulling it for...

Страница 7: ...ation purpose only They may be slightly different from the air conditioner you purchased depend on model The actual shape shall prevail The outlet has PTI screw bread Please use sealing materials and...

Страница 8: ...o Fig 7 3 Fig 7 3 Remove the front panel 2 Remove the string Refer to Fig 7 2 Allowing the front panel to fall forward will enable you to remove it Fig 7 2 Cover the joints of the connecting pipe with...

Страница 9: ...turn the valve clockwise with the hexagon wrench Securely tighten the valve until the shaft contacts the main bodyseal CAUTION CAUTION Always use a charge hose for service port connection After tighte...

Страница 10: ...o apply for products like washing machines air conditioners or electrical ovens The temperature of refrigerant circuit will be high please keep the interconnection cable away from the copper tube 1 2...

Страница 11: ...erminal block of indoor and outdoor units Re install the Indoor unit and outdoor unit The Specification of Power 8 3 8 4 Wiring of Indoor Unit Power Supply and Signal Wire The indoor unit should use d...

Страница 12: ...0 C For the third code ON super high fan speed OFF extreme super high fan speed 1 2 3 Temperature corrected code 0 means in the heating T1 TS 0 C the units capacity should be 0 Temperature corrected...

Страница 13: ...r fan is 4 minutes 01 means the time of stopping indoor fan is 8 minutes 10 means the time of stopping indoor fan is 12 minutes 11 means the time of stopping indoor fan is 16 minutes 6 21 6 21 6 21 6...

Страница 14: ...and then switch on it If you don t switch on the power the capacity you set can not implement Installation manual Cassette 4 way compact 13 Table 10 1 NO Type Contents LED Lamp flash Remarks The evapo...

Страница 15: ...conditioner is pre heated by turning on the power Set the air conditioner under the mode of COOLING with the remote controller and check the following points If there is any malfunction please resolv...

Страница 16: ...ASK FOR MORE INFORMATION Phone 34 93 446 27 80 eMail info mundoclima com TECHNICAL ASSISTANCE Phone 34 93 652 53 57 MVD www mundoclima com...

Отзывы: