Fig.7-10

Pressure meter

Multi-meter

-76 cmHg

Lo-lever

Lo-lever

Charge hose

Charge hose

Vacuum pump

Hi-lever

Manifold valve

8.    WIRING

CAUTION

The appliance shall be installed in accordance with 
natioanl wiring regualtions.

The air conditioner should use separate power supply 
with rated voltage.

The external power supply to the air conditioner should 
have ground wiring, which is linked to the ground wiring 
of the indoor and outdoor unit.

The wiring work should be done by qualified persons 
according to circuit drawing.

An all-pole disconnection device which has at least 3mm 
separation distance in all pole and a residual current 
device(RCD)with the rating of above 10mA shall be 
incorporated in the fixed wiring according to the national 
rule.

Be sure to locate the power wiring and the signal wring 
well to avoid cross-disturbance.

Do not turn on the power until you have checked 
carefully after wiring.

NOTE

Remark per EMC Directive 2004/108/EC
For to prevent flicker impressions during the start of the 
compressor (technical process) ,following installation 
conditions do apply.

The power connection for the air conditioner has to be 
done at the main power distribution. The impedance of 
the distribution has to be low impedance.

No other equipment has to be connected with this power 
line.

For detailed installation acceptance please refer to your 
power supplier, if restrictions do apply for products like 
washing machines, air conditioners or electrical ovens. 

The temperature of refrigerant circuit will be high, please 
keep the interconnection cable away from the copper 
tube.

1

2

3

For power details of the air conditioner refer to the rating 
plate of the product. 

For any question contact your local dealer.

4

5

Electric Wiring

8.1

7.2   Refrigerant pipe installation

6

9.1 Main board Code designation

Ventilate the air if there was any refrigerant leakage during 
installation.Leaked refrigerant will generate poisonous gas if 
meeting fire.

Make sure there is no refrigerant leakage after installation. 
Leaked refrigerant will generate poisonous gas if meeting fire.

Allowed Length and Drop of Piping

Requirements are different when installing the Outdoor 
Unit,please refer to Outdoor Unit Installation Manual for 
detailed information.

Material and Size of the Piping

Size(mm)

Pipe Material

Copper Pipe for Air Conditioner

Model

Φ

12.7

Φ

6.4

22-45

(Gas side)

(Liquid side)

Refrigerant Volume to Be Added

Refrigerant Volume to be added is calculated according to 
Outdoor Unit Installation Manual .

Be save to add refrigerant measuring by a scale.

If refrigerant volume added is inadequate (too much or 
insufficient),the compressor malfunction will be caused.Be 
sure to calculate the refrigerant volume carefully. 

The service man should note down the piping length and 
refrigerant volume added on the nameplate, which is on the 
Electric Control Box Cover of outdoor unit for to diagnose the 
compressor when compressor malfunction occurs.

Table 7-3

CAUTION

CAUTION

Installation manual

Cassette 4 way compact

9

Содержание CL23220

Страница 1: ...MVD Installation manual English CL23220 to CL23223 Console www mundoclima com...

Страница 2: ...The appliance shall not be installed in the laundry Before obtaining access to terminals all supply circuits must be disconnected The appliance must be positioned so that the plug is accessible The en...

Страница 3: ...t 1 meter away from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient enough to eliminate the noise The app...

Страница 4: ...improvement without further notices Cautions on remote controller installation Remote controller holder Mounting screw B ST2 9x10 C H QUANTITY SHAPE NAME 1 Hook 8 Installation manual 3 Remote control...

Страница 5: ...under which the electric wave is generated even if 1 meter is kept When run some of the units among the indoor units in heating mode voice of refrigeration flowing comes from some other non operating...

Страница 6: ...oor unit Refer to Fig 5 5 Fig 5 6 Fig 5 8 Fig 5 4 195mm Hook Tapping screw Washer mm Removing front grille 1 Open the front panel 2 Remove the 4 screws and remove the front grille while pulling it for...

Страница 7: ...ation purpose only They may be slightly different from the air conditioner you purchased depend on model The actual shape shall prevail The outlet has PTI screw bread Please use sealing materials and...

Страница 8: ...o Fig 7 3 Fig 7 3 Remove the front panel 2 Remove the string Refer to Fig 7 2 Allowing the front panel to fall forward will enable you to remove it Fig 7 2 Cover the joints of the connecting pipe with...

Страница 9: ...turn the valve clockwise with the hexagon wrench Securely tighten the valve until the shaft contacts the main bodyseal CAUTION CAUTION Always use a charge hose for service port connection After tighte...

Страница 10: ...o apply for products like washing machines air conditioners or electrical ovens The temperature of refrigerant circuit will be high please keep the interconnection cable away from the copper tube 1 2...

Страница 11: ...erminal block of indoor and outdoor units Re install the Indoor unit and outdoor unit The Specification of Power 8 3 8 4 Wiring of Indoor Unit Power Supply and Signal Wire The indoor unit should use d...

Страница 12: ...0 C For the third code ON super high fan speed OFF extreme super high fan speed 1 2 3 Temperature corrected code 0 means in the heating T1 TS 0 C the units capacity should be 0 Temperature corrected...

Страница 13: ...r fan is 4 minutes 01 means the time of stopping indoor fan is 8 minutes 10 means the time of stopping indoor fan is 12 minutes 11 means the time of stopping indoor fan is 16 minutes 6 21 6 21 6 21 6...

Страница 14: ...and then switch on it If you don t switch on the power the capacity you set can not implement Installation manual Cassette 4 way compact 13 Table 10 1 NO Type Contents LED Lamp flash Remarks The evapo...

Страница 15: ...conditioner is pre heated by turning on the power Set the air conditioner under the mode of COOLING with the remote controller and check the following points If there is any malfunction please resolv...

Страница 16: ...ASK FOR MORE INFORMATION Phone 34 93 446 27 80 eMail info mundoclima com TECHNICAL ASSISTANCE Phone 34 93 652 53 57 MVD www mundoclima com...

Отзывы: