201703
49
P
art 4 - Diagnosis and T
roubleshoo
ting
Procedure
4.2.4
E0 / E8
Water flow switch connection on
hydronic box main PCB is loose
1
Yes
Ensure the switch is connected properly
No
Water flow is insufficient
2
Yes
Check the water piping and valves. Make
sure the water piping is clean, there is no
air in the water piping and all valves are
open. If the internal circulator pump is
not already set to the highest speed,
increase its speed.
No
Water flow switch is damaged
Yes
Replace the water flow switch
No
Internal circulator pump fuse, backup
electric heater fuse or hydronic box main
PCB fuse has blown
3
Yes
Replace the blown fuse
No
Replace hydronic box main PCB
Notes:
1.
Water flow switch connection is port CN8 on the main PCB for hydronic box (labeled 5 in Figure 4-2.8 in Part 4, 2.2 “Hydronic Box PCB”).
2.
Check water pressure on the manometer. If the water pressure is not > 1 bar, water flow is insufficient. Refer to Figure 2-1.6 and 2-1.7 in Part 2, 1
“Hydronic Box Layout”.
3.
The fuse is labeled 30 in Figure 4-2.8 in Part 4, 2.2 “Hydronic Box PCB”.