78
201703
4.19 P6 Troubleshooting for single-phase models
Digital display output
4.19.1
Description
4.19.2
Inverter module protection.
M-Thermal Split stops running.
Error code P6 is displayed on the user interface. Specific error code L0, L1, L2, L4, L5, L7, L8 or L9 is displayed on the
outdoor unit main PCB.
Possible causes
4.19.3
Inverter module protection.
DC bus low or high voltage protection.
MCE error.
Zero speed protection.
Phase sequence error.
Excessive compressor frequency variation.
Actual compressor frequency differs from target frequency.
Specific error codes for P6 inverter module protection
4.19.4
If a P6 error code is displayed on the user interface, one of the following specific error codes is displayed on the outdoor
unit main PCB: L0, L1, L2, L4, L5, L7, L8, L9. Refer to Table 4-4.1.
Table 4-4.1: Specific error codes for error P6
Specific error code
Content
L0
Inverter module protection
L1
DC bus low voltage protection
L2
DC bus high voltage protection
L4
MCE error
L5
Zero speed protection
L7
Phase sequence error
L8
Compressor frequency variation greater than 15Hz within one second protection
L9
Actual compressor frequency differs from target frequency by more than 15Hz protection
The specific error codes can also be obtained from the LED indicators LED1/LED2 on the inverter module. Refer to Figure
4-4.2 and Figure 4-2.4 or 4-2.6 in Part 4, 2.1 “Outdoor Unit PCBs”.
MUNDOCLIMA AEROTHERM V17 - BIBLOC
Содержание Aerotherm V17 Series
Страница 3: ...2 201703 MUNDOCLIMA AEROTHERM V17 BIBLOC...
Страница 28: ...26 201703 MUNDOCLIMA AEROTHERM V17 BIBLOC...