Munchkin HIGH EFFICIENCY HEATER with the

13

WARNING  

Failure to follow all precautions could result in fire, explosion or death!

GAS CONNECTION

It is recommended that a soapy solution be used to detect leaks. Bubbles will appear on the pipe to
indicate a leak is present. The gas piping must be sized for the proper flow and length of pipe, to avoid
pressure drop. Both the gas meter and the gas regulator must be properly sized for the total gas load.
If you experience a pressure drop greater than 1" WC, the meter, regulator or gas line is undersized or
in need of service. You can attach a manometer to the incoming gas drip leg, by removing the cap and
installing the manometer. The gas pressure must remain between 3.5" and 14" during stand-by (static)
mode and while in operating (dynamic) mode. 

If an in-line regulator is used, it must be a minimum

of 10 feet from the Munchkin. It is very important that the gas line is properly purged by the gas
supplier or utility. Failure to properly purge the lines or improper line sizing, will result in ignition
failure.

This problem is especially noticeable in NEW LP installations and also in empty tank situations.

This can also occur when a utility company shuts off service to an area to provide maintenance to their
lines. This gas valve must not be replaced with a conventional gas valve under any circumstances. As
an additional safety feature, this gas valve has a flanged connection to the Venturi and blower.

DUNGS GAS VALVE 

THROTTLE ADJUSTER
(NOTE: IF FOR ANY 
REASON THE THROTTLE 
NEEDS TO BE 
ADJUSTED

,

 IT IS 

VERY IMPORTANT THAT 
A "COMBUSTION 
ANAYLYZER" BE USED 
TO ENSURE SAFE AND 
PROPER OPERATION.  
TURN THE ADJUSTER 
TO THE (+) TO 
INCREASE GAS OR THE 
(-) TO DECREASE THE 
GAS SUPPLY. THIS 
ADJUSTMENT COULD 
AFFECT CO/CO% 
LEVELS. MAKE SURE 
THE LEVELS 
CORRESPOND TO THE 
CHART IN COMBUSTION 
SETTINGS.) 

Fig. 3-1

Содержание HIGH EFFICIENCY HEATER with the "925" Controller

Страница 1: ...eighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency...

Страница 2: ...HEATER AND PRESSURE VESSEL CODE Section IV ALONG WITH CSD1 THE HEATER GAS PIPING WATER PIPING VENTING AND ELECTRICAL MUST BE INSTALLED BY TRAINED QUALIFIED PERSONNEL FAMILIAR WITH INSTALLATION PRACTI...

Страница 3: ...ng with Circulators or Zone Valves 22 B Circulator Sizing 23 C Fill and Purge Heating System 24 D Piping Illustrations 25 PART 6 34 thru 37 START UP PROCEDURES A Sequence of operation 34 B Items to be...

Страница 4: ...seconds to pre purge the system before starting the Munchkin The Munchkin controller will now start to modulate the pre mix burner based on analyzing the return temperature supply water temperature an...

Страница 5: ...GENERAL INFORMATION 5 Figure 1 1 NOTE The Munchkin is rated at zero clearance to combustibles 80M 140M 199M T50M T80M RECOMMENDED SERVICE CLEARANCES Figure 1 2...

Страница 6: ...GENERAL INFORMATION 6 Figure 1 3 T50M T80M DIMENSIONS...

Страница 7: ...GENERAL INFORMATION 7 DIMENSIONS 80M 140M 199M Figure 1 4 Figure 1 5...

Страница 8: ...certified for use on combustible floors 2 Refer to Figure 1 1 and Figure 1 2 for the recommended clearance to allow for rea sonable access to the boiler Local codes or special conditions may require...

Страница 9: ...r your convenience we have labeled all the wires that need to be connected to operate the Munchkin CAUTION The Munchkin is certified as an indoor appliance Do not install the Munchkin outdoors or loca...

Страница 10: ...n should now be reading the outlet temperature Note see Part 6 Startup Procedure section in the manual to change the temperature setting or run the heater CAUTION Electrical wiring on the Incoming Pow...

Страница 11: ...R FIRE AND COULD DAMAGE THE CONTROL O R A N G E B R O W N G R E E N Figure 2 1 Connection Wiring Directly to Central Heating Circulator Figure 2 2 Connection Wiring without Wiring Central Heating Circ...

Страница 12: ...rom the gas line In order to do this you must shut the gas off using factory and field installed gas cocks following the lighting instructions in Part 6 Section B This will prevent high pressure Failu...

Страница 13: ...inimum of 10 feet from the Munchkin It is very important that the gas line is properly purged by the gas supplier or utility Failure to properly purge the lines or improper line sizing will result in...

Страница 14: ...ombustibles Note For Concrete construction or to meet certain fire codes exhaust and inlet piping at the wall penetration to the Munchkin must be CPVC Schedule 40 or 80 to meet local fire codes The ba...

Страница 15: ...Never vent over or under a window or over a doorway where the exhaust plume or conden sation liquid will cause obtrusive or dangerous conditions Or refer to National Fuel Gas Code CAN B149 3 Never ins...

Страница 16: ...CREENS FROM THE PROVIDED INLET TEE AND INSTALL THEM IN THE INLET SOCKET AND OUTLET SOCKET Y TEE CONNECTION OF THE KIT PRIOR TO INSTALLING THE SCHEDULE 40 PIPE AND GLUING VENTING 12 in minimum Forced a...

Страница 17: ...ed combined length of pipe on the inlet and exhaust must not exceed 125 equivalent feet total Example Installation requires the following material for both the inlet and exhaust piping when extending...

Страница 18: ...7 Any improper operation of the common venting system should be corrected so the installa tion conforms with the National Fuel Gas Code ANSI Z223 1 When resizing any portion of the common venting sys...

Страница 19: ...hed a minimum of a per foot back to the heater to allow drainage of condensate Figure 4 1 IMPORTANT NOTE All vent pipes must be glued prop erly supported and the exhaust must be pitched a mini mum of...

Страница 20: ...ust must be pitched a minimum of a per foot back to the heater to allow drainage of condensate Figure 4 3 IMPORTANT NOTE All vent pipes must be glued properly supported and the exhaust must be pitched...

Страница 21: ...ched a minimum of a per foot back to the heater to allow drainage of condensate Figure 4 5 IMPORTANT NOTE All vent pipes must be glued properly supported and the exhaust must be pitched a minimum of a...

Страница 22: ...use glycol that is specially formulated for this purpose It includes inhibitors which prevent the glycol from attacking the metallic system components Make certain that the system fluid is checked for...

Страница 23: ...g illustrations included in this section Figs 5 3 to 5 11 for suggested guidelines in piping the Munchkin heater with either zone valves or circulator pumps Please note that these illustrations are me...

Страница 24: ...ested at least once a year and as recommended by the glycol manufacturer 3 Anti freeze solutions expand more than water For example a 50 by volume solution expands 4 8 in volume for a temperature incr...

Страница 25: ...valve air separator backflow preventer diaphragm type expansion tank pressure reducing valve diff pressure bypass anti scald rated mixing valve pressure gauge 4 way motorized mixing valve 3 way motori...

Страница 26: ...140M 5 gpm Munchkin model 199M 7 gpm 3 The minimum pipe size for connecting a Super Stor water heater is 1 inch 4 The minimum pipe size for connecting a Munchkin boiler is 1 25 inches 5 All pumps are...

Страница 27: ...gpm Munchkin model 80M 3 gpm Munchkin model 140M 5 gpm Munchkin model 199M 7 gpm 3 The minimum pipe size for connecting a Super Stor water heater is 1 inch 4 The minimum pipe size for connecting a Mun...

Страница 28: ...for connecting a Munchkin boiler is 1 25 inches 5 All pumps are shown with isolation flanges The alternative is standard flanges with full port ball valves 6 The anti scald mixing valve is recommended...

Страница 29: ...3 The minimum pipe size for connecting a Super Stor water heater is 1 inch 4 The minimum pipe size for connecting a Munchkin boiler is 1 25 inches 5 All pumps are shown with isolation flanges The alte...

Страница 30: ...pe size for connecting a Munchkin boiler shall be 1 25 inches 6 All pumps are shown with isolation flanges The alternative is standard flanges with full port ball valves 7 The anti scald mixing valve...

Страница 31: ...stalled upstream and downstream of all closely spaced tees 4 The minimum pipe size for connecting a Super Stor water heater is 1 inch 5 The minimum pipe size for connecting a Munchkin boiler shall be...

Страница 32: ...ize for connecting a Munchkin boiler shall be 1 25 inches 6 All pumps are shown with isolation flanges The alternative is standard flanges with full port ball valves 7 The anti scald mixing valve is r...

Страница 33: ...pe size for connecting a Munchkin boiler shall be 1 25 inches 6 All pumps are shown with isolation flanges The alternative is standard flanges with full port ball valves 7 The anti scald mixing valve...

Страница 34: ...l enters an idle state while continuing to moni tor temperature and the state of other system devices If a call for heat is received the con trol will automatically return to step 2 in sequence and re...

Страница 35: ...ian Force or attempted repair may result in a fire or explosion 4 Do not use this appliance if any part has been under water Immediately call a qualified serv ice technician to inspect the appliance a...

Страница 36: ...he burn er will not start until the outlet temperature of the system falls below 159 F degrees 180 20 F 160 F To adjust press either S1 Decrease Value or S2 Increase Value Ranges 5 F to 30 F Press the...

Страница 37: ...mode stops automatically To exit Test Mode press S1 and S2 key together for 1 second H TO TURN OFF GAS TO APPLIANCE 1 Set the thermostat to lowest setting 2 Turn off all electric power to the applian...

Страница 38: ...e controller will illuminate the red fault indication light and display a fault code in the format Example F00 on the display module 2 Note the fault code and refer to Table 7 2 for an explanation of...

Страница 39: ...c o l b e u l f y n a k c e h C 0 1 F r e l i o b e h T l a n g i S e m a l F f o s s o L e h t e r o f e b s e m i t 4 t h g i l e r l l i w t u o k c o l s i h t o t n i s e o g l o r t n o c n o i...

Страница 40: ...t Temperature F Resistance ohms 32 32550 41 25340 50 19870 59 15700 68 12490 77 10000 86 8059 95 6535 104 5330 113 4372 122 3605 131 2989 140 2490 149 2084 158 1753 167 1481 176 1256 185 1070 194 915...

Страница 41: ...check burner for deterioration If deterioration is observed replace burner System Water Pressure check pressure regulator and system pressure Check system for air which will create noise Open air vent...

Страница 42: ...y buildup then vacuum the debris from the coils 4 Spray the coils with clear water making sure to confine the spray to the area being cleaned Try to avoid getting the back ceramic wall of the unit wet...

Страница 43: ...YOUT Fig 8 1 There is a spare 6 3 amp slow blow fuse included on the control cover HTP p n 7250 378 or you may purchase it from Radio Shack p n 270 1068 Caution Do not replace with any amperage other...

Страница 44: ...MAINTENANCE 44...

Страница 45: ...MAINTENANCE 45...

Страница 46: ...NOTES 46...

Страница 47: ...NOTES 47...

Страница 48: ...SuperStor Ultra SuperStor Voyager Voyager Sanitizer and Everlast are registered trademarks of Heat Transfer Products Inc Munchkin R1 2004 Heat Transfer Products Inc LP 61 REV 1 17 05...

Отзывы: