Multi-Amp CB-832 Скачать руководство пользователя страница 18

 

 

Part 

 12470 

 

Rev. 2  3/25/99 

15 

MAINTENANCE OF MOLDED CASE CIRCUIT BREAKERS

 

 

The molded case circuit breaker essentially consists of two separate elements.  One element is a set 

of contacts and suitable mechanical linkage for manual operation of the breaker as a switch in an 

electrical circuit.  The other element is a device that senses and reacts to an overload or short circuit. 

 Normally, the time delay overload device is thermal and the instantaneous overload device, when 

supplied, is magnetic.  The thermal element usually uses a bimetallic strip; two pieces of dissimilar 

material bonded together.  An overload causes an increase in heat which will result in moving the 

bimetallic  unit  and  eventually  trip  the  circuit  breaker.    The  magnetic  element  operates  with  no 

intentional time delay to provide instantaneous protection against high magnitude faults. 

 

PLANNED MAINTENANCE PROGRAM

 

 

A scheduled program for maintenance of molded case circuit breakers consists primarily of "good 

housekeeping" in conjunction with visual inspections and electrical tests.  A brief outline is given 

below: 

 

1. 

Clean   

 

All  types  of  molded  case  circuit  breakers  should  be  externally  cleaned  so  that  the  heat 

produced  in  normal  operation  can  be  dissipated  properly.    It  is  possible  for  dirt  or  dust 

caused by normal plant conditions to accumulate and prevent proper dissipation of heat, 

resulting in a nuisance operation of the breaker. 

 

2. 

Tighten Connections 

 

This  is  particularly  important  because  loose  electrical  connections  can  cause  extra  heat 

which may result in an unnecessary operation of the breaker. 

 

3. 

Test 

 

The molded case circuit breaker should be subjected to a simulated overload and the tripping 

time measured.  This is important because after a period of inactivity, the overload device 

may become stiff or inoperable.  The only way to determine this condition and eliminate the 

stiffness is to electrically operate the breaker on a periodic basis.  Manually opening and 

closing  the  main  contacts  of  the  breaker  does  not  move  any  of  the  mechanical  linkage 

associated with the overload device.  Testing may be as often as every 6 months or as long as 

every three or four years, depending upon conditions where the breaker is installed. 

 

 

THERMAL ELEMENT

 

Содержание CB-832

Страница 1: ...ON MANUAL For HIGH CURRENT TEST SET MODEL CB 832 It is essential that this instruction book be read thoroughly before putting the equipment in service Advanced Test Equipment Rentals www atecorp com 8...

Страница 2: ...ly reserves to itself all rights to such proprietary information as well as all rights under any such patent none of which is waived by the submission of this instruction manual to anyone The recipien...

Страница 3: ...6 D Overload Capacity 7 III TEST PROCEDURES 8 A Maintenance of Motor Overload Relays 8 1 Planned Maintenance Program 10 2 Time Delay 11 3 Instantaneous Element 13 B Maintenance of Molded Case Circuit...

Страница 4: ...complete working understanding of the CB 832 test set It is divided into five main sections SECTION I Gives a description of the test set Gives basic guidelines on the different applications performe...

Страница 5: ...essential that the technician properly and effectively ground earth the test set This is accomplished by connecting the input line cord to a properly grounded receptacle CAUTION The input voltage of t...

Страница 6: ...er output circuit of CB 832 against overloads CONTROL FUSE Protects instrumentation and control circuitry against overloads OUTPUT CONTROL Variable autotransformer provides continuous non stepped outp...

Страница 7: ...power remains energized but output current remains de energized and timer will not count AMMETER LED displays show the numeral one in the left most position when the meter is over ranged RANGE SWITCH...

Страница 8: ...not connect CONTACTS binding posts to an energized circuit STOP MODE Switch Selects either current actuated position to stop the current output and timer or either of the two external contact stop mod...

Страница 9: ...ome experimentation and will be easier as familiarity increases NOTE There is no relationship between the ammeter ranges and the ratings of the output terminal All ammeter ranges can be used in conjun...

Страница 10: ...00 amperes may be drawn at any voltage from 0 3 5 volts for 15 minutes provided the test set is subsequently de energized for 30 minutes b 353 5 amperes 70 7 of 500 amperes may be continuously drawn a...

Страница 11: ...ference to tables or charts supplied by the manufacturer of the overload relays and motors Whenever a motor trips out it is poor practice to uprate the overload relay indiscriminately the motor may ac...

Страница 12: ...nergy in the spring This interrupts the circuit of the holding coil in the motor starter and shuts down the motor The starter may be reset only after the temperature of the heater has cooled sufficien...

Страница 13: ...ossible for dirt or dust created by conditions in the plant to prevent parts of the relay from moving These same conditions can also prevent the proper dissipation of normal heating resulting in unnec...

Страница 14: ...load relay Connect other end of this lead to the appropriate output terminal see SELECTION OF OUTPUT TERMINAL 4 Connect test set to suitable single phase power supply 5 Turn test set on with POWER ON...

Страница 15: ...may decrease fall off during the test because the resistance or impedance of the test circuit increases as it heats up Rotate OUTPUT CONTROL knob clockwise to keep test current at desired value 15 Wh...

Страница 16: ...Open Contacts of overload relay to binding posts of test set labeled CONTACTS 9 Select appropriate timer STOP MODE 10 Select desired timer display mode and range 11 Rotate OUTPUT CONTROL knob clockwis...

Страница 17: ...e is sometimes referred to as the jogging or step method For nearly all applications this method works best however there is another method referred to as the run up method Instead of the OUTPUT MODE...

Страница 18: ...ual inspections and electrical tests A brief outline is given below 1 Clean All types of molded case circuit breakers should be externally cleaned so that the heat produced in normal operation can be...

Страница 19: ...ument displays should light 6 Use RANGE Switch to select ammeter range so test current will be near full scale and no less than 10 of full scale 7 Put ammeter DISPLAY MODE Switch in MEMORY position 8...

Страница 20: ...r impedance of the test circuit increases as it heats up Rotate OUTPUT CONTROL knob clockwise to keep test current at desired value 14 When circuit breaker trips timer stops and output is de energized...

Страница 21: ...sition 9 Select desired timer display mode and range 10 Rotate OUTPUT CONTROL knob clockwise and momentarily press OUTPUT MODE Switch in MOMENTARY release Observe current reading retained by ammeter I...

Страница 22: ...ings and brush es can cause premature wear down of the brush es and carbon buildup see SERVICE DATA GROUND FAULT ELEMENT 1 Set up CB 832 with a POWER ON OFF Switch in OFF position instrument displays...

Страница 23: ...OUTPUT CONTROL knob at maximum clockwise rotation return knob to zero and transfer output lead to the next higher voltage lesser current terminal Proceed with current adjustment as in Steps 10 and 11...

Страница 24: ...cloth can be dampened with an approved solvent that does not attack the finish or leave residue 2 Control Panel The control panel can be wiped clean with a soft dry cloth Do not wipe the meter lenses...

Страница 25: ...SRO number will be assigned for proper handling of the unit when it arrives at the factory If desired a letter with the SRO number and instructions can be provided Provide the factory with model numbe...

Страница 26: ...mps and shocks of shipping via common commercial carrier For example you may wish to reship your unit to Multi Amp for annual calibration certification OPERATIONAL ERRORS TROUBLESHOOTING Some operatio...

Страница 27: ...ts connector has come loose from the PCB d Triac failure 5 Same as above will not initiate in N O or N C Contacts mode a Faulty test leads b Incorrect test scheme for stop mode selected c Contacts bei...

Страница 28: ...quipment which has damage or cause of defect due to accident negligence improper operation faulty installation by the purchaser or improper service or repair by any person company or corporation not a...

Страница 29: ...Part 12470 Rev 2 3 25 99 26 SECTION V SCHEMATICS...

Отзывы: