Multi-Amp CB-832 Скачать руководство пользователя страница 14

 

 

Part 

 12470 

 

Rev. 2  3/25/99 

11 

5. 

Test 

The motor overload relay should be subjected to a simulated overload and the tripping time 

measured.  This should be compared to the manufacturer's specifications or the relay's time 

curves to make certain that the relay is operating properly.  A tolerance of + 15% is usually 

acceptable.  If the relay's curves or specifications are not available, it is suggested that the 

Heat Damage Curve of the motor be used as a guide for maximum trip time at 300% of 

motor full load current. TIME DELAY OF MOTOR OVERLOAD RELAYS 

 

TIME DELAY

 

1. 

Set-up CB-832 with: 

a. 

POWER ON/OFF Switch in OFF position (instrument displays off). 

b. 

OUTPUT CONTROL knob at minimum 

`0'

 position. 

c. 

OUTPUT MODE Switch in center OFF position. 

2. 

Connect one end of a high-current lead to one side of thermal element or current coil 

in overload relay.  Connect other end of this lead to the COMMON terminal of test 

set. 

3. 

Connect one end of second high-current lead to other side of thermal element or 

current  coil  in  overload relay.   Connect  other  end  of this  lead  to  the appropriate 

output terminal (see SELECTION OF OUTPUT TERMINAL). 

4. 

Connect test set to suitable single-phase power supply. 

5. 

Turn test set on with POWER ON/OFF Switch (instrument displays should light). 

6. 

Use RANGE Switch to select ammeter range so test current will be near full scale 

and no less than 10% of full scale. 

7. 

Put ammeter DISPLAY MODE Switch in MEMORY position. 

8. 

Connect  a  pair  of  light  leads  (timer  leads)  from  Normally  Closed  Contacts  or 

Normally  Open  Contacts  of  overload  relay  to  binding  posts  of  test  set  labeled 

CONTACTS. 

9. 

Select appropriate timer STOP MODE. 

10. 

Select desired timer display mode and range. 

11. 

Rotate  OUTPUT  CONTROL  knob  clockwise  and  momentarily  press  OUTPUT 

MODE Switch in MOMENTARY and release.  Observe current reading retained by 

ammeter. 

 

 

 

12. 

Continue to rotate OUTPUT CONTROL knob clockwise while jogging (repeatedly 

moving to MOMENTARY position and releasing) OUTPUT MODE Switch until 

desired test current is reached.  Suggested test current is three times (3x) the rating of 

thermal relays or three times (3x) the pick-up current of magnetic relays. 

 

If  the  relay  utilizes  a  high  impedance  thermal  element  or  operating  coil  and  the 

Содержание CB-832

Страница 1: ...ON MANUAL For HIGH CURRENT TEST SET MODEL CB 832 It is essential that this instruction book be read thoroughly before putting the equipment in service Advanced Test Equipment Rentals www atecorp com 8...

Страница 2: ...ly reserves to itself all rights to such proprietary information as well as all rights under any such patent none of which is waived by the submission of this instruction manual to anyone The recipien...

Страница 3: ...6 D Overload Capacity 7 III TEST PROCEDURES 8 A Maintenance of Motor Overload Relays 8 1 Planned Maintenance Program 10 2 Time Delay 11 3 Instantaneous Element 13 B Maintenance of Molded Case Circuit...

Страница 4: ...complete working understanding of the CB 832 test set It is divided into five main sections SECTION I Gives a description of the test set Gives basic guidelines on the different applications performe...

Страница 5: ...essential that the technician properly and effectively ground earth the test set This is accomplished by connecting the input line cord to a properly grounded receptacle CAUTION The input voltage of t...

Страница 6: ...er output circuit of CB 832 against overloads CONTROL FUSE Protects instrumentation and control circuitry against overloads OUTPUT CONTROL Variable autotransformer provides continuous non stepped outp...

Страница 7: ...power remains energized but output current remains de energized and timer will not count AMMETER LED displays show the numeral one in the left most position when the meter is over ranged RANGE SWITCH...

Страница 8: ...not connect CONTACTS binding posts to an energized circuit STOP MODE Switch Selects either current actuated position to stop the current output and timer or either of the two external contact stop mod...

Страница 9: ...ome experimentation and will be easier as familiarity increases NOTE There is no relationship between the ammeter ranges and the ratings of the output terminal All ammeter ranges can be used in conjun...

Страница 10: ...00 amperes may be drawn at any voltage from 0 3 5 volts for 15 minutes provided the test set is subsequently de energized for 30 minutes b 353 5 amperes 70 7 of 500 amperes may be continuously drawn a...

Страница 11: ...ference to tables or charts supplied by the manufacturer of the overload relays and motors Whenever a motor trips out it is poor practice to uprate the overload relay indiscriminately the motor may ac...

Страница 12: ...nergy in the spring This interrupts the circuit of the holding coil in the motor starter and shuts down the motor The starter may be reset only after the temperature of the heater has cooled sufficien...

Страница 13: ...ossible for dirt or dust created by conditions in the plant to prevent parts of the relay from moving These same conditions can also prevent the proper dissipation of normal heating resulting in unnec...

Страница 14: ...load relay Connect other end of this lead to the appropriate output terminal see SELECTION OF OUTPUT TERMINAL 4 Connect test set to suitable single phase power supply 5 Turn test set on with POWER ON...

Страница 15: ...may decrease fall off during the test because the resistance or impedance of the test circuit increases as it heats up Rotate OUTPUT CONTROL knob clockwise to keep test current at desired value 15 Wh...

Страница 16: ...Open Contacts of overload relay to binding posts of test set labeled CONTACTS 9 Select appropriate timer STOP MODE 10 Select desired timer display mode and range 11 Rotate OUTPUT CONTROL knob clockwis...

Страница 17: ...e is sometimes referred to as the jogging or step method For nearly all applications this method works best however there is another method referred to as the run up method Instead of the OUTPUT MODE...

Страница 18: ...ual inspections and electrical tests A brief outline is given below 1 Clean All types of molded case circuit breakers should be externally cleaned so that the heat produced in normal operation can be...

Страница 19: ...ument displays should light 6 Use RANGE Switch to select ammeter range so test current will be near full scale and no less than 10 of full scale 7 Put ammeter DISPLAY MODE Switch in MEMORY position 8...

Страница 20: ...r impedance of the test circuit increases as it heats up Rotate OUTPUT CONTROL knob clockwise to keep test current at desired value 14 When circuit breaker trips timer stops and output is de energized...

Страница 21: ...sition 9 Select desired timer display mode and range 10 Rotate OUTPUT CONTROL knob clockwise and momentarily press OUTPUT MODE Switch in MOMENTARY release Observe current reading retained by ammeter I...

Страница 22: ...ings and brush es can cause premature wear down of the brush es and carbon buildup see SERVICE DATA GROUND FAULT ELEMENT 1 Set up CB 832 with a POWER ON OFF Switch in OFF position instrument displays...

Страница 23: ...OUTPUT CONTROL knob at maximum clockwise rotation return knob to zero and transfer output lead to the next higher voltage lesser current terminal Proceed with current adjustment as in Steps 10 and 11...

Страница 24: ...cloth can be dampened with an approved solvent that does not attack the finish or leave residue 2 Control Panel The control panel can be wiped clean with a soft dry cloth Do not wipe the meter lenses...

Страница 25: ...SRO number will be assigned for proper handling of the unit when it arrives at the factory If desired a letter with the SRO number and instructions can be provided Provide the factory with model numbe...

Страница 26: ...mps and shocks of shipping via common commercial carrier For example you may wish to reship your unit to Multi Amp for annual calibration certification OPERATIONAL ERRORS TROUBLESHOOTING Some operatio...

Страница 27: ...ts connector has come loose from the PCB d Triac failure 5 Same as above will not initiate in N O or N C Contacts mode a Faulty test leads b Incorrect test scheme for stop mode selected c Contacts bei...

Страница 28: ...quipment which has damage or cause of defect due to accident negligence improper operation faulty installation by the purchaser or improper service or repair by any person company or corporation not a...

Страница 29: ...Part 12470 Rev 2 3 25 99 26 SECTION V SCHEMATICS...

Отзывы: