background image

5

Troubleshooting

100 SERIES COLD CLIMATE FLUSHING SYSTEM

TROUBLESHOOTING THE CONTROLLER

TROUBLESHOOTING THE UNIT

The Hydro-Guard® Unit  
will not shut off: 
Possible Causes

•  The solenoid is stuck in the 

open position or debris is 
interfering with operation of 
plunger.

•  Batteries weak or dead.
•  Connection loss from battery 

box to solenoid.

•  The solenoid is loose or there is 

debris In the plunger.

•  There is a hole in or debris 

around the diaphragm or in the 
valve screen.

If your Hydro-Guard® Unit does not 
activate: 
Possible Causes 

•  Water pressure off or low.
•  Batteries weak or dead.
•  Connection loss from controller 

to solenoid.

•  Solenoid not working properly.
•  Obstruction In flow of water.

Try this Correction 

•  Check if curb stop is open.
•  Change batteries.
•  Check connections for corrosion, 

breaks, or lack of connection.

•  Run a manual flush and confirm 

the solenoid plunger is kicking 
out and pulling back in by 
listening for a click. 

•  Check to make sure the flow 

control knob is open on the 
valve OR check the pipes for 
obstructions OR check the valve.

Try this Correction 

•  Run a manual flush for 1 minute.
•  Change batteries.
•  Check connections for corrosion, 

breaks, or lack of connection.

•  Check the adapters and solenoid 

for debris- Run the electrical 
systems check.

•  Refer to valve troubleshooting for 

possible corrective measures.

PROBLEM

CA 

CAUSE 

USE C

SOLUTION

Controller does not flush as desired

Water at main water supply is shut off

Check main supply valve

Battery dead

Replace battery

Controller set to OFF

Set controller to desired program

Controller improperly programmed

Check program and clock settings

Blank display

Battery dead

Replace battery

Water does not turn off

Overlapping programming

Review all programming and edit any 
program that is in conflict with desired  
off schedule 
Clear all programming in memory  
and reset

Programmer not communicating

Check Programming 
Run Manual On/Off with solenoid 
removed from valve (hold finger or object 
over solenoid plunger to prevent plunger 
from dislodging from solenoid body)
Check wiring for damage and connectors 
to ensure proper connection  
(red to red & black to black)

Содержание HUDRO-GUARD 100 Series

Страница 1: ...y valve has been closed verified and secured and internal piping pressure has been relieved 4 Always use all necessary safety equipment and follow all recommended procedures when installing operating and maintaining the Hydro Guard Automatic Flushing Device 5 Perform annual safety inspections and replace worn or defective parts 6 Operate the Hydro Guard Automatic Flushing Device only when fully in...

Страница 2: ...Unit with clean fill and or 57 stone Backfilling should be accomplished in 6 compacted lifts Check that the Unit is level flow away from the Hydro Guard Flushing Unit or to be absorbed by the surrounding soil 6 After installation is complete sod the area around the Hydro Guard Unit or take other steps in order to prevent erosion Inspect the area immediately around the Unit in order to ensure that ...

Страница 3: ...d to the internal memory on the Smartphone Tablet 100 Series Cold Climate Requires Bluetooth Controller The BL KR battery powered irrigation module communicates with the K Rain BL Application on a Smartphone or Tablet by using Bluetooth SMART 4 0 low energy on an iPhone with iOS version 7 minimum or an Android phone tablet with Marshmallow version 6 0 or higher Important CAUTION For use only with ...

Страница 4: ... off and secured 100 Series Cold Climate Battery Replacement 1 Shut off water supply to unit 2 Use HG A2023 Security Tool to unlock and remove protective Exterior Housing Cover 3 Unscrew protective cap from gray Programming Interface which is located at top of unit 4 Extract battery harness and remove old battery dispose of battery appropriately 5 Connect fresh industrial grade 9 volt lithium or a...

Страница 5: ...knob is open on the valve OR check the pipes for obstructions OR check the valve Try this Correction Run a manual flush for 1 minute Change batteries Check connections for corrosion breaks or lack of connection Check the adapters and solenoid for debris Run the electrical systems check Refer to valve troubleshooting for possible corrective measures PROBLEM CA CAUSE USE C SOLUTION Controller does n...

Страница 6: ...bly 3 546521 Sample Valve Assembly 4 546329 Riser Assembly 5 546519 Dechlorination System 6 HG S316 Stainless Steel Housing Bracket 7 545729 Centering Star 8 HG S126 Insulation Star Sub Assembly 9 HG S128 Freeze Protection System Sub Assembly 10 545729 Centering Star 11 545738 Splash Pad 12 HG 13105 Latching Rods x 26 13 HG S124 Latching Solenoid Sub Assembly 14 HG S325 Control Valve Sub Assembly ...

Страница 7: ...7 Notes 100 SERIES COLD CLIMATE FLUSHING SYSTEM ...

Страница 8: ...r Products Inc All Rights Reserved The trademarks logos and service marks displayed in this document are the property of Mueller Water Products Inc its affiliates or other third parties Products marked with a section symbol are subject to patents or patent applications For details visit www mwppat com These products are intended for use in potable water applications Please contact your Mueller Sal...

Отзывы: