hydro-guard
®
remote Pressure Monitoring System
operating Instructions
• MAINTENANCE function: The
Hydro-Guard
®
Pressure Monitoring
System allows for the scheduling of
an immediate response log report,
referenced as the MAINTENANCE
mode. This mode can be scheduled
or operated on an “as needed”
basis.
• TRANSIENT MONITORING
function: The Hydro-Guard
®
Pressure Monitoring System has
the ability to monitor for transient
pressures (up to 256 readings per
second). This function must be
scheduled. To schedule a transient
monitoring session open the Device
• Data Upload/CONNECT function:
The Hydro-Guard
®
Pressure
Monitoring System has been pre-
programmed for one data upload
per day (default). This setting can
be modified to upload data weekly,
daily, or up to 24 times per day. To
modify the number of data uploads
open the Device SETTINGS web
page and locate the calendar
application at the lower section of
the management screen. Using the
blue PLUS button, open the drop
down navigation. Select CONNECT
to select the date(s) and time(s) to
initiate a data upload.
SETTINGS web page and locate
the calendar application at the lower
section of the management screen.
Using the blue PLUS button,
open the drop down navigation.
Select PRESSURE-TRANSIENT
CAPTURE. The select the date(s)
and time(s) to schedule the Device
to measure and log transient activity.
WARNING: Operating in
the PRESSURE-TRANSIENT
CAPTURE mode for more than
thirty (30) days during the life
of the Device can reduce the
Device’s overall battery life.
EDIT PAGE: From the “Edit Device” menu the viewer can select any existing Device to be edited. Selecting the “Edit”
tab will advance the viewer to the edit screen where the viewer can view or customize the “Device’s” management and
sampling parameters. On the administrator screen (above), the customer can enter or change alert levels.
!