113601 – AL Gas Valve 1 feedback
Red alarm. Initiated by SAM.
Cause
Corrective action
Feedback signal from valve 1
does not correspond with
setpoint signal.
u
Check valve 1 and cabling.
113902 – SS Local Initiated Emerg. Stop
Red alarm. Initiated by SAM.
Cause
Corrective action
Emergency stop detected.
Emergency stop was released
manually (button), or ignition
system reported overspeed.
u
1.4540.009 – Zero Pressure Detected
Yellow alarm. Initiated by TecJet.
Cause
Corrective action
No gas pressure/gas flow
detected.
u
Check gas pressure.
1.4540.010 – Zero Flow Detected
Yellow alarm. Initiated by TecJet.
Cause
Corrective action
No gas pressure/gas flow
detected.
u
Check gas pressure.
1.4540.011 – Flow Not Reached
Red alarm. Initiated by TecJet.
Cause
Corrective action
No gas flow detected.
1. Check inlet and outlet.
2. Check gas pressure, gas quality, gas filter, gas line for
obstruction.
3. Check engine for overloading.
1.4540.012 – Valve Position Error
Red alarm. Initiated by TecJet.
Cause
Corrective action
Hardware not ready for
operation.
u
Restart TecJet.
MS150097/01E 2013-10
| Troubleshooting | 67