4.16 Emergency stop from LOP
NOTICE
An emergency stop causes extreme stress to the engine plant.
Risk of overheating, damage to components!
• Initiate emergency stop only in emergency situations.
Emergency stop from LOP
Item
Measure
LOP
Open cap of illuminated EMERGENCY STOP pushbutton (→ Page 52).
LOP
Press EMERGENCY STOP illuminated pushbutton.
•
Engine is stopped by disconnecting the power supply to the ECU.
•
On engines with emergency-air shutoff flaps: flaps close;
•
EMERGENCY STOP illuminated pushbutton flashes. Horn, flashing
lamp etc. are tripped.
After emergency stop from LOP
Item
Measure
LOP
Press ALARM ACKNOWLEDGE illuminated pushbutton (→ Page 52).
•
Audible and visual signalization stops.
LOP
Press ALARM ACKNOWLEDGE button again.
•
Power supply to ECU is provided;
•
Alarm has been acknowledged.
Engine
On engines with emergency-air shutoff flaps: open flaps.
•
Engine is ready for starting.
MS150046/02E 2013-07 | Operation | 69
TIM-ID: 0000002314 - 004