454 – SS Power Reduction Active
CAN message
Cause
Corrective action
Alarm is only available as a
separate CAN message, power
reduction is active.
1. Observe any other messages.
2. Determine and rectify cause of power reduction.
470 – SD T-ECU
Yellow alarm; warning
Cause
Corrective action
Temperature sensor for engine
governor faulty; short circuit or
wire break.
u
Check sensor and wiring, replace as necessary (→ Page 149).
471 – SD HP Fuel Control Block
Yellow alarm; warning
Cause
Corrective action
Control of HP fuel control block
faulty; short circuit or wire
break.
u
Check sensor and wiring, replace as necessary (→ Page 149).
474 – AL Wiring FO
Yellow alarm; warning
Cause
Corrective action
Line break or short circuit at FO
channel.
u
Check wiring (→ Page 149).
476 – AL Crash Rec. Init. Error
Yellow alarm; warning
Cause
Corrective action
Initialization error of crash
recorder.
u
Check settings with DiaSys.
478 – AL Comb. Alarm Yel (Plant)
Yellow alarm; warning
Cause
Corrective action
Combined alarm initiated by
plant.
u
Observe any other messages.
70 | Troubleshooting | MS15042/00E 2014-10