
Remedy the cause, re-enable starting
Item
Measure
Engine control system
Determine cause for emergency stop and take remedial action; if the fault
cannot be corrected, contact Service.
Fault acknowledgment is possible in engine stop mode only . Automatic se-
lection and remote start immediately following an emergency engine stop is
not admissible.
Plant control system
An extended scavenging phase with the ignition off precedes engine starting
when selected again following an emergency engine stop. Suitable exhaust
gas ventilation equipment shall be provided in the facility to ensure that the
exhaust gas system downstream of the engine is safely purged.
• A contact is provided to request the ventilation system in the scavenging
phase.
Note:
Gas train
• The gas control system shall be equipped with an SAV (safety shut-off
valve) when using gas control systems with inlet pressures in excess of
0.1 bar. If the SAV is tripped by an EMERGENCY STOP it shall be reset
manually. SAV tripping is not indicated by the engine.
Table 36: Remedy the cause, re-enable starting
50 | Operation | MS150104/02E 2016-11
TIM-ID: 0000043159 - 003