363 – AL Stop Power Stage
ZKP-Number: 1.8004.560
Red alarm; engine stop
Cause
Corrective action
Internal electronic fault,
electronics possibly faulty.
1. Check wiring (→ Page 119).
2. Acknowledge alarm.
3. Restart engine.
4. Request towing locomotive if required.
365 – AL Stop MV-Wiring Ground (Injector Amplifier Ground)
ZKP-Number: 1.8004.561
Red alarm; engine stop
Cause
Corrective action
Injector wiring fault.
1. Check wiring (→ Page 119).
2. Acknowledge alarm.
3. Restart engine.
4. Request towing locomotive if required.
381 – AL Wiring TOP 1
ZKP-Number: 2.8006.638
Yellow alarm; warning
Cause
Corrective action
Short circuit or wire break on
transistor output 1 plant-side 1
(TOP 1).
u
Check wiring to plant (→ Page 119).
382 – AL Wiring TOP 2
ZKP-Number: 2.8006.639
Yellow alarm; warning
Cause
Corrective action
Short circuit or wire break on
transistor output 2 plant-side
(TOP 2).
u
Check wiring to plant (→ Page 119).
383 – AL Wiring TOP 3
ZKP-Number: 2.8006.640
Yellow alarm; warning
Cause
Corrective action
Short circuit or wire break on
transistor output 3 plant-side
(TOP 3).
u
Check wiring to plant (→ Page 119).
MS15033/02E 2015-02
| Troubleshooting | 61
TIM-ID: 0000047144 - 003