182 – AL CAN Wrong Parameters
ZKP-Number: 2.0500.682
Yellow alarm; warning
Cause
Corrective action
Incorrect parameter values
entered in data record.
u
Contact Service.
183 – AL CAN No PU-Data
ZKP-Number: 2.0500.683
Yellow alarm; warning
Cause
Corrective action
The selected CAN mode
initializes communication by
means of the PU data module.
However, the required PU data
module is not available or not
valid.
1. Check devices connected to CAN.
2. Contact Service.
184 – AL CAN PU-Data Flash Error
ZKP-Number: 2.0500.684
Yellow alarm; warning
Cause
Corrective action
A programming error occurred
when attempting to copy a
received PU data module into
the Flash module.
u
Contact Electroncs Service.
186 – AL CAN1 Bus Off
ZKP-Number: 2.0500.686
Yellow alarm; warning
Cause
Corrective action
CAN controller 1 is in "Bus-Off"
status.
1. Check CAN bus for short circuit, rectify short circuit as
necessary.
2. Check shielding, improve shielding as necessary.
187 – AL CAN1 Error Passive
ZKP-Number: 2.0500.687
Yellow alarm; warning
Cause
Corrective action
CAN controller 1 has signaled a
warning.
1. Check CAN bus for short circuit, rectify short circuit as
necessary.
2. Check shielding, improve shielding as necessary.
50 | Troubleshooting | MS15033/02E 2015-02
TIM-ID: 0000047144 - 003